Plan Review Details - Permit 12100555
Plan Review Stops For Permit 12100555
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-05-01 Cont ID  
Sent By jwitmer Date 2013-05-01 Time 12:54 Rev Time 0.00
Received By jwitmer Date 2013-05-01 Time 11:56 Sent To  
Notes
2013-05-01 12:43:23BUILDING PLAN REVIEW
 PERMIT: 12100 555
 ADD: 1721 PALM BEACH LAKES
 CONT: EMJ CORP
 TEL: (423)855-1550
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) PROVISO: COMPONENTS AND CLADDING WILL BE CONSIDERED
 TO BE A REVISION UNDER SEPERATE REVIEW & ASSOCIATED
 FEES.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-04-04 Cont ID  
Sent By jwitmer Date 2013-04-04 Time 13:06 Rev Time 0.00
Received By jwitmer Date 2013-04-01 Time 16:39 Sent To  
Notes
2013-04-04 13:26:14BUILDING PLAN REVIEW
 PERMIT: 12100 555
 ADD: 1721 PALM BEACH LAKES
 CONT: EMJ CORP
 TEL: (423)855-1550
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: 04/04/2013
 ACTION: DENIED
  
 1-2 COMPLIED.
  
 3A) OCCUPANT LOADS FOR J-10- COMPLIED.
  
 3B) OCCUPANT LOAD FOR J-09 STILL HAS ISSUES, THE TOTAL
 SQUARE FOOTAGE THAT CONTRIBUTES TO THE EXIT PASSAGEWAY
 IS 68,986 SQ FT, DIVIDE BY 30 = 2299.53, OR 29300
 OCCUPANTS. 2300 /2= 1150 OCCUPANTS GOING OUT THE EXIT
 PASSAGE WAY.
 DOOR 9-45 (2) 2-10 CLEAR 64" 320 OCCUPANTS
 DOOR 9-16 (2) 2-10 CLEAR 64" 320 OCCUPANTS
 DOOR 9-61 (2) 3-0 CLEAR 68" 340 OCCUPANTS
 980 OCCUPANTS TOTAL
  
 1150 OCCUPANTS
 -980 OCCUPANTS
 170 OCCUPANTS STILL NEED EXITING THROUGH THESE OPENINGS
  
 4) COMPLIED.
  
 5) PROVISO:
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) PROVISO: COMPONENTS AND CLADDING WILL BE CONSIDERED
 TO BE A REVISION UNDER SEPERATE REVIEW & ASSOCIATED
 FEES.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS RESONCE TO # 12 .
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 8) COMPLIED.
  
 9) COMPLIED: THRESHOLD DOCUMENTS.
  
 10) COMPLIED.
  
 11) 2ND REQUEST NO COMMENT RESPONCEIT JUMPS FROM 8 TO
 12. SHEET C510 PAVING DOES NOT INDICATE THE LOADING
 ZONE, OR DROPPED CURB NOR DOES DETAIL 4 SHEET A 407.
 2010 FL ACCESSIBILITY CODE
 503.1 GENERAL.
 PASSENGER LOADING ZONES SHALL COMPLY WITH 503.
  
 503.2 VEHICLE PULL-UP SPACE.
 PASSENGER LOADING ZONES SHALL PROVIDE A VEHICULAR
 PULL-UP SPACE 96 INCHES (2440 MM) WIDE MINIMUM AND 20
 FEET (6100 MM) LONG MINIMUM.
  
 503.3 ACCESS AISLE.
 PASSENGER LOADING ZONES SHALL PROVIDE ACCESS AISLES
 COMPLYING WITH 503 ADJACENT TO THE VEHICLE PULL-UP
 SPACE. ACCESS AISLES SHALL ADJOIN AN ACCESSIBLE ROUTE
 AND SHALL NOT OVERLAP THE VEHICULAR WAY
  
 503.3.1 WIDTH.
 ACCESS AISLES SERVING VEHICLE PULL-UP SPACES SHALL BE
 60 INCHES (1525 MM) WIDE MINIMUM
  
 503.3.2 LENGTH.
 ACCESS AISLES SHALL EXTEND THE FULL LENGTH OF THE
 VEHICLE PULL-UP SPACES THEY SERVE.
  
 503.3.3 MARKING.
 ACCESS AISLES SHALL BE MARKED SO AS TO DISCOURAGE
 PARKING IN THEM.
  
 503.4 FLOOR AND GROUND SURFACES.
 VEHICLE PULL-UP SPACES AND ACCESS AISLES SERVING THEM
 SHALL COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE
 SAME LEVEL AS THE VEHICLE PULL-UP SPACE THEY SERVE.
 CHANGES IN LEVEL ARE NOT PERMITTED.
  
 EXCEPTION: SLOPES NOT STEEPER THAN 1:48 SHALL BE
 PERMITTED.
  
 503.5 VERTICAL CLEARANCE.
 VEHICLE PULL-UP SPACES, ACCESS AISLES SERVING THEM, AND
 A VEHICULAR ROUTE FROM AN ENTRANCE TO THE PASSENGER
 LOADING ZONE, AND FROM THE PASSENGER LOADING ZONE TO A
 VEHICULAR EXIT SHALL PROVIDE A VERTICAL CLEARANCE OF
 114 INCHES (2895 MM) MINIMUM.
  
 12) PROVISO: SKYLIGHT PRODUCT APPROVALS TO BE SUBMITTED
 AS A REVISION, SEE COMMENT # 6.
  
 13 A-B) PROVISO: SPECIALTY ENGINEER WILL DESIGN FRAMING
 DETAILS, TO BE REVIEWED BY STRUCTURAL ENGINEER BEFORE
 SUBMITTAL TO CITY FOR REVIEW.
  
 14) COMPLIED.
  
 15) COMPLIED.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-26 Cont ID  
Sent By jwitmer Date 2013-02-26 Time 12:41 Rev Time 0.00
Received By jwitmer Date 2013-02-08 Time 15:34 Sent To  
Notes
2013-02-25 14:17:14BUILDING PLAN REVIEW
 PERMIT: 13030276
 ADD: 3401 PARKER AVE
  
 INTERACTIVE WATER FEATURE ONLY!!!!!
  
 CONT: HEDRICK BROTHERS
 CONTACT: DON JONES
 TEL: (561)689-8880
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 INTERACTIVE WATER FEATURE ONLY!!!!!
 BUILDING PROVISO:
  
 1) PLEASE PROVIDE COMPLIANCE WITH SECTION 424.1.9.8.6.9
 OF THE 2010 FBC-B BEFORE THE INTERACTIVE WATER FEATURE
 WILL BE ABLE TO RECEIVE A CERTIFICATE OF COMPLETION.
 2010 FBC-B 424.1.9.8.6.9 IWFS SHALL BE FENCED IN THE
 SAME FASHION AS WADING POOLS AS NOTED IN SECTION
 424.1.7.7.
 424.1.7.7 WADING POOL DECKS.
 WHEN ADJACENT TO SWIMMING POOLS, WADING POOLS SHALL BE
 SEPARATED FROM THE SWIMMING POOL BY BARRIER OR A FENCE
 OF A MINIMUM OF 48 INCHES (1219 MM) IN HEIGHT WITH
 SELF-LATCHING AND SELF-CLOSING GATES. WHEN ADJACENT TO
 AREAS LESS THAN ONE FOOT (305 MM) DEEP OF ZERO DEPTH
 ENTRY POOLS, THE FENCE OR EFFECTIVE BARRIER IS REQUIRED
 IF THE WATER EDGES ARE LESS THAN 40 FEET (12 192 MM)
 APART.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-05-06 Cont ID  
Sent By dharvey Date 2013-05-06 Time 10:07 Rev Time 0.00
Received By dharvey Date 2013-05-06 Time 10:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-04-01 Cont ID  
Sent By rlecky Date 2013-04-01 Time 11:22 Rev Time 0.00
Received By rlecky Date 2013-04-01 Time 11:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-03-08 Cont ID  
Sent By rlecky Date 2013-03-11 Time 17:24 Rev Time 0.00
Received By rlecky Date 2013-03-04 Time 12:34 Sent To  
Notes
2013-03-08 17:29:24 
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2013-03-06 Cont ID  
Sent By mgonzale Date 2013-03-06 Time   Rev Time 1.00
Received By mgonzale Date 2013-03-06 Time   Sent To Z
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2013-05-03 Cont ID  
Sent By rferguso Date 2013-05-03 Time 12:30 Rev Time 0.00
Received By rferguso Date 2013-05-03 Time 12:30 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2013-04-06 Cont ID  
Sent By wjolin Date 2013-04-06 Time 12:40 Rev Time 0.00
Received By wjolin Date 2013-03-28 Time 09:32 Sent To  
Notes
2013-03-28 13:14:161721 PALM BEACH LAKES BOULEVARD - 10 BUILDINGS IN MALL
 PERMIT #12100555
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAIL COMMENT: REFER TO BUILDING PLAN REVIEW COMMENT #3B
 REGARDING EXIT PASSAGEWAY.
  
  
 *****PROVISO - THE CIVIL/SITE PLANS SHOW THE ENTIRE
 MALL SITE FOR REFERENCE AND CLARIFICATION PURPOSES
 ONLY: THE FOLLOWING COMMENTS MAY APPLY TO SITE WORK
 LOCATED OUTSIDE THE SCOPE OF THIS PERMIT
 (#12100555).*****
 REPEAT COMMENTS:
 SHEET C403 & C405: NO FIRE LANE CURBS OR SIGNS LOCATED
 ON PLAN FOR "H" BUILDINGS. INDICATE FIRE LANES ON BOTH
 FRONT AND REAR OF BUILDINGS.
  
 SHEET C602: FIRE HYDRANTS WILL NEED TO BE INSTALLED AND
 MAINTAINED WITH WORKING CLEARANCES OF 7'-6" TO THE
 FRONT/SIDES AND 4'-0" TO THE REAR. ANY PARKING SPACES
 LOCATED WITHIN THIS BUFFER ZONE WILL NEED TO BE
 INDICATED AS "NO PARKING" STALLS.
  
 SHEET C602: FIRE DEPARTMENT CONNECTION FOR FUTURE
 BUILDING "PBA #5" SHALL BE LOCATED WITHIN 150 FEET OF A
 FIRE HYDRANT.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-03-28 Cont ID  
Sent By wjolin Date 2013-03-18 Time 09:31 Rev Time 0.00
Received By wjolin Date 2013-03-18 Time 11:38 Sent To  
Notes
2013-03-18 11:40:591721 PALM BEACH LAKES BOULEVARD - 10 BUILDINGS IN MALL
 PERMIT #12100555
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REVIEW #1 COMMENT TO BE ELIMINATED:
 FIRE ALARM: FIRE ALARM NOTIFICATION SHALL BE
 ACCOMPLISHED WITH PRE-RECORDED VOICE ANNOUNCEMENTS FOR
 ALL MALL BUILDINGS. PROVIDE SPEAKER/STROBE APPLIANCES
 THROUGHOUT.
 (NOTE: THIS FIRE REVIEW COMMENT IS BEING RETRACTED DUE
 TO ADDITIONAL CODE RESEARCH, NFPA 101 INDICATES THAT
 VOICE ANNOUNCEMENTS SHALL BE PERMITTED (NOT REQUIRED).
  
  
 REVIEW #1 COMMENTS:
 SHEET C403 & C405: NO FIRE LANE CURBS OR SIGNS LOCATED
 ON PLAN FOR "H" BUILDINGS. INDICATE FIRE LANES ON BOTH
 FRONT AND REAR OF BUILDINGS.
  
 SHEET C602: FIRE HYDRANTS WILL NEED TO BE INSTALLED AND
 MAINTAINED WITH WORKING CLEARANCES OF 7'-6" TO THE
 FRONT/SIDES AND 4'-0" TO THE REAR. ANY PARKING SPACES
 LOCATED WITHIN THIS BUFFER ZONE WILL NEED TO BE
 INDICATED AS "NO PARKING" STALLS.
  
 SHEET C602: FIRE DEPARTMENT CONNECTION FOR FUTURE
 BUILDING "PBA #5" SHALL BE LOCATED WITHIN 150 FEET OF A
 FIRE HYDRANT.
  
 SHEET LS1: THE OCCUPANT LOAD FACTOR SHOULD BE 30 SQ.FT.
 PER PERSON (IN LIEU OF 50 SQ.FT. PERSON) FOR MERCANTILE
 OCCUPANCIES WITH SALES AREAS ON THE STREET LEVEL. THIS
 OCCUPANT LOAD FACTOR WILL RESULT IN A REVISED OCCUPANT
 LOAD OF 14,362 PERSONS FOR THE MERCANTILE OCCUPANCY AND
 AN OVERALL OCCUPANT LOAD OF 14,937 PERSONS.
  
 SHEET LS2 AND SEVERAL OTHER SHEETS: THE OCCUPANT LOAD
 FACTOR SHOULD BE 30 SQ.FT. PER PERSON (IN LIEU OF 50
 SQ.FT. PERSON) FOR MERCANTILE OCCUPANCIES WITH SALES
 AREAS ON THE STREET LEVEL.
  
 SHEET LS2 AND SEVERAL OTHER SHEETS: IN BUILDINGS
 PROTECTED THROUGOUT BY AN AUTOMATIC SPRINKLER SYSTEM,
 DEAD-END CORRIDORS FOR BOTH MERCANTILE AND STORAGE
 OCCUPANCIES SHALL NOT EXCEED 20 FEET PER SECTION
 36.2.5.2.1 AND SECTION 42.2.5 (NFPA 101 - W/ FLORIDA
 AMENDMENTS).
  
 SHEET LS2 AND SEVERAL OTHER SHEETS: STENCIL/PAINT REAR
 EXIT DOORS, "EXIT DOOR - DO NOT BLOCK."
  
 SHEET LS7: PROVIDE ADDITIONAL EXIT SIGNS IN LONG
 CORRIDORS. PER SECTION 7.10.1.5.2 (NFPA 101), SIGNS
 SHALL BE PLACED SUCH THAT NO POINT IN A CORRIDOR IS IN
 EXCESS OF THE RATED VIEWING DISTANCE OR 100 FEET,
 WHICHEVER IS LESS, FROM THE NEAREST SIGN.
  
 SHEET LS7: PROVIDE ADDITIONAL EXIT SIGN NEAR ASSEMBLY
 OCCUPANCY BATHROOMS.
  
 SHEET A507: FOR ASSEMBLY OCCUPANCIES (FOOD COURT) WITH
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS, PANIC HARDWARE
 SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH.
 NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT
 BE RELEASED BY THE PANIC HARDWARE.
  
 DOOR SCHEDULES: ANY DOORS FEATURING A THUMB-TURN STYLE
 LOCK SHALL ALSO BE EQUIPPED WITH A READILY
 DISTINGUISHABLE LOCK/UNLOCK INDICATOR.
  
 WALL DETAILS: EACH FIRE-RATED BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 WALL DETAILS: ALL EXIT ACCESS CORRIDORS AND EXIT
 PASSAGEWAYS SHALL HAVE SIGNS OR STENCILING READING
 "EXIT CORRIDOR - NO STORAGE PERMITTED." CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-02-25 Cont ID  
Sent By wjolin Date 2013-02-25 Time 15:27 Rev Time 0.00
Received By wjolin Date 2013-02-07 Time 10:08 Sent To  
Notes
2013-02-07 10:52:011721 PALM BEACH LAKES BOULEVARD - 10 BUILDINGS IN MALL
 PERMIT #12100555
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET C403 & C405: NO FIRE LANE CURBS OR SIGNS LOCATED
 ON PLAN FOR "H" BUILDINGS. INDICATE FIRE LANES ON BOTH
 FRONT AND REAR OF BUILDINGS.
  
 SHEET C602: FIRE HYDRANTS WILL NEED TO BE INSTALLED AND
 MAINTAINED WITH WORKING CLEARANCES OF 7'-6" TO THE
 FRONT/SIDES AND 4'-0" TO THE REAR. ANY PARKING SPACES
 LOCATED WITHIN THIS BUFFER ZONE WILL NEED TO BE
 INDICATED AS "NO PARKING" STALLS.
  
 SHEET C602: FIRE DEPARTMENT CONNECTION FOR FUTURE
 BUILDING "PBA #5" SHALL BE LOCATED WITHIN 150 FEET OF A
 FIRE HYDRANT.
  
 SHEET LS1: THE OCCUPANT LOAD FACTOR SHOULD BE 30 SQ.FT.
 PER PERSON (IN LIEU OF 50 SQ.FT. PERSON) FOR MERCANTILE
 OCCUPANCIES WITH SALES AREAS ON THE STREET LEVEL. THIS
 OCCUPANT LOAD FACTOR WILL RESULT IN A REVISED OCCUPANT
 LOAD OF 14,362 PERSONS FOR THE MERCANTILE OCCUPANCY AND
 AN OVERALL OCCUPANT LOAD OF 14,937 PERSONS.
  
 SHEET LS2 AND SEVERAL OTHER SHEETS: THE OCCUPANT LOAD
 FACTOR SHOULD BE 30 SQ.FT. PER PERSON (IN LIEU OF 50
 SQ.FT. PERSON) FOR MERCANTILE OCCUPANCIES WITH SALES
 AREAS ON THE STREET LEVEL.
  
 SHEET LS2 AND SEVERAL OTHER SHEETS: IN BUILDINGS
 PROTECTED THROUGOUT BY AN AUTOMATIC SPRINKLER SYSTEM,
 DEAD-END CORRIDORS FOR BOTH MERCANTILE AND STORAGE
 OCCUPANCIES SHALL NOT EXCEED 20 FEET PER SECTION
 36.2.5.2.1 AND SECTION 42.2.5 (NFPA 101 - W/ FLORIDA
 AMENDMENTS).
  
 SHEET LS2 AND SEVERAL OTHER SHEETS: STENCIL/PAINT REAR
 EXIT DOORS, "EXIT DOOR - DO NOT BLOCK."
  
 SHEET LS7: PROVIDE ADDITIONAL EXIT SIGNS IN LONG
 CORRIDORS. PER SECTION 7.10.1.5.2 (NFPA 101), SIGNS
 SHALL BE PLACED SUCH THAT NO POINT IN A CORRIDOR IS IN
 EXCESS OF THE RATED VIEWING DISTANCE OR 100 FEET,
 WHICHEVER IS LESS, FROM THE NEAREST SIGN.
  
 SHEET LS7: PROVIDE ADDITIONAL EXIT SIGN NEAR ASSEMBLY
 OCCUPANCY BATHROOMS.
  
 SHEET A507: FOR ASSEMBLY OCCUPANCIES (FOOD COURT) WITH
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS, PANIC HARDWARE
 SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH.
 NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT
 BE RELEASED BY THE PANIC HARDWARE.
  
 DOOR SCHEDULES: ANY DOORS FEATURING A THUMB-TURN STYLE
 LOCK SHALL ALSO BE EQUIPPED WITH A READILY
 DISTINGUISHABLE LOCK/UNLOCK INDICATOR.
  
 WALL DETAILS: EACH FIRE-RATED BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 WALL DETAILS: ALL EXIT ACCESS CORRIDORS AND EXIT
 PASSAGEWAYS SHALL HAVE SIGNS OR STENCILING READING
 "EXIT CORRIDOR - NO STORAGE PERMITTED." CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 FIRE ALARM: FIRE ALARM NOTIFICATION SHALL BE
 ACCOMPLISHED WITH PRE-RECORDED VOICE ANNOUNCEMENTS FOR
 ALL MALL BUILDINGS. PROVIDE SPEAKER/STROBE APPLIANCES
 THROUGHOUT.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-02-25 Cont ID  
Sent By lwagner Date 2013-02-25 Time 14:30 Rev Time 0.00
Received By lwagner Date 2013-02-25 Time 13:29 Sent To  
Notes
2013-06-21 15:02:49SEPARATE GAS PERMIT REQUIRED

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2013-05-07 Time   Rev Time 0.00
Received By rregueir Date 2013-04-19 Time 14:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2013-04-15 Time   Rev Time 0.00
Received By rregueir Date 2013-03-22 Time 11:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-03-11 Time   Rev Time 0.00
Received By rregueir Date 2013-02-04 Time 14:52 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2012-12-13 Time   Rev Time 0.00
Received By rbrown Date 2012-12-13 Time 13:28 Sent To  
Notes
2012-12-13 13:28:11THE ASSESSED IMPACT FEES ARE OFFSET BY THE EXISTING USE
 CREDIT AS STATED IN THE FOLLOWING MESSAGE RECEIVED FROM
 WILLIE SWOOPE AT THE PALM BEACH COUNTY IMPACT FEE
 OFFICE:
  
 PURSUANT TO OUR CONVERSATION, PALM BEACH LAKES MALL
 APPLIED FOR AN IMPACT FEE ASSESSMENT ON NOVEMBER 20,
 2012 FOR REDEVELOPMENT OF THE EXISTING PROPERTY. THE
 TOTAL SQUARE FOOTAGE INVOLVED IN THIS PERMIT WAS
 465,705 SQUARE FEET. PALM BEACH COUNTY PR # MU
 2012-021414 WAS USED TO TRACK THE IMPACT FEE ASSESSMENT
 FOR THIS PROJECT. THE TOTAL FEES ASSESSED ARE LISTED
 BELOW:
  
 PUB BLDING - $111,597.29
 ROADS - $1,717,036.60
  
 THE FEES ABOVE WERE OFFSET BY AN EXISTING USE CREDIT
 (IFX-2012-102).
  
 PLSE CALL IF YOU HAVE QUESTIONS.
  
 WILLIE M. SWOOPE
 "SUNNY SKIES ON THE HORIZON"
 IMPACT FEE MANAGER
 FINANCIAL MANAGEMENT & BUDGET
 PALM BEACH COUNTY GOVERNMENT
 EMAIL: [email protected] OR [email protected]
 WEBSITE:WWW.PBCGOV.COM/PZB/IMPACTFEES/
 2300 N. JOG RD, WPB, FL 33411-2741
 (561)233-5025 / (561)656-7971(FAX)
 (561)233-5167 (ALT FAX)

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-05-06 Cont ID  
Sent By hmoser Date 2013-05-06 Time 11:32 Rev Time 0.00
Received By hmoser Date 2013-05-06 Time 11:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-04-03 Cont ID  
Sent By hmoser Date 2013-04-03 Time 10:49 Rev Time 0.00
Received By hmoser Date 2013-04-03 Time 10:45 Sent To  
Notes
2013-04-03 10:49:23REVISIONS REQUIRED
 PROVIDE INFORMATION FOR THE RTU UNITS
 ON THE ROOF PER SECTION 304.12 AREA SERVED.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-02-15 Cont ID  
Sent By hmoser Date 2013-02-15 Time 12:56 Rev Time 0.00
Received By hmoser Date 2013-02-15 Time 12:56 Sent To  
Notes
2013-02-15 13:21:57MECHANICAL PLANS DENIED
 1) PROVIDE DUCT SIZE FOR ALL DUCT
 SUPPLY RETURN AIR AND EXHAUST, TRANSFER DUCT.
 IN BUILDING # 10 PER SECTION 107 FBC 2010
 2) PROVIDE IDENTIFICATION FOR ALL RTU UNITS ON THE ROOF
 PER SECTION 304.12 AREA SERVED 2010 FBC (M)
 3) PAGE M221 OF THE PLANS REFER TO SECTION 304.11
 GUARDS AND
 501.2.1 LOCATION OF EXHAUST OUTLETS. 2010 FBC (M)
 4) PAGE M501 OF THE PLANS PROVIDE THE BOLT SIZE
 THROUGH THE ROOF ON THE PIPE SUPPORT DETAIL.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 5) PAGE 502 PROVIDE A DETAIL SHOWING
 CURB TO ROOF AND RTU TO CURB TIEDOWN (PROVIDE
 BOLT SIZE ON DETAIL)
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-03-27 Cont ID  
Sent By lwagner Date 2013-03-27 Time 10:30 Rev Time 0.00
Received By lwagner Date 2013-03-27 Time 10:18 Sent To  
Notes
2013-03-27 10:30:55PROVISO ADDRESSED

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-02-25 Cont ID  
Sent By lwagner Date 2013-02-25 Time 15:37 Rev Time 0.00
Received By lwagner Date 2013-02-11 Time 10:03 Sent To  
Notes
2013-02-11 10:38:49***PROVISO***
 1. MINIMUM SIZE IN ANY DIRECTION FOR SCUPPERS IS 4"
 1107.3 SIZING OF SECONDARY DRAINS.
 ...SCUPPERS SHALL NOT HAVE AN OPENING DIMENSION OF LESS
 THAN 4 INCHES (102 MM). THE FLOW THROUGH THE PRIMARY
 SYSTEM SHALL NOT BE CONSIDERED WHEN SIZING THE
 SECONDARY ROOF DRAIN SYSTEM.
  
 2. SHEET A403 & A404 - ONE AMBULATORY STALL IS REQUIRED
 IN EACH RESTROOM WITH 6 OR MORE WATER CLOSETS/ URINALS.
 213.3.1 TOILET COMPARTMENTS.
 WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE
 TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN
 ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH
 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH
 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE
 PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER
 CLOSETS TOTALS SIX OR MORE FIXTURES.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2013-05-07 Cont ID  
Sent By eschneid Date 2013-05-07 Time 16:03 Rev Time 10.00
Received By eschneid Date 2013-05-06 Time 11:04 Sent To  
Notes
2013-05-07 16:14:40PASSED W/PROVISOS
  
 1) PRIOR TO THE ISSUANCE OF THE FIRST CERTIFICATE OF
 OCCUPANCY, A REVISED FORMAL SITE PLAN SHALL BE
 SUBMITTED TO AND BE APPROVED BY THE PLANNING DIVISION.
 THE REVISED PLAN SHALL CORRECT ALL THE DISCREPANCIES
 BETWEEN THE CURRENTLY APPROVED FORMAL SITE PLAN AND THE
 APPROVED BUILDING PERMIT PLANS. STAFF HAS IDENTIFIED
 THE FOLLOWING DISCREPANCIES (THE REVISED PLANS SHALL
 ADDRESS ALL DISCREPANCIES, EVEN IF NOT LISTED BY STAFF
 BELOW) WHICH ARE NOT INCONSISTENT WITH THE DESIGN
 GUIDELINES:
  
 A. HEIGHTS OF PARAPETS AND TOWERS AND MISCELLANEOUS
 FACADE ELEMENTS.
 B. SCREEN WALLS FOR MECHANICAL EQUIPMENT ADJACENT TO
 SERVICE COURTS - SHORTER THAN APPROVED. PLEASE NOTE
 THAT PER THE DESIGN GUIDELINES, THE EQUIPMENT SHALL
 STILL BE SCREENED IF A LOWER HEIGHT IS PROVIDED.
 C. BUILDING SQUARE FOOTAGES PLANS AND THE TABLE.
 MAXIMUM APPROVED HAS NOT BEEN EXCEEDED.
 D. THE CHILDREN'S PLAY AREA. PLEASE NOTE THE REMOVAL OF
 THE MEDJOOL PALM TREE REQUIRES THAT A REVISED, CODE
 COMPLIANT LANDSCAPE PLAN SHALL BE SUBMITTED TO THE
 BUILDING DIVISION.
 E. NEW AND RELOCATED DOORWAYS, WALKWAYS, WALL OPENINGS
 AND FOUNDATION PLANTINGS. PLEASE NOTE THAT THE CHANGES
 TO THE LANDSCAPE REQUIRE THAT A REVISED, CODE COMPLIANT
 LANDSCAPE PLAN SHALL BE SUBMITTED TO THE BUILDING
 DIVISION.
 F. NEW AND RELOCATED COMPACTORS.
 G. SMART CART AND ATM LOCATIONS HAVE BEEN ADDED.
  
 2) SEPARATE PERMITS ARE REQUIRED FOR:
 A. SIGNAGE
 B. AWNINGS
 C. SHADE STRUCTURES
 D. SMART CART INSTALLATION
  
 3) PER THE FORMAL SITE PLAN APPROVAL, THE PALM TRAN
 FACILITY SHALL BE COMPLETED AND AVAILABLE FOR OPERATION
 BY PALM TRAN AND THE PARK AND RIDE SIGNS SHALL BE
 INSTALLED PRIOR TO THE ISSUANCE OF THE FIRST
 CERTIFICATE OF OCCUPANCY.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2013-04-12 Cont ID  
Sent By eschneid Date 2013-04-12 Time 11:01 Rev Time 10.00
Received By eschneid Date 2013-04-08 Time 16:25 Sent To  
Notes
2013-04-12 11:03:09FAILED
  
 PLEASE RESPOND TO COMMENTS IN WRITING.
  
 1) SOME PLAN SHEETS HAVE MULTIPLE VERSIONS OF THE SAME
 AREA SHOWN, BUT THE LOCATIONS OF SOME OF THE DEPICTED
 ITEMS DIFFER - THIS APPEARS TO BE A NOMENCLATURE ISSUE.
 CHANGES HAVE BEEN MADE TO SOME PLANS BUT NOT OTHERS.
 DESCRIPTIVE TAG LINES ON THE CIVIL PLAN POINT TO
 INCORRECT AREAS. PLEASE PROOF ALL SHEETS BEFORE THE
 RESUBMITTAL.
  
 2) PRIOR TO ZONING APPROVAL OF THE PERMIT, THE POLICE
 DEPARTMENT CRIME PREVENTION OFFICER SHALL HAVE APPROVED
 THE ATM LOCATIONS.
  
 3) REPEAT COMMENT: NONE OF THE SIDEWALKS IN FRONT OF
 SERVICE COURTS ARE SHOWN AS A PAVERED MATERIAL AS
 REQUIRED BY THE APPROVED SITE PLANS. THIS IS WITHIN THE
 LIMITS OF WORK.
  
 4) PARTIAL REPEAT COMMENT: THE BICYCLE RACKS SHOWN BY
 THE WPB POLICE OFFICE ARE SHOWN IN DIFFERENT LOCATIONS
 ON DIFFERENT PLANS. THE INTENT SEEMS TO BE TO PUT THEM
 BY POLICE DEPARTMENT OFFICE, BUT EX. SHEET
 0214.1-A204.1 BUILDING J5 FLOOR PLAN STILL SHOWS IT IN
 ENTRY CORRIDOR. ALL PLANS SHALL BE CONSISTENT.
  
 5) REPEAT COMMENT: PROVIDE THE DETAILS ON SERVICE COURT
 METAL DOORS. THE RESPONSE SAID THESE WERE PROVIDED, BUT
 UNABLE TO LOCATE.
  
 6) THE RELOCATED TRANSFORMER ADJACENT TO BUILDING J1 IS
 WITHIN VIEW IN THE SERVICE COURT OPENING. THE
 TRANSFORMER SHALL BE SCREENED IN ACCORDANCE WITH THE
 DESIGN GUIDELINES. THE DETAILS REFERENCED ON THE PLANS
 INDICATE THAT ONLY BOLLARDS SURROUND THE TRANSFORMER.
 AN OPAQUE BARRIER IS REQUIRED. PROVIDE DETAILS OF THE
 OPAQUE BARRIER ON THE PLANS. PLEASE NOTE THAT THIS
 TRANSFORMER IS SHOWN IN DIFFERENT LOCATIONS ON
 DIFFERENT PLANS.
  
 7) PARTIAL REPEAT COMMENT: THE FOUNDATION LANDSCAPE
 AREAS ACROSS FROM THE SERVICE COURT ENTRANCE FOR
 BUILDING J6 (SOUTH SIDE OF OPENING) AND BUILDING J7
 (EAST SIDE OF OPENING) ARE NOT FIVE (5) FEET PAST THE
 OPENING AS REQUIRED BY THE DESIGN GUIDELINES.
  
 8) THE MECHANICAL PLANS DO NOT SHOW THE AC EQUIPMENT IN
 THE SAME LOCATION AND/OR SIZE AS THE ROOF PLANS
 (BUILDING J3, J4 [MAY BE OLD LAYER], AND J7 [IT APPEARS
 THAT THERE IS AT LEAST ONE AC UNIT MISSING ON THE ROOF
 PLAN FOR BUILDING J7 - SHEET 0226-A226]). ALL PLANS
 SHALL BE CONSISTENT.
  
 9) THE SIGHT LINE STUDY DOES NOT ACCURATELY MEASURE THE
 WORST CASE SCENARIOS FOR EACH BUILDING OR HAVE OTHER
 ERRORS TO CORRECT AS LISTED BELOW (BUILDINGS/EXAMPLES
 NOT LISTED ARE CORRECT AND SHOULD NOT BE CHANGED):
  
 A. BUILDING J1: THE SITE LINE STUDY CALLS OUT A.1 AND
 A.2 ON THE PLANS YET ONLY SHOWS AN A EXAMPLE. THE
 EXAMPLE (ASSUMED TO BE A.2) NEEDS TO BE CORRECTED AS IT
 DOES NOT CALL OUT THE SIZE OF THE RTU (12.5 TONS),
 SHOWS THE 12.5 TON RTU NOT AT THE 54 INCHES HEIGHT, AND
 SHOWS THE UNIT IS BACK FARTHER FROM THE EDGE OF THE
 ROOF THEN IT IS SHOWN ON THE ROOF AND MECHANICAL PLANS.
 WHILE NO EXAMPLE WAS GIVEN FOR A.1, THE RTU ON THE
 MIDDLE AND NORTH PORTIONS OF THE BUILDING ARE THE 10
 TON UNITS AND ARE SET BACK FURTHER FROM THE PARAPET
 WALL.
  
 B. BUILDING J2: EXAMPLE D INCORRECTLY STATES THAT IT IS
 FROM THE EAST (WESTERN VIEW). THE RTU DOES NOT SHOW A
 SIZE, BUT IN THE WORST CASE IT IS A 12.5 TON RTU (ONE
 SHOWN ON ROOF). THE HEIGHT OF THE RTU THAT IS SHOWN IS
 ONLY AS TALL AS A 10 RTU.
  
 C. BUILDING J3: EXAMPLE E PICTURES AN RTU WITH NO SIZE,
 BUT IN THE WORST CASE IT IS A 12.5 TON RTU (ONE SHOWN
 ON ROOF, YET NOT IN LINE WITH THE E SIGHT LINE). THE
 HEIGHT OF THE RTU THAT IS SHOWN IS ONLY AS TALL AS A 6
 RTU. EXAMPLE F IS NOT NECESSARY AS THE WORST CASE CAN
 BE COVERED BY A REVISED E.
  
 D. BUILDING J6: THE MECHANICAL PLAN SPECIFIES 12.5 TON
 RTU, WHILE THE SIGHT LINE STUDY SHOWS 7.5 AND 8.5 RTU
 AND A NON-LABELED RTU. THE PLANS SHALL SHOW THE LARGEST
 UNIT THAT IS IN THE SIGHT LINE. EXAMPLE L SHOWS THE RTU
 SETBACK 15 FEET FROM THE PARAPET, WHILE THE MECHANICAL
 DRAWINGS SHOW A 10 FOOT SETBACK. ADDITIONALLY, THE
 PARAPET IS ONLY 23 FEET TALL. EXAMPLE M IS A 12.5 TON
 RTU AND SHALL BE LABELED AS SUCH.
  
 E. BUILDING J7: EXAMPLE N SHALL ALSO BE RUN TO SHOW ONE
 OF THE 12.5 BTU THAT IS BEHIND THE 23 FOOT PARAPET.
 EXAMPLE O INCORRECTLY USES A 6 TON RTU WHEN THE
 MECHANICAL PLAN SHOWS A 10 TON RTU, WHICH IS LARGER.
  
 F. BUILDING J8: EXAMPLE P SHOWS THE UNIT TOO FAR BACK
 FROM THE PARAPET. THERE ARE UNITS AS CLOSE AS 23 FEET
 FROM A 23 FOOT HIGH PARAPET IN THE EXAMPLE P AREA,
 WORST CASE SHALL BE SHOWN. EXAMPLE P SHALL ALSO BE
 EXPANDED TO SHOW THE 12.5 FOOT RTU SITUATION THAT
 EXISTS. EXAMPLE Q SHOWS THE RTU AT 52 FEET FROM THE
 PARAPET WHILE THE ROOF PLANS SHOW THE UNIT ONLY 47 FEET
 FROM THE PARAPET.
  
 10) PRIOR TO THE ISSUANCE OF THE FIRST CERTIFICATE OF
 OCCUPANCY, A REVISED FORMAL SITE PLAN SHALL BE
 SUBMITTED TO AND BE APPROVED BY THE PLANNING DIVISION.
 THE REVISED PLAN SHALL CORRECT ALL THE DISCREPANCIES
 BETWEEN THE CURRENTLY APPROVED FORMAL SITE PLAN AND THE
 APPROVED BUILDING PERMIT PLANS. STAFF HAS IDENTIFIED
 THE FOLLOWING DISCREPANCIES (THE REVISED PLANS SHALL
 ADDRESS ALL DISCREPANCIES, EVEN IF NOT LISTED BY STAFF
 BELOW) WHICH ARE NOT INCONSISTENT WITH THE DESIGN
 GUIDELINES:
  
 A. HEIGHTS OF PARAPETS AND TOWERS AND MISCELLANEOUS
 FACADE ELEMENTS.
  
 B. SCREEN WALLS FOR MECHANICAL EQUIPMENT ADJACENT TO
 SERVICE COURTS - SHORTER THAN APPROVED. PLEASE NOTE
 THAT PER THE DESIGN GUIDELINES, THE EQUIPMENT SHALL
 STILL BE SCREENED IF A LOWER HEIGHT IS PROVIDED.
  
 C. BUILDING SQUARE FOOTAGES PLANS AND THE TABLE.
 MAXIMUM APPROVED HAS NOT BEEN EXCEEDED.
  
 D. THE CHILDREN'S PLAY AREA. PLEASE NOTE THE REMOVAL OF
 THE MEDJOOL PALM TREE REQUIRES THAT A REVISED, CODE
 COMPLIANT LANDSCAPE PLAN SHALL BE SUBMITTED TO THE
 BUILDING DIVISION.
  
 E. NEW AND RELOCATED DOORWAYS, WALKWAYS, WALL OPENINGS
 AND FOUNDATION PLANTINGS. PLEASE NOTE THAT THE CHANGES
 TO THE LANDSCAPE REQUIRE THAT A REVISED, CODE COMPLIANT
 LANDSCAPE PLAN SHALL BE SUBMITTED TO THE BUILDING
 DIVISION.
  
 F. NEW AND RELOCATED TRANSFORMER (SEE COMMENT NO. 6 AND
 COMPACTORS.
  
 G. SMART CART AND ATM LOCATIONS HAVE BEEN ADDED.
  
 11) PER THE FORMAL SITE PLAN APPROVAL, THE PALM TRAN
 FACILITY SHALL BE COMPLETED AND AVAILABLE FOR OPERATION
 BY PALM TRAN AND THE PARK AND RIDE SIGNS SHALL BE
 INSTALLED PRIOR TO THE ISSUANCE OF THE FIRST
 CERTIFICATE OF OCCUPANCY.
  
 12) SEPARATE PERMITS ARE REQUIRED FOR:
 A. SIGNAGE
 B. AWNINGS
 C. PARKING LOT STRIPING
 D. SHADE STRUCTURES
 E. SMART CART INSTALLATION
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-03-07 Cont ID  
Sent By eschneid Date 2013-03-07 Time 16:44 Rev Time 10.00
Received By eschneid Date 2013-03-07 Time 16:44 Sent To  
Notes
2013-03-07 16:45:04FAILED
  
 PLEASE RESPOND TO COMMENTS IN WRITING.
  
 1) THE FORMAL SITE PLAN APPROVAL ISSUED FOR THE OUTLET
 BUILDINGS INCLUDED A CONDITION THAT, "THERE SHALL BE NO
 DOORS ON THE SOUTHERN FACADES OF THE OUTLET CENTER
 BUILDINGS (BUILDINGS J-7 AND J-8) OPPOSITE THE OPENINGS
 TO THE SERVICE BAYS." BLDGS J-7 AND J-8 HAVE DOORWAYS
 ACROSS FROM THE SERVICE BAY OPENING, WHICH IS NOT
 PERMITTED.
  
 2) THE FOLLOWING HAVE BEEN IDENTIFIED AS DISCREPANCIES
 BETWEEN THE APPROVED FORMAL SITE PLAN AND THE PROPOSED
 BUILDING PERMIT PLANS. WHILE STAFF RECOGNIZES THAT SOME
 CHANGES ARE INEVITABLE BETWEEN SITE PLAN APPROVAL AND
 BUILDING PERMIT PLANS, STAFF DOES NOT SUPPORT ALL OF
 THE PROPOSED CHANGES.
  
 A. THE EXTERIOR PARAPET HEIGHTS ON THE PROPOSED PLANS
 DO NOT MATCH THE EXTERIOR PARAPET HEIGHTS ON THE
 APPROVED FORMAL SITE PLAN. VARIOUS BUILDINGS HAVE
 LOWER, HIGHER OR BOTH CONDITIONS. IT IS NOT CONSISTENT
 TO ONE TYPE OF PARAPET, BUT RATHER THE HEIGHT
 DIFFERENCES APPLY TO EACH TYPE OF PARAPET. STAFF IS
 CONCERNED THAT THE LOWER PARAPETS NO LONGER PROVIDE
 ACCURATE SCREENING OF THE ROOFTOP MECHANICAL EQUIPMENT.
 SEE COMMENT #3 BELOW.
  
 B. NONE OF THE SIDEWALKS IN FRONT OF SERVICE COURTS ARE
 SHOWN AS A PAVERED MATERIAL AS REQUIRED BY THE APPROVED
 SITE PLANS.
  
 C. THE SERVICE COURT SCREEN WALLS ARE TWO (2) INCHES
 SHORTER THAN APPROVED.
  
 D. SOME OF THE PROPOSED SERVICE BAY OPENINGS ARE
 GREATER THAN THE APPROVED OPENING WIDTH, WHICH RESULTS
 IN THE REQUIRED SERVICE AREA LANDSCAPE NOT EXTENDING
 FIVE (5) FEET PAST THE END OF THE WALL OPENING.
  
 E. THE BICYCLE RACKS SHOWN BY THE WPB POLICE OFFICE ARE
 SHOWN IN A DIFFERENT LOCATION. IF IT THE BICYCLE RACKS
 ARE TO BE LOCATED TO THE WEST OF THE OFFICE, THEN THE
 WALKWAY DIMENSION, MEETING ADA WIDTH MINIMUM, SHALL BE
 SHOWN FROM THE END OF A PARKED BICYCLE (IE NOT THE
 RACK).
  
 F. THE VALET PICK-UP AREA IS DIFFERENT.
  
 G. PARKING LOT AREAS ARE DIFFERENT.
  
 H. A CHILDREN'S PLAY AREA HAS BEEN ADDED TO THE PLAN,
 WHICH REMOVES A MEDJOOL PALM TREE. WHERE IS THIS TREE
 BEING INSTALLED? A CODE COMPLIANT REVISED LANDSCAPE
 PLAN SHALL BE SUBMITTED TO THE BUILDING DIVISION.
  
 I. NEW AND RELOCATED DOORWAYS AND WALKWAYS HAVE ARE
 INCLUDED WITH BLDG J-3, J-5, J-6 AND J-8. THESE CHANGES
 IMPACT THE APPROVED FOUNDATION LANDSCAPE FOR THE OUTLET
 BUILDINGS AND SINCE LANDSCAPE IS BEING REMOVED, THE
 OVERALL SITE LANDSCAPE PERCENTAGE, WHICH WAS BARELY IN
 EXCESS OF THE REQUIRED 15% MINIMUM, MAY AFFECT THE
 REMAINDER OF THE SITE'S DEVELOPMENT. A CODE COMPLIANT
 REVISED LANDSCAPE PLAN SHALL BE SUBMITTED TO THE
 BUILDING DIVISION.
  
 J. FACADE ELEMENTS HAVE CHANGED ON SOME OF THE
 BUILDINGS.
  
 3) THE SECTION DRAWINGS SHOW SOME OF THE ROOF TOP
 MECHANICAL EQUIPMENT EXTENDING OVER THE HEIGHT OF THE
 PARAPET WALLS. PLEASE PROVIDE VERIFICATION THAT ALL THE
 ROOFTOP MECHANICAL EQUIPMENT WILL BE SCREENED.
  
 4) WHY IS THE BUS PARKING BAY BY BLDG J-2 BEING SHOW AS
 EXTENDING INTO THE PEDESTRIAN CROSS WALK?
  
 5) PLEASE EXPLAIN THE "SMART CART" AND HOW THIS AREA
 WILL LOOK & FUNCTION.
  
 6) THE PLANTER AT THE SOUTHWEST CORNER OF BLDG. J-5
 APPEARS TO BE BRICKED OVER ON THE SITE PLAN.
  
 7) THERE ARE NEW DOORS IN THE SERVICE BAY WALLS.
 PROVIDE THE DETAILS ON SERVICE COURT METAL DOORS.
  
 8) PLEASE DESCRIBE THE KNOCKOUT PANELS SHOWN ON BLDG
 J-5.
  
 9) SEPARATE PERMITS ARE REQUIRED FOR:
 A. SIGNAGE
 B. AWNINGS
 C. PARKING LOT STRIPING
 D. SHADE STRUCTURES
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.