Plan Review Details - Permit 12100368
Plan Review Stops For Permit 12100368
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-10-18 Cont ID  
Sent By jwitmer Date 2012-10-18 Time 08:29 Rev Time 0.00
Received By jwitmer Date 2012-10-18 Time 08:27 Sent To  
Notes
2012-10-18 08:28:58NEW E & FA INDICATING IN THIS TENAT SPACE THERE IS NO
 A/C AND NO DUCT DETECTORS REQUIRED. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-10-14 Cont ID  
Sent By jwitmer Date 2012-10-14 Time 13:19 Rev Time 0.00
Received By jwitmer Date 2012-10-14 Time 11:45 Sent To  
Notes
2012-10-14 13:03:57BUILDING PLAN REVIEW
 PERMIT:12100368 (REV)/ 12070697 (MASTER)
 ADD: 2400 S DIXIE HWY
 CONT: SYMMETRY CONSTRUCTION GROUP
 TEL: (954)696-6878
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 OCT. 14/2012
 1ST REVIEW
 ACTION: DENIED
  
 1) THE E1 SHEET ( PANEL A & B CIRCUITS 2-8, AHU #2 & CU
 #2) AS WELL AS THE FIRE ALARM SHEET BOTH INDICATE THERE
 IS AN EXISTING A/C SYSTEM IN THIS BUILDING, THE FIRE
 ALARM SYSTEM IS NOT REQUIRED BECAUSE OF THE OCCUPANTCY
 BEING A -3 AND NOT HAVING 300 OCCUPANTS BUT THE 2010
 FBC-B SECTION 907.3.1 DOES REQUIRE DUCT SMOKE DETECTOR,
 PLEASE REVIEW EXCEPTION # 2 AN WILL BE CONNECTED TO THE
 BUILDINGS FIRE ALARM CONTROL UNIT WHAN A FIRE ALARM
 SYSTEM IS REQUIRED BY SECTION 907.3.1.EXCEPTION # 2.
  
 907.3.1 EXCEPTION # 2. IN OCCUPANCIES NOT REQUIRED TO
 BE EQUIPPED WITH A FIRE ALARM SYSTEM, ACTUATION OF A
 SMOKE DETECTOR SHALL ACTIVATE A VISIBLE AND AN AUDIBLE
 SIGNAL IN AN APPROVED LOCATION. SMOKE DETECTOR TROUBLE
 CONDITIONS SHALL ACTIVATE A VISIBLE OR AUDIBLE SIGNAL
 IN AN APPROVED LOCATION AND SHALL BE IDENTIFIED AS AIR
 DUCT DETECTOR TROUBLE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-10-18 Cont ID  
Sent By jwitmer Date 2012-10-18 Time 15:24 Rev Time 0.00
Received By jwitmer Date 2012-10-18 Time 15:24 Sent To  
Notes
2012-10-18 15:25:09APPROVED PER P. PETTY. JW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-10-18 Cont ID  
Sent By wjolin Date 2012-10-18 Time 13:14 Rev Time 0.00
Received By wjolin Date 2012-10-18 Time 13:00 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-10-18 Cont ID  
Sent By jwitmer Date 2012-10-18 Time 15:25 Rev Time 0.00
Received By jwitmer Date 2012-10-11 Time 12:17 Sent To  
Notes
2012-10-11 12:18:45EXPEDITED
 B--17