Plan Review Details - Permit 12100269
Plan Review Stops For Permit 12100269
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-01-24 Cont ID  
Sent By jwitmer Date 2013-01-24 Time 11:07 Rev Time 0.00
Received By jwitmer Date 2013-01-24 Time 11:07 Sent To  
Notes
2013-01-24 11:16:22BUILDING PLAN REVIEW
 PERMIT: 12100269
 ADD: 4847 FRED GLADSTONE DRIVE
 CONT: THE WHITING TURNER CO.
 TEL: (561)688-1910 (JOBSITE/ HENRY)
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, ROOF HATCH.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, INSULATION
 (E) SHUTTERS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-13 Cont ID  
Sent By jwitmer Date 2012-11-13 Time 10:10 Rev Time 0.00
Received By jwitmer Date 2012-11-07 Time 11:40 Sent To  
Notes
2012-11-07 15:26:16BUILDING PLAN REVIEW
 PERMIT: 12100269
 ADD: 4847 FRED GLADSTONE DRIVE
 CONT: THE WHITING TURNER CO.
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 NOV. 07/2012
 ACTION: DENIED
  
 1) GOO1 WIND SPEED MAP INDICATES P B COUNTY AMENDMENTS,
 2010 WEST PALM BEACH CHAPTER 1 AMENDMENTS,
 ADMINISTRATIVE 119.1FIGURES 1609A B AND C ARE HEREBY
 ADOPTED AS THE OFFICIAL ULTIMATE DESIGN WIND SPEED RISK
 CATEGORY MAPS FOR THE CITY OF WEST PALM BEACH.
  
 2) MISSING SOILS REPORT PER 2010 FBC-B 1803.6
 GEOTECHNICAL SOILS REPORT REQUIRED.
  
 3) MISSING 2010 FBC-ENERGY MISSING ENERGY CALCS.
 101.4.3 ADDITIONS.
  
 4) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, ROOF HATCH.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, INSULATION
 (E) SHUTTERS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) S201 COMPONENTS & CLADDING ULTIMATE AND ALLOWABLE
 LOAD CHARTS NOTE # 1 BOTH INDICATE EITHER THE USE OF
 IMPACT RESISTANT WINDOWS OR PROTECTED BY IMPACT
 PROTECTIVE SYSTEMS. 2010 WEST PALM BEACH ADMINISTRATIVE
 CODE 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL"
 OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION...
  
 7) SHEET A601 SOILED LAUNDRY DOOR 127 IN THE DOOR
 SCHEDULE A601 DOES NOT INDICATE A RATED DOOR PER 2010
 FBC-B TABLE 715.4 IN HOURS AND MINUTES.
  
 8) SHEET A601 DOOR SCHEDULE DOOR 128 INDICATES HARDWARE
 GROUP 13 BUT DOES NOT PROVIDE A SCHEDULE FOR THE
 HARDWARE. 2010 FBC-B 420.3.4.1.5.1. LOCKABLE DOOR.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-02-04 Cont ID  
Sent By rlecky Date 2013-02-04 Time 16:48 Rev Time 0.00
Received By rlecky Date 2013-02-04 Time 16:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-11-06 Cont ID  
Sent By rlecky Date 2012-11-06 Time 11:12 Rev Time 0.00
Received By rlecky Date 2012-11-05 Time 16:51 Sent To  
Notes
2012-11-06 11:15:0412100269
 4847 FRED GLADSTONE DRIVE
 RENOVATION
  
 PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW
 COMMENTS.
  
 E003
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION. NEC 110.22,
 110.16
  
 E005:
 ELECTRICAL METALLIC TUBING (EMT) IS NOT AN ACCEPTABLE
 WIRING METHOD AS SHOWN MOUNTED ON THE ROOF EXPOSED TO
 PHYSICAL DAMAGE AND EXPOSED TO THE WEATHER. NEC 358.12
  
 E301
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 E601
 PANEL EQH2 DOES NOT MATCH WITH THE RISER PLAN ON E002.
 NEC 215.5
 PANEL NH1A DOES NOT MATCH WITH THE RISER PLAN ON E003.
  
 NOTE:
 SEPARATE PERMITS ARE REQUIRED FOR VOICE AND DATA, FIRE
 ALARM SYSTEMS AND LIGHTNING PROTECTION.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2012-11-29 Cont ID  
Sent By mgonzale Date 2012-11-29 Time   Rev Time 1.00
Received By mgonzale Date 2012-11-29 Time   Sent To  
Notes
2012-11-29 12:52:38NO OBJECTION.
  
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-11-01 Cont ID  
Sent By wjolin Date 2012-11-01 Time 15:27 Rev Time 0.00
Received By wjolin Date 2012-10-26 Time 10:01 Sent To  
Notes
2012-10-26 11:36:384847 FRED GLADSTONE DRIVE
 PERMIT #12100269
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****APPROVED W/ PROVISIONS - SUBMIT REVISION*****
  
 SHEET G101: THE OCCUPANCY TYPE IS INDICATED AS
 INSTITUTIONAL (I-2) PER THE FLORIDA BUILDING CODE;
 HOWEVER, THE OCCUPANT LOAD IS BASED UPON A DAY-CARE
 OCCUPANCY USING AN OCCUPANT LOAD FACTOR OF 20 SQ.FT.
 PER PERSON. PLEASE INDICATE IF THIS SPACE IS INTENDED
 TO BE UTILIZED AS AN ADULT DAY-CARE FACILITY WHERE
 OCCUPANTS ARE CAPABLE OF SELF-PRESERVATION OR WILL THE
 SPACE BE USED FOR PERSONS WHO ARE NOT CAPABLE OF
 SELF-PRESERVATION. ALSO INDICATE THE TIME FRAME FOR
 RECEIVING CARE (MORE THAN OR LESS THAN 24 HOURS PER
 DAY).
  
 SHEET G101: ROOM #110 AND #112 SHOW AN EXIT DISCHARGE
 TO AN EXTERIOR COURTYARD. INDICATE THE ROUTE FROM THE
 COURTYARD TO THE PUBLIC WAY.
  
 SHEET A101: PROVIDE DOOR NUMBER INDICATORS FOR THE MAIN
 ENTRANCE (LOBBY #101), AND DAY ROOM #7 (DOUBLE DOORS).
  
 SHEET A601: INDICATE THE FIRE RESISTANCE RATING (IN
 MINUTES) OF ANY FIRE-RATED DOORS. INDICATE WHAT IS
 INCLUDED (CLOSER, PANIC HARDWARE, LOCKS,ETC.) WITH EACH
 DOOR HARDWARE GROUP AS NO SPECIFICATIONS WERE
 SUBMITTED. NOTE: ANY DOOR IN A REQUIRED MEANS OF EGRESS
 FROM AN AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS SHALL BE PERMITTED TO BE PROVIDED WITH A LOCK
 OR LATCH ONLY IF THEY ARE RELEASED BY PANIC HARDWARE
 PER SECTION 16.2.2.2.2 (NFPA 101 FLORIDA).
  
 GENERAL: EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT
 CLIENTS CAN OPEN THE DOOR FROM INSIDE THE CLOSET. EVERY
 BATHROOM DOOR LOCK SHALL BE DESIGNED TO ALLOW OPENING
 OF THE LOCKED DOOR FROM THE OUTSIDE BY AN OPENING
 DEVICE THAT SHALL BE READILY ACCESSIBLE TO THE STAFF
 PER SECTION 16.2.2.2.5 (NFPA 101 FLORIDA).
  
 PLEASE PROVIDE THE FOLLOWING NOTES ON THE LIFE SAFEY
 PLAN:
  
 1) ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 50 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 2) AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN
 BUILDING PRIOR TO OCCUPANCY.
  
 3) EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY.
 ALL DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM.
  
 4) FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED
 MONTHLY BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER
 WHICH A COPY OF THE LATEST INSPECTION REPORT SHALL BE
 POSTED IN A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY.
 IT SHALL BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS
 DAILY TO ENSURE THAT ALL DOORS AND EXIT PATHS ARE
 MAINTAINED CLEAR OF OBSTRUCTIONS.
  
 SHEET FP101 AND SHEET E0004: FIRE PROTECTION SYSTEMS
 SHALL REMAIN ACTIVE DURING DEMOLITION AND RENOVATION
 ACTIVITIES. IN THE EVENT A FIRE PROTECTION SYSTEM IS
 OUT OF SERVICE FOR MORE THAN 4-HOURS IN A 24-HOUR
 PERIOD, THE BUILDING SHALL BE PLACED UNDER A FIRE
 WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED IN
 WRITING (FAX: 561-804-4774) AND APPROVED BY THE OFFICE
 OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-02-16 Cont ID  
Sent By rregueir Date 2013-02-16 Time 08:52 Rev Time 0.00
Received By rregueir Date 2013-01-23 Time 11:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2012-12-13 Time   Rev Time 0.00
Received By rbrown Date 2012-10-09 Time 13:36 Sent To  
Notes
2012-10-29 13:37:05DIGITAL PLANS IN PROJECTDOX

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-03-19 Cont ID  
Sent By rregueir Date 2013-03-19 Time 14:45 Rev Time 0.00
Received By rregueir Date 2013-03-19 Time 14:45 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-01-24 Cont ID  
Sent By jwitmer Date 2013-01-24 Time 11:16 Rev Time 0.00
Received By jwitmer Date 2013-01-24 Time 11:16 Sent To  
Notes
2013-01-24 11:17:22BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-02-05 Cont ID  
Sent By rregueir Date 2013-02-05 Time 14:14 Rev Time 0.00
Received By rregueir Date 2013-02-05 Time 14:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-12-13 Cont ID  
Sent By rregueir Date 2012-12-13 Time 11:53 Rev Time 0.00
Received By rregueir Date 2012-12-13 Time 10:26 Sent To  
Notes
2012-12-13 11:53:02REVIEW #: 1ST
 ACTION: DENIED
  
 REVIEWED FOR COMPLIANCE WITH THE FOLLOWING:
 FBC 2010
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. DUCT SIZES MISSING IN SEVERAL LOCATIONS ON THE
 PLANS. EXAMPLES: RETURN DUCT SERVING STORAGE ROOM 123
 MECH ROOM 124; RETURN DUCT SERVING SOILED LAUNDRY ROOM
 127. THESE ARE ONLY EXAMPLES. PLEASE CHECK ENTIRE PLAN
 AND PROVIDE ALL MISSING DUCT SIZES. FBC-M 603.1
  
 2. PG M201: UNABLE TO DETERMINE DRYER EXHAUST DUCT
 LENGTH ON PLAN. WHAT IS THE TOTAL DEVELOPED LENGTH OF
 ALL VERTICAL AND HORIZONTAL SECTIONS? DRYER EXHAUST
 DUCT SHALL NOT EXCEED 35 FEET UNLESS DRYER
 MANUFATURER'S INSTALLATION INSTRUCTIONS PROVIDE FOR
 LONGER DUCT INSTALLATION. FBC-M 504.6.
  
 3. PG M202: PLEASE CLARIFY THE AIR BALANCE OVERALL.
 THERE APPEARS TO BE MANY AREAS IN WHICH SUPPLY AND
 RETURN ARE 100% EQUAL. IF 100% OF AIR IS BEING
 RETURNED, HOW IS THERE ENOUGH CAPACITY FOR THE SUPPLY
 TO PROVIDE THE REQUIRED QUANTITIES OF VENTILATION AIR
 FOR EACH HABITABLE SPACE PER FBC-M SECTION 403.
  
 4. SHOW HOW THE CONDITIONED SPACE IS TO BE PRESSURIZED
 WITH RESPECT TO THE OUTDOORS (POST-CONSTRUCTION, NOT
 DURING CONTAMINATION PREVENTION STAGE) PER FBC-EC
 SECTION 503.2.10.6.
  
 5. PG M400: DETAIL #5 SHOWS MIN. 1 INCH SUPPORT STRAPS
 FOR FLEXIBLE DUCTS. FLEXIBLE DUCT SUPPORTS ARE REQUIRED
 TO BE MIN. 1.5 INCHES WIDE PER FBC-M 603.10.3.
  
 6. PG M400: PROVIDE WIND RESISTANT ATTACHMENT DETAIL
 FOR ROOF MOUNTED EQUIPMENT. A NOTE ON THE PLAN CALLING
 FOR CODE COMPLIANT INSTALLATION IS NOT SUFFICIENT.
 PROVIDE SUFFICIENT DETAIL TO ALLOW FOR A REVIEW OF THE
 ATTACHMENT METHOD PER FBC-M 301.12 AND FBC-B 106.1.
  
 7. SHOW HOW FAN SHUT-DOWN BY SMOKE DETECTION IS TO BE
 PROVIDED PER FBC-M 606.1. DETAIL #5 ON PG M600 SHOWS
 DUCT SMOKE DETECTORS ON SUPPLY SIDE AND RETURN SIDE. IS
 THIS CORRECT? ALSO, DETAIL DOES NOT SHOW THE DUCT SMOKE
 DETECTORS INTERLOCKED WITH FIRE ALARM SYSTEM. SHOW
 COMPLIANCE WITH FBC-M 606.4.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-10-30 Cont ID  
Sent By lwagner Date 2012-10-30 Time 09:56 Rev Time 0.00
Received By lwagner Date 2012-10-30 Time 09:56 Sent To  
Notes
2012-10-30 09:57:16***PROVISO***
 ROUTE SINK WASTE LINE TO
 DOWNSTREAM SIDE OF WATER CLOSETS.
 FBC PLUMBING 909.1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-03-19 Cont ID  
Sent By rregueir Date 2013-03-19 Time 14:45 Rev Time 0.00
Received By rregueir Date 2013-03-19 Time 14:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-02-12 Cont ID  
Sent By eschneid Date 2013-02-12 Time 14:02 Rev Time 2.00
Received By eschneid Date 2013-02-07 Time 16:51 Sent To  
Notes
2013-02-08 08:30:30PASSES
  
 1) SEPARATE PERMITS REQUIRED:
 A. LANDSCAPE
 B. IRRIGATION
 C. PARKING LOT RENOVATIONS (VAN PARKING AND SOUTHWEST
 PARKING LOT)
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-10-30 Cont ID  
Sent By eschneid Date 2012-10-30 Time 09:14 Rev Time 0.50
Received By eschneid Date 2012-10-30 Time 09:14 Sent To  
Notes
2012-10-30 09:19:27FAILED
  
 1) THE EXPANSION REQUIRES THE APPROVAL OF THE MAJOR
 AMENDMENT THAT IS CURRENTLY IN PROCESS BY THE CITY
 COMMISSION. THE FIRST READING IS NOT UNTIL NOV. 13,
 2012.
  
 2) ADDITIONALLY, THE EXPANSION REQUIRES THE APPROVAL OF
 A FORMAL SITE PLAN REVIEW, PER THE MORSELIFE CSPD. THE
 FORMAL SITE PLAN HAS NOT BEEN SUBMITTED TO THE CITY FOR
 REVIEW. ZONING WILL NOT REVIEW THE BUILDING PERMIT
 PLANS UNTIL THE FORMAL SITE PLAN HAS BEEN APPROVED. THE
 PLANS SUBMITTED FOR BUILDING PERMIT SHALL MATCH THE
 APPROVED FORMAL SITE PLAN APPROVAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.