| 2012-11-07 16:57:45 | BUILDING PLAN REVIEW |
| | PERMIT: 12100361 |
| | ADD: 550 S ROSEMARY SUITE 250 |
| | CONT: TO BE DETERMINED |
| | TEL: (561)856-6655 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | NOV. 07/2012 |
| | ACTION: DENIED |
| | |
| | 1) SHEET LS-1.0 INDICATES A PLATFORM SEATING AREA # 1 |
| | WITH AN ELEVATION OF 6 INCHES AND A SINGLE 6 INCH |
| | STAIR. PLEASE SEE 2010 FBC-B SECTION 1003.5 ELEVATION |
| | CHANGE. WHERE CHANGES IN ELEVATION OF LESS THAN 12 |
| | INCHES (305 MM) EXIST IN THE MEANS OF EGRESS, SLOPED |
| | SURFACES SHALL BE USED. WHERE THE SLOPE IS GREATER THAN |
| | ONE UNIT VERTICAL IN 20 UNITS HORIZONTAL (5-PERCENT |
| | SLOPE), RAMPS COMPLYING WITH SECTION 1010 SHALL BE |
| | USED. WHERE THE DIFFERENCE IN ELEVATION IS 6 INCHES |
| | (152 MM) OR LESS, THE RAMP SHALL BE EQUIPPED WITH |
| | EITHER HANDRAILS OR FLOOR FINISH MATERIALS THAT |
| | CONTRAST WITH ADJACENT FLOOR FINISH MATERIALS. |
| | |
| | 2) SHEET LS-1.0 ALSO INDICATES THE USE OF A CHAIR LIFT |
| | PLEASE PROVIDE DOCUMENTATIONOF COMPLIANCE WITH 2010 |
| | FBC-408 LIMITED USE / LIMITED APPLICATION ELEVATORS, |
| | (LULA LIFTS). |
| | |
| | 3) SHEET A1.0 INDICATES THE USE OF STRUCTURAL |
| | POLYSTYRENE FILLER, PLEASE SEE USE OF PLASTICS SECTION |
| | 603 COMBUSTIBLE MATERIAL IN TYPE I AND II CONSTRUCTION |
| | EXCEPTION #3 FOAM PLASTICS IN ACCORDANCE WITH CHAPTER |
| | 26. |
| | 2603.3 SURFACE-BURNING CHARACTERISTICS. |
| | UNLESS OTHERWISE INDICATED IN THIS SECTION, FOAM |
| | PLASTIC INSULATION AND FOAM PLASTIC CORES OF |
| | MANUFACTURED ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT |
| | MORE THAN 450 WHERE TESTED IN THE MAXIMUM THICKNESS |
| | INTENDED FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723. |
| | 2603.3 EXCEPTION #4 FOAM PLASTIC INSULATION GREATER |
| | THAN 4 INCHES (102 MM) IN THICKNESS SHALL HAVE A |
| | MAXIMUM FLAME SPREAD INDEX OF 75 AND A SMOKE-DEVELOPED |
| | INDEX OF 450 WHERE TESTED AT A MINIMUM THICKNESS OF 4 |
| | INCHES (102 MM), PROVIDED THE END USE IS APPROVED IN |
| | ACCORDANCE WITH SECTION 2603.9 USING THE THICKNESS AND |
| | DENSITY INTENDED FOR USE |
| | 2603.9 SPECIAL APPROVAL. |
| | FOAM PLASTIC SHALL NOT BE REQUIRED TO COMPLY WITH THE |
| | REQUIREMENTS OF SECTIONS 2603.4 THROUGH 2603.7 WHERE |
| | SPECIFICALLY APPROVED BASED ON LARGE-SCALE TESTS SUCH |
| | AS, BUT NOT LIMITED TO, NFPA 286 (WITH THE ACCEPTANCE |
| | CRITERIA OF SECTION 803.2), FM 4880, UL 1040 OR UL |
| | 1715. SUCH TESTING SHALL BE RELATED TO THE ACTUAL |
| | END-USE CONFIGURATION AND BE PERFORMED ON THE FINISHED |
| | MANUFACTURED FOAM PLASTIC ASSEMBLY IN THE MAXIMUM |
| | THICKNESS INTENDED FOR USE. FOAM PLASTICS THAT ARE USED |
| | AS INTERIOR FINISH ON THE BASIS OF SPECIAL TESTS SHALL |
| | ALSO CONFORM TO THE FLAME SPREAD REQUIREMENTS OF |
| | CHAPTER 8. ASSEMBLIES TESTED SHALL INCLUDE SEAMS, |
| | JOINTS AND OTHER TYPICAL DETAILS USED IN THE |
| | INSTALLATION OF THE ASSEMBLY AND SHALL BE TESTED IN THE |
| | MANNER INTENDED FOR USE. |
| | |
| | 4) SHEET A-2.1INDICATES THE INSTALATION OF NEW |
| | STOREFRONT FIXED WINDOW AND EXTERIOR SWING GLAZED |
| | DOORS. NO PRODUCT APPROVAL WAS SUBMITTED WITH THIS |
| | PACKAGE, PLEASE SEE 2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING AND RULE |
| | 9N-3 (31).FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | |
| | 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6) SHEET A-3.0 INDICATES THE USE OF 16- 8 INCH PVC |
| | PIPES OVERHEAD, PLEASE PROVIDE ADDITIONAL INFORMATION |
| | THAT THE EXISTING BAR JOIST CAN ACCEPT THE ADDITIONAL |
| | WEIGHT (DEAD LOAD FBC-B 1606.2.) OF THE 8 INCH PVC |
| | PIPE, UNI-STRURT, HANGERS, TUBING AND WEIGHT OF BEER |
| | WITHIN THE TUBING AND THE LIGHTING THAT WILL BE |
| | ATTACHED TO THE UNDER SIDE OF THE SYSTEM. |
| | |
| | 7) SHEET A-3.0 PVC PIPING AND 603.1.2 PIPING. THE USE |
| | OF COMBUSTIBLE PIPING MATERIALS SHALL BE PERMITTED WHEN |
| | INSTALLED IN ACCORDANCE WITH THE LIMITATIONS OF THE |
| | FLORIDA BUILDING CODE, MECHANICAL. AND THE FLORIDA |
| | BUILDING CODE, PLUMBING. |
| | |
| | 8) SHEET A3.0 AND A-4.2 DETAIL 10 DO NOT INDICATE IF |
| | THE 16- 8 INCH PVC PIPE ARE LOCATED ABOVE THE CEILING , |
| | BELOW THE CEILING OR IF THERE WILL BE A CEILING? |
| | WALL SECTIONS ON SHEET A-4.0 DO INDICATE THERE IS A |
| | DROPPED CEILING. 2010 FBC-B 603.1 EXCEPTION 25. |
| | MATERIALS EXPOSED WITHIN PLENUMS COMPLYING WITH SECTION |
| | 602 OF THE FLORIDA BUILDING CODE, MECHANICAL |
| | |
| | 9) SHEET A-3.3 WIND DESIGN FOR ROOF TOP EQUIPMENT IS |
| | DESIGN TO THE 2007 FBC WHEN REFERENECING ASCE 7-05. THE |
| | 2010 FBC-B REFERENECES THE ASCE 7-10 STANDARD. |
| | |
| | 10) SHEET A-4.2 INDICATES FIXED IN PLACE BANQUET |
| | INDICATES THE USE OF WHITE WOOD AND PLYWOOD. 2010 FBC-B |
| | 603.1 FIRE RETARDANT TREATED WOOD. |
| | |
| | 11) SHEET A-4.2 DETAIL TYPICAL HANDRAIL IS LOCATED |
| | 8'-6" ABOVE FINISH FLOOR. REVIEW 2010 FBC-B 10112.2 |
| | HEIGHT. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | 11) |
| | |