Plan Review Details - Permit 12100482
Plan Review Stops For Permit 12100482
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-06-11 Cont ID  
Sent By jgomez Date 2013-06-11 Time 12:54 Rev Time 0.00
Received By jgomez Date 2013-06-11 Time 12:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-02-27 Cont ID  
Sent By jgomez Date 2013-02-27 Time 10:01 Rev Time 0.00
Received By jgomez Date 2013-02-27 Time 10:01 Sent To  
Notes
2013-02-27 10:20:15NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE DRAINAGE PLAN AS REQ'D BY SEC. R401.3 F 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT).
 ***ENGINEER OF RECORD RESPONSE LETTER SAID "REFER TO
 ATTACHED RESIDENTIAL DRAINAGE PLANS". WHERE IS IT?.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND
 PAGE SHOWING THE CONNECTOR. THIS APPLIES TO STRUCTURAL
 CONNECTORS ONLY. (REPEAT COMMENT. NOT ADDRESSED).
  
 B) GARAGE EXTERIOR SWING DOOR & REAR SWING DOOR AS
 SHOWN ON PLANS. EXTERIOR ELEVATIONS SHOW SOLID DOORS,
 WHILE NOA 12-0118.32 SHOWS GLAZED DOORS. REVISE AS
 REQUIRED TO MATCH. SAME APPLIES FOR ENTRY DOOR.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 AS REQUIRED BY SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
 (REPEAT COMMENT. NOT ADDRESSED).
 ***ENGINEER OF RECORD RESPONSE LETTER SAID "REFER TO
 ATTACHED ENGINEER OF RECORD SIGNED AND DATED PRODUCT
 APPROVALS". WHERE IS IT?
  
 4- SOIL TEST REPORT FROM NUTTING ENGINEERS DATED MAY
 2012 IDENTIFIES MUCK ON THE SOIL. ENGINEER (RICK
 WOHLFARTH) SUGGESTED OWNER (O.C. MOORE) DEEPER TEST
 BORING TO PROVIDE DEEP FOUNDATION RECOMMENDATIONS. MR.
 MOORE TOLD THE ENGINEER THAT HE WILL PERFORM A
 DEMUCKING OPERATION RATHER THAN PURSUING A DEEP
 FOUNDATION SYSTEM. ENGINEER ALSO TOLD TO THE OWNER THAT
 GIVEN THE CONDITIONS OF THE SITE THE DEEP FOUNDATION
 SYSTEM WAS RECOMMENDED RATHER THAN DEMUCKING.
 ***NOTE: OWNER NEEDS TO GET A PERMIT FOR DEMUCKING.
 NEED TO PROVIDE COMPLETE ENGINEERING REPORT FOR THE
 DEMUCKING PROCESS. SEC. 107.2.1.3 CITY AMENDMENTS TO
 FBC. DENSITY TEST DONE BY TESTING LAB OF THE PALM
 BEACHES, INC. DATED 6/13/12 WAS DONE TO A DEPTH OF
 3'-0" ONLY. THERE IS NO INDICATION OF WHAT WAS DONE TO
 THE MUCK. OWNER STILL NEEDS TO ADDRESS THE MUCK ISSUE
 PER SOIL TEST REPORT RECOMMENDATIONS. (REPEAT COMMENT)
 ***ENGINEER OF RECORD RESPONSE LETTER SAID "PREPARING A
 REPORT TO ADDRESS THE EXISTING SOIL CONDITIONS ON SITE
 IN CONJUNCTION WITH PROPOSED RESIDENCE DESIGN, REPORT
 FORTHCOMING". PROVIDE REPORT.
  
 5- ENGINEER OF RECORD TO REVIEW SOIL TEST REPORT. THE
 REPORT IDENTIFIES MUCK ON THE SOIL AND SPECIFIES THAT
 IF THE SITE IS PROPERLY PREPARED, THEN THE FOUNDATION
 SYSTEM SHOULD BE DESIGNED FOR AN ALLOWABLE SOIL BEARING
 PRESSURE OF 2,000 POUNDS PER SQUARE FOOT. THE REPORT
 ALSO RECOMMENDS A MINIMUM FOOTING WITH OF 16 INCHES.
 ENGINEER OF RECORD SPECIFIES 2500 SOIL BEARING CAPACITY
 AND THE WIDTH OF THE FOOTING IS 14 INCHES. ENGINEER OF
 RECORD TO ADDRESS THIS ISSUES BY REVISING PLANS
 ACCORDING TO RECOMMENDATIONS OR BY PROVIDING
 ENGINEERING ANALYSIS SHOWING WHY IS NOT REQUIRED TO
 FOLLOW REPORT RECOMMENDATIONS. SEC. 107.2.1.3 CITY
 AMENDMENTS TO FBC. (REPEAT COMMENT).
 *** ENGINEER OF RECORD RESPONSE LETTER SAID THE SAME AS
 FOR PREVIOUS COMMENT. PROVIDE REPORT.
  
 6- PROVIDE HURRICANE SHUTTERS COMPLETE INSTALLATION
 SCHEDULE TO VERIFY COMPLIANCE WITH THE PRODUCT APPROVAL
 LIMITATIONS AND DESIGN PRESSURES REQUIRED BY SEC.
 R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. (REPEAT COMMENT.
 NOT ADDRESSED).
  
 7- REVISE PROPOSED KEYNOTE #PN-31 ON SHEET A-1. GARAGE
 DOOR NOA 09-0604.05 WAS SUPERSEDED BY MIAMI-DADE AND
 WAS NOT THE NOA SUBMITTED BY THE CONTRACTOR. . SEE NOA
 SUBMITTED AND REVISE ACCORDINGLY. CURRENT NOA REQUIRED
 BY DCA RULE 9N-3. (REPEAT COMMENT. NOT ADDRESSED).
 ***ENGINEER OF RECORD RESPONSE LETTER SAID THAT SHEET
 A-1 WAS REVISED. THIS ITEM ON SHEET A-1 STILL SPECIFIES
 OLD NOA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-12-18 Cont ID  
Sent By jgomez Date 2012-12-18 Time 15:59 Rev Time 0.00
Received By jgomez Date 2012-12-18 Time 15:25 Sent To  
Notes
2012-12-18 15:59:58NEW RESIDENCE (R3) SECOND BUILDING REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQ'D BY COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 2- PROVIDE DRAINAGE PLAN AS REQ'D BY SEC. R401.3 F 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED).
  
 3- CLEARLY SPECIFY EGRESS BEDROOM WINDOWS. SEC. R310 OF
 2010 FBC-RESIDENTIAL. SPECIFY ALL WINDOW TYPES & SIZES.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 4. AT LEAST ONE BATHROOM SHALL PROVIDE DOOR WITH MIN.
 29" CLEAR OPENING. SEC. R320.1.1 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED).
  
 5- SPECIFY SAFETY GLASS ON BATHROOMS. SEC. R308.4(5) OF
 2010 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED).
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) HORIZONTAL SLIDING WINDOWS AS SHOWN ON PLANS.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND
 PAGE SHOWING THE CONNECTOR. THIS APPLIES TO STRUCTURAL
 CONNECTORS ONLY. (REPEAT COMMENT. NOT ADDRESSED).
  
 C) GARAGE EXTERIOR SWING DOOR & REAR SWING DOOR AS
 SHOWN ON PLANS. NEED CURRENT PRODUCT APPROVAL AND
 PROVIDE 2 COPIES. PRODUCT INFORMATION SUBMITTED IS NOT
 CURRENT. (REPEAT COMMENT. NOT ADDRESSED).
  
 D) FIXED WINDOWS AS SHOWN ON PLANS. (REPEAT COMMENT.
 NOT ADDRESSED).
  
 E) PEEL & STICK SHINGLES UNDERLAYMENT AS SPECIFIED ON
 PROPOSED KEY NOTE PN-20 ON SHEET A-1. NOTE;
 UNDERLAYMENT TO BE DESIGNED TO BE USED WITH SHINGLES.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 8- SOIL TEST REPORT FROM NUTTING ENGINEERS DATED MAY
 2012 IDENTIFIES MUCK ON THE SOIL. ENGINEER (RICK
 WOHLFARTH) SUGGESTED OWNER (O.C. MOORE) DEEPER TEST
 BORING TO PROVIDE DEEP FOUNDATION RECOMMENDATIONS. MR.
 MOORE TOLD THE ENGINEER THAT HE WILL PERFORM A
 DEMUCKING OPERATION RATHER THAN PURSUING A DEEP
 FOUNDATION SYSTEM. ENGINEER ALSO TOLD TO THE OWNER THAT
 GIVEN THE CONDITIONS OF THE SITE THE DEEP FOUNDATION
 SYSTEM WAS RECOMMENDED RATHER THAN DEMUCKING.
 ***NOTE: OWNER NEEDS TO GET A PERMIT FOR DEMUCKING.
 NEED TO PROVIDE COMPLETE ENGINEERING REPORT FOR THE
 DEMUCKING PROCESS. SEC. 107.2.1.3 CITY AMENDMENTS TO
 FBC. DENSITY TEST DONE BY TESTING LAB OF THE PALM
 BEACHES, INC. DATED 6/13/12 WAS DONE TO A DEPTH OF
 3'-0" ONLY. THERE IS NO INDICATION OF WHAT WAS DONE TO
 THE MUCK. OWNER STILL NEEDS TO ADDRESS THE MUCK ISSUE
 PER SOIL TEST REPORT RECOMMENDATIONS. (REPEAT COMMENT.
 NOT ADDRESSED).
  
 9- ENGINEER OF RECORD TO REVIEW SOIL TEST REPORT. THE
 REPORT IDENTIFIES MUCK ON THE SOIL AND SPECIFIES THAT
 IF THE SITE IS PROPERLY PREPARED, THEN THE FOUNDATION
 SYSTEM SHOULD BE DESIGNED FOR AN ALLOWABLE SOIL BEARING
 PRESSURE OF 2,000 POUNDS PER SQUARE FOOT. THE REPORT
 ALSO RECOMMENDS A MINIMUM FOOTING WITH OF 16 INCHES.
 ENGINEER OF RECORD SPECIFIES 2500 SOIL BEARING CAPACITY
 AND THE WIDTH OF THE FOOTING IS 14 INCHES. ENGINEER OF
 RECORD TO ADDRESS THIS ISSUES BY REVISING PLANS
 ACCORDING TO RECOMMENDATIONS OR BY PROVIDING
 ENGINEERING ANALYSIS SHOWING WHY IS NOT REQUIRED TO
 FOLLOW REPORT RECOMMENDATIONS. SEC. 107.2.1.3 CITY
 AMENDMENTS TO FBC. (REPEAT COMMENT. NOT ADDRESSED).
  
 10- PROVIDE HURRICANE SHUTTERS COMPLETE INSTALLATION
 SCHEDULE TO VERIFY COMPLIANCE WITH THE PRODUCT APPROVAL
 LIMITATIONS AND DESIGN PRESSURES REQUIRED BY SEC.
 R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. (REPEAT COMMENT.
 NOT ADDRESSED).
  
 11- SPECIFY ATTIC ACCESS SIZE. SEC. R807 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED).
  
 12- REVISE PROPOSED KEYNOTE #PN-31 ON SHEET A-1. GARAGE
 DOOR NOA 09-0604.05 WAS SUPERSEDED BY MIAMI-DADE AND
 WAS NOT THE NOA SUBMITTED BY THE CONTRACTOR. . SEE NOA
 SUBMITTED AND REVISE ACCORDINGLY. CURRENT NOA REQUIRED
 BY DCA RULE 9N-3. (REPEAT COMMENT. NOT ADDRESSED).
  
 13- SHEET A-2:
 A) DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON THE
 EXTERIOR ELEVATIONS DON'T MATCH THE DESIGN PRESSURES
 SHOWN ON THE WIND LOAD SCHEDULE. SEC. R301.2.1.4.3 OF
 2010 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED).
  
 B) CORNER DISTANCE "A" SHOWN ON THE WIND LOAD SCHEDULE
 IS 4'-0" MIN. NOT 3'-0". SEE FOOTNOTE ON FIGURE
 R301.2(7) OF 2010 FBC-RESIDENTIAL AND REVISE AS
 REQUIRED. (REPEAT COMMENT. NOT ADDRESSED).
  
 C) REVISE PLYWOOD SHEATHING NAILING SCHEDULE. SEC.
 R803.2.3.1 OF 2010 FBC-RESIDENTIAL REQUIRES 8D RING
 SHANK NAILS AT 4"O.C. NOT 6"O.C. IN ROOF ZONE 3.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 14- SPECIFY SPECIFY CARBON MONOXIDE ALARM FOR SLEEPING
 ROOMS. SEC. R315 OF 2010 FBC-RESIDENTIAL. AND,
 REVISE/CLARIFY GENERAL ELECTRIC NOTE #12 ON SHEET A-5.
 NOT CLEAR IF ONLY INSTALLING CARBON MONOXIDE ALARMS IN
 GARAGE. (REPEAT COMMENT. NOT ADDRESSED).
  
 15- ROOF FRAMING PLAN: ENGINEER TO SPECIFY ALL THE LIVE
 AND DEAD LOADS AS REQUIRED BY SEC. R301.1 ALSO, INCLUDE
 THE ATTIC LIVE LOAD REQUIRED BY TABLE R301.5 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-16 Cont ID  
Sent By jgomez Date 2012-11-16 Time 16:29 Rev Time 0.00
Received By jgomez Date 2012-11-16 Time 14:23 Sent To  
Notes
2012-11-16 16:47:51NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQ'D BY COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE DRAINAGE PLAN AS REQ'D BY SEC. R401.3 F 2010
 FBC-RESIDENTIAL.
  
 3- CLEARLY SPECIFY EGRESS BEDROOM WINDOWS. SEC. R310 OF
 2010 FBC-RESIDENTIAL. SPECIFY ALL WINDOW TYPES & SIZES.
  
 4. AT LEAST ONE BATHROOM SHALL PROVIDE DOOR WITH MIN.
 29" CLEAR OPENING. SEC. R320.1.1 OF 2010
 FBC-RESIDENTIAL.
  
 5- SPECIFY SAFETY GLASS ON BATHROOMS. SEC. R308.4(5) OF
 2010 FBC-RESIDENTIAL.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) HORIZONTAL SLIDING WINDOWS AS SHOWN ON PLANS.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS. PROVIDE
 COMPLETE REPORT. NOA 12-0209.13 SUBMITTED IS
 INCOMPLETE. AND, NEED TO PROVIDE 2 COPIES. ONLY ONE WAS
 SUBMITTED.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND
 PAGE SHOWING THE CONNECTOR. THIS APPLIES TO STRUCTURAL
 CONNECTORS ONLY.
  
 D) ROOF SHINGLES. ONLY THE HIP AND RIDGE PRODUCT
 APPROVAL WAS SUBMITTED. ALSO, NEED TO PROVIDE 2 COPIES
 OF HIP AND RIDGE PRODUCT APPROVAL. ONLY ONE COPY WAS
 SUBMITTED.
  
 E) ENTRY DOOR AS SHOWN ON PLANS.
  
 F) GARAGE EXTERIOR SWING DOOR & REAR SWING DOOR AS
 SHOWN ON PLANS. NEED CURRENT PRODUCT APPROVAL AND
 PROVIDE 2 COPIES. PRODUCT INFORMATION SUBMITTED IS NOT
 CURRENT.
  
 G) HURRICANE SHUTTERS. PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE SHOWING THE FLORIDA PRODUCT APPROVAL NUMBER
 AND APPROVAL STATUS. INFORMATION SUBMITTED DIDN'T
 INCLUDE THE COVER PAGE.
  
 H) FIXED WINDOWS AS SHOWN ON PLANS.
  
 G) PEEL & STICK SHINGLES UNDERLAYMENT AS SPECIFIED ON
 PROPOSED KEY NOTE PN-20 ON SHEET A-1. NOTE;
 UNDERLAYMENT TO BE DESIGNED TO BE USED WITH SHINGLES.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 8- SOIL TEST REPORT FROM NUTTING ENGINEERS DATED MAY
 2012 IDENTIFIES MUCK ON THE SOIL. ENGINEER (RICK
 WOHLFARTH) SUGGESTED OWNER (O.C. MOORE) DEEPER TEST
 BORING TO PROVIDE DEEP FOUNDATION RECOMMENDATIONS. MR.
 MOORE TOLD THE ENGINEER THAT HE WILL PERFORM A
 DEMUCKING OPERATION RATHER THAN PURSUING A DEEP
 FOUNDATION SYSTEM. ENGINEER ALSO TOLD TO THE OWNER THAT
 GIVEN THE CONDITIONS OF THE SITE THE DEEP FOUNDATION
 SYSTEM WAS RECOMMENDED RATHER THAN DEMUCKING.
 ***NOTE: OWNER NEEDS TO GET A PERMIT FOR DEMUCKING.
 NEED TO PROVIDE COMPLETE ENGINEERING REPORT FOR THE
 DEMUCKING PROCESS. SEC. 107.2.1.3 CITY AMENDMENTS TO
 FBC. DENSITY TEST DONE BY TESTING LAB OF THE PALM
 BEACHES, INC. DATED 6/13/12 WAS DONE TO A DEPTH OF
 3'-0" ONLY. THERE IS NO INDICATION OF WHAT WAS DONE TO
 THE MUCK. OWNER STILL NEEDS TO ADDRESS THE MUCK ISSUE
 PER SOIL TEST REPORT RECOMMENDATIONS.
  
 9- ENGINEER OF RECORD TO REVIEW SOIL TEST REPORT. THE
 REPORT IDENTIFIES MUCK ON THE SOIL AND SPECIFIES THAT
 IF THE SITE IS PROPERLY PREPARED, THEN THE FOUNDATION
 SYSTEM SHOULD BE DESIGNED FOR AN ALLOWABLE SOIL BEARING
 PRESSURE OF 2,000 POUNDS PER SQUARE FOOT. THE REPORT
 ALSO RECOMMENDS A MINIMUM FOOTING WITH OF 16 INCHES.
 ENGINEER OF RECORD SPECIFIES 2500 SOIL BEARING CAPACITY
 AND THE WIDTH OF THE FOOTING IS 14 INCHES. ENGINEER OF
 RECORD TO ADDRESS THIS ISSUES BY REVISING PLANS
 ACCORDING TO RECOMMENDATIONS OR BY PROVIDING
 ENGINEERING ANALYSIS SHOWING WHY IS NOT REQUIRED TO
 FOLLOW REPORT RECOMMENDATIONS. SEC. 107.2.1.3 CITY
 AMENDMENTS TO FBC.
  
 10- PROVIDE HURRICANE SHUTTERS COMPLETE INSTALLATION
 SCHEDULE TO VERIFY COMPLIANCE WITH THE PRODUCT APPROVAL
 LIMITATIONS AND DESIGN PRESSURES REQUIRED BY SEC.
 R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
  
 11- SPECIFY ATTIC ACCESS SIZE. SEC. R807 OF 2010
 FBC-RESIDENTIAL.
  
 12- REVISE PROPOSED KEYNOTE #PN-31 ON SHEET A-1. GARAGE
 DOOR NOA 09-0604.05 WAS SUPERSEDED BY MIAMI-DADE AND
 WAS NOT THE NOA SUBMITTED BY THE CONTRACTOR. . SEE NOA
 SUBMITTED AND REVISE ACCORDINGLY. CURRENT NOA REQUIRED
 BY DCA RULE 9N-3.
  
 13- SHEET A-2:
 A) DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON THE
 EXTERIOR ELEVATIONS DON'T MATCH THE DESIGN PRESSURES
 SHOWN ON THE WIND LOAD SCHEDULE. SEC. R301.2.1.4.3 OF
 2010 FBC-RESIDENTIAL.
  
 B) CORNER DISTANCE "A" SHOWN ON THE WIND LOAD SCHEDULE
 IS 4'-0" MIN. NOT 3'-0". SEE FOOTNOTE ON FIGURE
 R301.2(7) OF 2010 FBC-RESIDENTIAL AND REVISE AS
 REQUIRED.
  
 C) REVISE PLYWOOD SHEATHING NAILING SCHEDULE. SEC.
 R803.2.3.1 OF 2010 FBC-RESIDENTIAL REQUIRES 8D RING
 SHANK NAILS AT 4"O.C. NOT 6"O.C. IN ROOF ZONE 3.
  
 14- SPECIFY SPECIFY CARBON MONOXIDE ALARM FOR SLEEPING
 ROOMS. SEC. R315 OF 2010 FBC-RESIDENTIAL. AND,
 REVISE/CLARIFY GENERAL ELECTRIC NOTE #12 ON SHEET A-5.
 NOT CLEAR IF ONLY INSTALLING CARBON MONOXIDE ALARMS IN
 GARAGE.
  
 15- ROOF FRAMING PLAN: ENGINEER TO SPECIFY ALL THE LIVE
 AND DEAD LOADS AS REQUIRED BY SEC. R301.1 ALSO, INCLUDE
 THE ATTIC LIVE LOAD REQUIRED BY TABLE R301.5 OF 2010
 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-03-01 Cont ID  
Sent By rlecky Date 2013-03-01 Time 11:37 Rev Time 0.00
Received By rlecky Date 2013-03-01 Time 11:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2012-12-21 Cont ID  
Sent By rlecky Date 2012-12-21 Time 14:59 Rev Time 0.00
Received By rlecky Date 2012-12-21 Time 14:54 Sent To  
Notes
2012-12-21 15:01:01PLEASE REVISE THE PLANS TO INCLUDE THE REQUIREMENTS
 NOTED ON THE PREVIOUS REVIEW AND LISTED HERE.
  
  
 12100482
 500 HURON PL.
 SFD
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE
 PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC
 210.12
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. 2010 FBC R314, 315
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
 MINIMUM SIZE SERVICE CONDUCTORS FOR A 200 AMPERE
 RESIDENTIAL SERVICE IS 2/0 COPPER. NEC 310.16
 THE ELECTRICAL SERVICE REQUIRES A MAIN 200 AMPERE
 SERVICE DISCONNECT OUTSIDE ADJACENT TO THE METER. NEC
 230.70
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-11-09 Cont ID  
Sent By rlecky Date 2012-11-09 Time 11:32 Rev Time 0.00
Received By rlecky Date 2012-11-09 Time 10:43 Sent To  
Notes
2012-11-09 11:33:4612100482
 500 HURON PL.
 SFD
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE
 PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC
 210.12
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. 2010 FBC R314, 315
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
 MINIMUM SIZE SERVICE CONDUCTORS FOR A 200 AMPERE
 RESIDENTIAL SERVICE IS 2/0 COPPER. NEC 310.16
 THE ELECTRICAL SERVICE REQUIRES A MAIN 200 AMPERE
 SERVICE DISCONNECT OUTSIDE ADJACENT TO THE METER. NEC
 230.70
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2013-06-11 Cont ID  
Sent By jgomez Date 2013-06-11 Time 14:39 Rev Time 0.00
Received By jgomez Date 2013-05-22 Time 09:08 Sent To  
Notes
2013-05-23 09:09:34INCOMING SENT TO JULIOS' DESK, NEW NOA'S. JW

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-05-23 Cont ID  
Sent By rbrown Date 2013-05-23 Time 17:01 Rev Time 0.00
Received By rbrown Date 2013-05-07 Time 10:04 Sent To  
Notes
2013-05-23 17:00:555-23-13 CALLED DEREK SCHENEVAR, P.E., AND MR. O.C.
 MOORE (OWNER) AND TOLD THEM THAT SLAB PROPOSAL IS
 ACCEPTABLE PROVIDED PLAN SHEET S-2 IS REVISED TO
 REFERENCE THE ALLTERRA GEOTECHNICAL RECOMMENDATION
 LETTER REPORT DATED 5/3/13. GEOTECHNICAL REPORT PUT
 WITH REMAINDER OF PACKET AND SENT TO JULIO GOMEZ' DESK
 FOR HIM TO REVIEW THE 5/22/13 RESUBMITTAL. RB
  
2013-05-07 10:05:16SOIL ENGINEER REPORT SENT TO ROBERT BROWN'S DESK FOR
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-03-01 Cont ID  
Sent By rlecky Date 2013-03-01 Time 11:37 Rev Time 0.00
Received By rlecky Date 2013-02-12 Time 16:41 Sent To  
Notes
2013-02-12 16:42:58R--1

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-21 Cont ID  
Sent By mdekle Date 2012-12-21 Time   Rev Time 0.00
Received By mdekle Date 2012-12-06 Time 11:38 Sent To  
Notes
2012-12-07 11:41:22R--11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-30 Cont ID  
Sent By lmartine Date 2012-11-30 Time 12:44 Rev Time 0.00
Received By lmartine Date 2012-10-16 Time 11:16 Sent To  
Notes
2012-10-17 11:17:20SENT TO R1 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2013-06-11 Cont ID  
Sent By jgomez Date 2013-06-11 Time 14:32 Rev Time 0.00
Received By jgomez Date 2013-06-11 Time 14:32 Sent To  
Notes
2013-06-11 14:33:10PAID $1093.12. MU 2013 11826. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2013-02-27 Cont ID  
Sent By jgomez Date 2013-02-27 Time 10:26 Rev Time 0.00
Received By jgomez Date 2013-02-27 Time 10:26 Sent To  
Notes
2013-02-27 10:26:59BRING PLANS TO PALM BEACH COUNTY TO CHECK IF IMPACT
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. JG

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-12-18 Cont ID  
Sent By jgomez Date 2012-12-18 Time 16:00 Rev Time 0.00
Received By jgomez Date 2012-12-18 Time 16:00 Sent To  
Notes
2012-12-18 16:01:27BRING PLANS TO PALM BEACH COUNTY TO CHECK IF IMPACT
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. JG

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-11-16 Cont ID  
Sent By jgomez Date 2012-11-16 Time 15:10 Rev Time 0.00
Received By jgomez Date 2012-11-16 Time 15:10 Sent To  
Notes
2012-11-16 15:11:10BRING PLANS TO PALM BEACH COUNTY TO CHECK IF IMPACT
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. JG.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2013-06-11 Cont ID  
Sent By jgomez Date 2013-06-11 Time 14:33 Rev Time 0.00
Received By jgomez Date 2013-06-11 Time 14:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-06-11 Cont ID  
Sent By jgomez Date 2013-02-27 Time 15:15 Rev Time 0.00
Received By jgomez Date 2013-02-27 Time 15:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-12-10 Cont ID  
Sent By lmartine Date 2012-12-10 Time 08:43 Rev Time 0.00
Received By lmartine Date 2012-12-10 Time 08:43 Sent To  
Notes
2012-12-10 08:44:24*** MECHANICAL PLAN CORRECTIONS AS NOTED IN LAST PLAN
 REVIEW 11/30/12 ***
  
 1) EQUIPMENT SCHEDULE ON MECHANICAL PLAN A-3 DOES NOT
 COINCIDE WITH THE COOLING LOAD CAL'S OR E-CAL'S..
 PLEASE CORRECT PER 2010 FBC/RES. N1101, RES M1401.3 AND
 FBC/ENERGY 403.6.1, ENERGY 503.2.2.
  
 2) ENERGY CAL'S. NEED TO BE SIGNED & DATED BY THE
 OWNER/AGENT, PER 2010 FBC/ENERGY 103.2.3.2.
  
 3) RETURN AIR TRANSFER GRILLS TO THE TWO SMALL BEDROOMS
 ARE UNDER SIZED. PLEASE CORRECT PER 2010 FBC/M 601.4.
 TRANSFER GRILL AREA SHALL BE 50 SQ. IN. PER 100CFM'S OF
 SUPPLY AIR.
  
 4) CLOTHES DRYER VENT IS DISCHARGING TO CLOSE TO THE
 A/C CONDENSER UNIT, LINT MAY BE SUCKED INTO CONDENSER
 COIL. PLEASE SEE 2010 FBC/M 501.2.
  
 *** MECH. PLAN REVIEW BY TOM GORDON (HY-BYRD, INC.)
 *** FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-11-30 Cont ID  
Sent By lmartine Date 2012-11-30 Time 12:09 Rev Time 0.00
Received By lmartine Date 2012-11-30 Time 12:09 Sent To  
Notes
2012-11-30 12:43:56*** MECHANICAL PLAN CORRECTIONS ***
  
 1) EQUIPMENT SCHEDULE ON MECHANICAL PLAN DOES NOT
 COINCIDE WITH THE COOLING LOAD CAL'S OR E-CAL'S..
 PLEASE CORRECT PER 2010 FBC/ENERGY 403.6.1.
  
 2) ENERGY CAL'S. NEED TO BE SIGNED & DATED BY THE
 OWNER/AGENT, PER 2010 FBC/ENERGY 103.2.3.2.
  
 3) RETURN AIR TRANSFER GRILLS TO ALL THE BEDROOMS ARE
 UNDER SIZED. PLEASE CORRECT PER 2010 FBC/M 601.4.
 TRANSFER GRILL AREA SHALL BE 50 SQ. IN. PER 100CFM'S OF
 SUPPLY AIR.
  
 4) CLOTHES DRYER VENT IS DISCHARGING TO CLOSE TO THE
 A/C CONDENSER UNIT, LINT MAY BE SUCKED INTO CONDENSER
 COIL. PLEASE CORRECT PER 2010 FBC/M 501.2.
  
 *** MECH. PLAN REVIEW BY TOM GORDON (HY-BYRD, INC.)
 *** FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-02-27 Cont ID  
Sent By jgomez Date 2013-02-27 Time 13:59 Rev Time 0.00
Received By jgomez Date 2013-02-27 Time 13:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-11-19 Cont ID  
Sent By jgomez Date 2012-11-16 Time 16:47 Rev Time 0.00
Received By jgomez Date 2012-11-16 Time 16:47 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2020-12-11 Cont ID  
Sent By rgathrig Date 2020-12-11 Time 11:54 Rev Time 0.00
Received By rgathrig Date 2020-12-11 Time 11:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2013-02-21 Cont ID  
Sent By mdekle Date 2013-02-21 Time   Rev Time 0.00
Received By mdekle Date 2013-02-21 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2012-12-21 Cont ID  
Sent By mdekle Date 2012-12-21 Time   Rev Time 0.00
Received By mdekle Date 2012-12-21 Time   Sent To  
Notes
2012-12-21 16:19:38REPEAT COMMENTS:
  
 ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 12.21.2012
 PERMIT NO.: 12100482
 ADDRESS: 500 HURON PLACE
 CONTRACTOR/CONTACT: O.C. MOORE
 TELEPHONE NO.: 561.308.6240
 SCOPE OF REVIEW: CONSTRUCTION OF NEW SINGLE FAMILY
 C.B.S 3/2/2 HOME
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
 SEC. 94-442. - OPEN SPACE LANDSCAPE REQUIREMENTS.
  
 (A)INTENT. THE INTENT OF THIS SECTION IS TO PROVIDE
 STANDARDS FOR LANDSCAPING OPEN SPACE AREAS WHEN
 REQUIRED BY THIS CHAPTER. LANDSCAPE PLANS, EXCLUDING
 THOSE PREPARED FOR SINGLE-FAMILY DWELLING UNITS, SHALL
 BE PREPARED BY PERSONS AS AUTHORIZED BY F.S. CH. 481,
 PT. II (LANDSCAPE ARCHITECTURE).
  
 (B)GENERAL STANDARDS. ALL OPEN SPACE, AS REQUIRED BY
 THIS CHAPTER, SHALL BE LANDSCAPED AS PROVIDED IN THIS
 SECTION.
  
 (1)LANDSCAPING GENERALLY. ALL OPEN SPACE, EXCLUDING
 VEHICULAR AND PEDESTRIAN CIRCULATION FEATURES AND
 SURFACE PARKING, SHALL BE COVERED WITH GRASS, GROUND
 COVER, SHRUBBERY, OR OTHER SUITABLE PLANT MATERIAL, OR
 MAY HAVE PAVED ACTIVE RECREATION AREAS, PATIOS,
 TERRACES, PEDESTRIAN CIRCULATION AREAS, SWIMMING POOLS,
 WATER FEATURES, AND SIMILAR SITE COMPONENTS
 INCORPORATED IN THE OPEN SPACE DESIGNS.
  
 (2)GENERAL LANDSCAPING STANDARDS FOR SINGLE-FAMILY
 DWELLING UNITS AND ALL OTHER DEVELOPMENTS. GENERAL
 LANDSCAPING STANDARDS FOR SINGLE-FAMILY DWELLING UNITS
 AND ALL OTHER DEVELOPMENTS SHALL BE AS FOLLOWS:
 A.SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AND/OR
 CONSULT THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA
 PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
 WWW.CITYOFWPB.COM
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-10-24 Cont ID  
Sent By mdekle Date 2012-10-24 Time   Rev Time  
Received By mdekle Date 2012-10-24 Time   Sent To  
Notes
2012-10-24 09:44:33ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 10.24.2012
 PERMIT NO.: 12100482
 ADDRESS: 500 HURON PLACE
 CONTRACTOR/CONTACT: O.C. MOORE
 TELEPHONE NO.: 561.308.6240
 SCOPE OF REVIEW: CONSTRUCTION OF NEW SINGLE FAMILY
 C.B.S 3/2/2 HOME
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
 SEC. 94-442. - OPEN SPACE LANDSCAPE REQUIREMENTS.
  
 (A)INTENT. THE INTENT OF THIS SECTION IS TO PROVIDE
 STANDARDS FOR LANDSCAPING OPEN SPACE AREAS WHEN
 REQUIRED BY THIS CHAPTER. LANDSCAPE PLANS, EXCLUDING
 THOSE PREPARED FOR SINGLE-FAMILY DWELLING UNITS, SHALL
 BE PREPARED BY PERSONS AS AUTHORIZED BY F.S. CH. 481,
 PT. II (LANDSCAPE ARCHITECTURE).
  
 (B)GENERAL STANDARDS. ALL OPEN SPACE, AS REQUIRED BY
 THIS CHAPTER, SHALL BE LANDSCAPED AS PROVIDED IN THIS
 SECTION.
  
 (1)LANDSCAPING GENERALLY. ALL OPEN SPACE, EXCLUDING
 VEHICULAR AND PEDESTRIAN CIRCULATION FEATURES AND
 SURFACE PARKING, SHALL BE COVERED WITH GRASS, GROUND
 COVER, SHRUBBERY, OR OTHER SUITABLE PLANT MATERIAL, OR
 MAY HAVE PAVED ACTIVE RECREATION AREAS, PATIOS,
 TERRACES, PEDESTRIAN CIRCULATION AREAS, SWIMMING POOLS,
 WATER FEATURES, AND SIMILAR SITE COMPONENTS
 INCORPORATED IN THE OPEN SPACE DESIGNS.
  
 (2)GENERAL LANDSCAPING STANDARDS FOR SINGLE-FAMILY
 DWELLING UNITS AND ALL OTHER DEVELOPMENTS. GENERAL
 LANDSCAPING STANDARDS FOR SINGLE-FAMILY DWELLING UNITS
 AND ALL OTHER DEVELOPMENTS SHALL BE AS FOLLOWS:
 A.SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AND/OR
 CONSULT THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA
 PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
 WWW.CITYOFWPB.COM
  
  