Plan Review Details - Permit 12100373
Plan Review Stops For Permit 12100373
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-12-11 Cont ID  
Sent By jwitmer Date 2012-12-11 Time 14:25 Rev Time 0.00
Received By jwitmer Date 2012-12-10 Time 14:56 Sent To  
Notes
2012-12-11 14:27:24BUILDING PLAN REVIEW
 PERMIT: 12100373
 ADD: 1801 PALM BEACH LAKES BLVD FOUNDATIONS BLDG J1-J10
 CONT: EMJ CONSTRUCTION
 TEL: (423)414-1587
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 BUILDIN PROVISO:
  
 NOTICE: 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL
 OF THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-07 Cont ID  
Sent By jwitmer Date 2012-11-07 Time 09:55 Rev Time 0.00
Received By jwitmer Date 2012-10-29 Time 11:19 Sent To  
Notes
2012-11-06 16:49:11BUILDING PLAN REVIEW
 PERMIT: 12100373
 ADD: 1801 PALM BEACH LAKES BLVD FOUNDATIONS BLDG J1-J10
 CONT: EMJ CONSTRUCTION
 TEL: (423)414-1587
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 NOV. 06/ 2012
 ACTION: DENIED
  
 NOTICE: 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL
 OF THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER?S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 1) SHEET A-101 PROJECT INFORMATION INDICATES THIS OPEN
 MALL BUILDING COMPRISED OF MULTIPLE BUILDING ON A SITE
 PER FBC 402. PLEASE PROVIDE A CODE SECTION IN THE 2010
 FBC-B 402 THAT ALLOWS FOR UNLIMITED AREA FOR OPEN MALL
 BUILDINGS? IN SECTION 402.2 THE DEFINITION OF OPEN MALL
 BUILDINGS IS LOCATED. PLEASE REVIEW SECTION
 507.3.1.UNLIMITED AREA BUILDINGS / MIXED USE BUILDINGS
 WITH A1 AND A2 OCCUPANCIES.
  
 2) THE PERMIT APPLICATION INDICATES THIS IS FOR THE
 FOUNDATION OF BUILDINGS J-1 THROUGH J-10. THE PLANS ARE
 NOT CLEAR IF THIS PHASE IS TO ALSO INCORPORATE THE 24
 INCH AUGER CAST PILE FOR THE AWNINGS? ADDITIONAL
 INFORMATION IS REQUIRED 107.2.1.3. BOTH THE STRUCTURAL
 CALCULATIONS AND SOILS REPORT INDICATE THE USE OF 24
 INCH DIAMETER AUGER CAST PILING BUT NO STEEL
 REINFORCING IS INDICATED IN THE FOUNDATION SCHEDULE NOR
 IS THERE A SOILS ENGINEER INDICATED TO SUPERVISE THE
 INSTALATION OF THE AUGER CAST PILE.
  
 3) THE LOCATION OF AWNINGS AND AUGER CAST PILE ARE NOT
 CLEARLY INDICATED ON THE PLANS, WHAT APPEARS TO BE THE
 AWNINGS ALSO HAS THE ABBREVATIONS RMU, THIS ABBREVATION
 IS NOT FOUND IN THE ABBREVATIONS ON THE COVER SHEET,
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) THESE BUILDINGS ARE TO BE CONSIDERED AS THRESHOLD
 BUILDINGS SINCE SOME OF THESE BUILDINGS MAY MEET
 THRESHOLD REQUIREMENTS IN AREA AND IF ASSEMBLY
 OCCUPANCY. A SOFT HOLD WILL BE PUT ON THIS PERMIT THAT
 WILL ALLOW THE REVIEWS TO CONTINUE BUT NOT ALLOW IT TO
 BE ISSUED UNTIL THESE REQUIREMENTS ARE MET.
  
 THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 A HOLD WILL BE PUT ON THIS PROJECT UNTIL THESE ITEMS
 ARE COMPLETED AS REQUESTED BY THE CHIEF BUILDING
 INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 4.1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONCRETE RESTORATION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 4.2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-11-07 Cont ID  
Sent By rlecky Date 2012-11-07 Time 11:03 Rev Time 0.00
Received By rlecky Date 2012-10-30 Time 15:59 Sent To  
Notes
2012-11-06 16:58:0312100373
 1801 PALM BEACH LAKES
 FOUNDATION PERMIT
  
 THIS APPROVAL IS FOR FOUNDATION PERMITTING. PLEASE
 ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS
 PRIOR TO VERTICAL CONSTRUCTION.
  
 E 001
 NOTE 45: UPDATE WIND LOAD REQUIREMENTS FOR LIGHT POLES
 FOR EXPOSURE CATEGORY AND IMPORTANCE FACTOR. FBC 2010
 1609, ASCE 7-10
  
 NOTE 56: MULTI-WIRE BRANCH CIRCUITS REQUIRE A MEANS
 THAT WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED
 CONDUCTORS. NEC 210.4
  
 E 201
 INDICATE AND LABEL ON THE PLAN THE METHOD SELECTED TO
 PROVIDE THE REQUIRED SAFE WORKING CLEARANCES AND
 DEDICATED WORKING SPACE AT THE ELECTRICAL PANEL BOARDS.
 NEC 110.26, 240.24
  
 E202, 205, ETC ?
 PROVIDE A DETAIL WHICH ESTABLISHES A COMMON BONDING
 CONDUCTOR FOR THE SEPARATELY DERIVED ELECTRICAL
 SYSTEMS. NEC 250.30 (A) (4)
 GROUNDING ELECTRODE TAPS SHALL BE PROPERLY SIZED AND
 CONNECTED WITH A LISTED CONNECTOR OR EXOTHERMIC WELDING
 PROCESS. NEC 250.30(A) (4) (A,B,C)
  
 E601
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION. NEC 110.22,
 110.16
 PROVIDE A DETAIL WITH DIMENSIONS SHOWING THE REQUIRED
 WORKING CLEARANCES AND DEDICATED WORKING SPACE WITHIN
 THE ELECTRICAL EQUIPMENT ROOMS. INDICATE ON THE FLOOR
 PLAN WITHIN EACH TENANT SPACE THE REQUIRED WORKING
 CLEARANCES. NEC 110.26, 240.24
  
 E401, 402, 403
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 NEW SERVICE AND SWITCH GEAR. NEC 110.9, 110.10
 PANEL SCHEDULES AND MAIN DISCONNECTS ARE REQUIRED FOR
 TENANT SPACES. NEC 215.5
 GROUND-FAULT PROTECTION IS REQUIRED FOR THE METERING
 SWITCH BOARDS. NEC 230.95
  
 NOTES:
 SEPARATE PERMITS ARE REQUIRED FOR VOICE AND DATA, FIRE
 ALARM SYSTEMS AND LIGHTNING PROTECTION.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2012-10-13 Cont ID  
Sent By   Date 2012-10-13 Time   Rev Time 1.00
Received By   Date 2012-10-13 Time   Sent To Z
Notes
2012-10-13 00:36:21ENGINEERING REVIEW DONE THRU ESD.
  
 CONTRACTOR HAS APPLIED FOR PBC HEALTH DEPARTMENT AND AT
 THIS TIME HAS COMPLETED SUBMITTAL AND HAS ELECTED TO
 PROCEED DEMOLISH AND CONSTRUCT INFRASTRUCTURE ELEMENTS
 WHICH WILL SET THE STAGE FOR NEW MALL STORES AND
 BUILDINGS.
  
 NPDES IS REQUIRED.
  
 SITE UTILITIES WILL BE CONSTRUCTED AND CERTIFIED BY
 EOR.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-10 Cont ID  
Sent By rregueir Date 2013-01-10 Time 14:13 Rev Time 0.00
Received By rregueir Date 2012-12-04 Time 16:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-07 Cont ID  
Sent By rregueir Date 2012-11-06 Time 14:31 Rev Time 0.00
Received By rregueir Date 2012-10-12 Time 14:31 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2012-12-13 Cont ID  
Sent By rbrown Date 2012-12-13 Time 13:27 Rev Time 0.00
Received By rbrown Date 2012-12-13 Time 13:26 Sent To  
Notes
2012-12-13 13:26:02THE ASSESSED IMPACT FEES ARE OFFSET BY THE EXISTING USE
 CREDIT AS STATED IN THE FOLLOWING MESSAGE RECEIVED FROM
 WILLIE SWOOPE AT THE PALM BEACH COUNTY IMPACT FEE
 OFFICE:
  
 PURSUANT TO OUR CONVERSATION, PALM BEACH LAKES MALL
 APPLIED FOR AN IMPACT FEE ASSESSMENT ON NOVEMBER 20,
 2012 FOR REDEVELOPMENT OF THE EXISTING PROPERTY. THE
 TOTAL SQUARE FOOTAGE INVOLVED IN THIS PERMIT WAS
 465,705 SQUARE FEET. PALM BEACH COUNTY PR # MU
 2012-021414 WAS USED TO TRACK THE IMPACT FEE ASSESSMENT
 FOR THIS PROJECT. THE TOTAL FEES ASSESSED ARE LISTED
 BELOW:
  
 PUB BLDING - $111,597.29
 ROADS - $1,717,036.60
  
 THE FEES ABOVE WERE OFFSET BY AN EXISTING USE CREDIT
 (IFX-2012-102).
  
 PLSE CALL IF YOU HAVE QUESTIONS.
  
 WILLIE M. SWOOPE
 "SUNNY SKIES ON THE HORIZON"
 IMPACT FEE MANAGER
 FINANCIAL MANAGEMENT & BUDGET
 PALM BEACH COUNTY GOVERNMENT
 EMAIL: [email protected] OR [email protected]
 WEBSITE:WWW.PBCGOV.COM/PZB/IMPACTFEES/
 2300 N. JOG RD, WPB, FL 33411-2741
 (561)233-5025 / (561)656-7971(FAX)
 (561)233-5167 (ALT FAX)
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2012-12-11 Cont ID  
Sent By jwitmer Date 2012-12-11 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2012-12-11 Time 14:22 Sent To  
Notes
2012-12-11 14:23:55NO IMPACT FEES TO BE COLLECTED AT THIS TIME FOR
 FOUNDATION PERMIT SINCE THE ORIGINAL MALL BEING
 DEMOLISHED HAS NOT RECEIVED CREDITS FOR DEMO.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-11-07 Cont ID  
Sent By jwitmer Date 2012-11-07 Time 09:56 Rev Time 0.00
Received By jwitmer Date 2012-11-07 Time 09:55 Sent To  
Notes
2012-11-07 09:56:20BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-10-29 Cont ID  
Sent By lwagner Date 2012-10-29 Time 13:37 Rev Time 0.00
Received By lwagner Date 2012-10-29 Time 12:27 Sent To  
Notes
2012-10-24 14:56:31****PROVISO****
 SHEET A208 - SINGLE DRINKING FOUNTAINS ARE SHOWN.
 HI/LOW OR THE EXCEPTION WILL BE REQUIRED.
 FBC ACCESSIBILITY 211.2
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-01-10 Cont ID  
Sent By rregueir Date 2013-01-10 Time 14:11 Rev Time 0.00
Received By rregueir Date 2013-01-10 Time 14:08 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2013-01-10 Cont ID  
Sent By jwitmer Date 2013-01-10 Time 14:12 Rev Time 0.00
Received By jwitmer Date 2013-01-10 Time 14:12 Sent To  
Notes
2012-12-11 14:29:16WRITTEN THRESHOLD PLAN IS PART OF THE STRUCTURAL
 DRAWINGS. JW

Review Stop Z ZONING
Rev No 2 Status P Date 2012-12-13 Cont ID  
Sent By eschneid Date 2012-12-13 Time 19:54 Rev Time 2.00
Received By eschneid Date 2012-12-13 Time 19:54 Sent To  
Notes
2012-12-13 19:54:10PASSED
  
 1) THIS REVIEW FOR THE FOUNDATION ONLY.
  
 2) THE NORTHEAST BICYCLE RACK HAS BEEN RELOCATED. THIS
 WILL NEED TO BE REFLECTED ON A MINOR SITE PLAN
 AMENDMENT, APPROVED BY THE PLANNING DIVISION, PRIOR TO
 C.O. OF THE FIRST SHELL. PLEASE NOTE THAT THE PLANS DID
 NOT HAVE DIMENSION LINES TO VERIFY IF THERE WAS A WIDE
 ENOUGH CLEAR WALKWAY BETWEEN THE BICYCLE RACK AND THE
 PLANTING GRATE.
  
 3) PLEASE NOTE THAT PER THE FORMAL SITE PLAN APPROVAL
 LETTER, DOORWAYS MAY NOT BE LOCATED ACROSS FROM THE
 SERVICE BAY ENTRANCES FOR BUILDINGS J-7 AND J-8.
  
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-10-16 Cont ID  
Sent By eschneid Date 2012-10-16 Time 11:31 Rev Time 3.00
Received By eschneid Date 2012-10-16 Time 11:31 Sent To  
Notes
2012-10-16 13:17:40FAILED
  
 THIS REVIEW FOR THE FOUNDATION ONLY.
  
 PLEASE PROVIDE WRITTEN RESPONSES TO THE COMMENTS.
  
 1) THE BUILDING FOOTPRINTS, TO INCLUDE THE SERVICE
 COURT LOCATIONS, DO NOT MATCH WHAT IS UNDER REVIEW FOR
 THE FORMAL SITE PLAN APPROVAL. BOTH SETS OF PLANS SHALL
 MATCH.
  
 2) THE PROPOSED OUTLET BUILDING SQUARE FOOTAGE EXCEEDS
 WHAT IS UNDER REVIEW FOR THE FORMAL SITE PLAN AND
 ASSOCIATED MINOR AMENDMENT BY APPROXIMATELY 4,700
 SQUARE FEET.
  
 3) THE VALET CANOPY IS NOT INCLUDED ON THE FORMAL SITE
 PLAN. IT MAY NOT BE INCLUDED, EVEN FOR THE FOOTERS,
 UNTIL IT IS APPROVED AS PART OF THE FORMAL SITE PLAN OR
 A SUBSEQUENT MINOR AMENDMENT.
  
 4) THE CONCOURSES SEEM TO HAVE LESS PLANTER AREAS THAN
 ARE ON THE PLANS UNDER REVIEW FOR THE FORMAL SITE PLAN.
 PLEASE REMEMBER THAT THAT THE INTERIOR TREES AND THE
 LANDSCAPE ARES ARE REQUIRED TO MEET SITE MINIMUMS.
  
 5) WRITTEN APPROVAL FROM THE CITY'S CRIME PREVENTION
 OFFICER, KELLY CARSILLO, IS REQUIRED FOR THE LOCATION
 OF THE POLICE OFFICE.
  
 6) NO SET BACK DIMENSIONS ARE SHOWN ON THE PLANS FROM
 THE PROPERTY LINE TO THE OUTLET CENTER BUILDINGS SO
 THAT STAFF CAN VERIFY THAT THE FOUNDATION IS BEING
 CONSTRUCTED IN THE CORRECT LOCATION AS SHOWN ON THE
 FORMAL SITE PLAN.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  