| Plan Review Stops For Permit 12100196 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2012-12-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-12-03 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-12-03 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2012-11-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-11-26 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-11-26 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2012-11-26 09:28:55 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE EXPOSURE CATEGORY OF B SPECIFIED ON THE PLANS IS | | | NOT CORRECT. FBCR 301.2.1.4.3 REQUIRES THE SURFACE | | | ROUGHNESS B TO PREVAIL IN THE UPWIND DIRECTION FOR A | | | DISTANCE OF AT LEAST 1500 FEET. THIS STRUCTURE IS | | | WITHIN 800 FEET OF THE INTER-COASTAL WATERWAY, | | | THEREFORE, IT IS EXPOSURE C. PLEASE CORRECT. | | | | | | 2) THE COMPONENT AND CLADDING PRESSURES FOR THE WALL | | | AREAS ON THE PLANS ARE FOR EXPOSURE B. PLEASE REVISE | | | THE PRESSURES TO REFLECT EXPOSURE CATEGORY C AND A MEAN | | | ROOF HEIGHT OF 20 FEET. FBCR 301.2.1 | | | | | | 3) PROVIDE STRUCTURAL DETAILS FOR THE WINDOW AND DOOR | | | INFILL FRAMING ON THE PLANS. CITY AMENDMENTS 107.2.1 | | | (REPEAT COMMENT) | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-11-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-11-07 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-11-07 |
Time |
11:11 |
Sent To |
Z |
|
| Notes |
| 2012-11-07 11:30:14 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) CITY AMENDMENTS 107.2.1 REQUIRES ALL INFORMATION, | | | DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA TO BEAR | | | THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN. PLEASE CORRECT. | | | | | | 2) SPECIFY THE WIND-SPEED DATA AND EXPOSURE CATEGORY ON | | | THE PLANS. FBCR 301.2.1 AND 301.2.1.4.3 | | | | | | 3) SPECIFY THE COMPONENT AND CLADDING PRESSURE FOR THE | | | WALL AREAS ON THE PLANS. FBCR 301.2.1 | | | | | | 4) PROVIDE STRUCTURAL DETAILS FOR THE WINDOW AND DOOR | | | INFILL FRAMING ON THE PLANS. CITY AMENDMENTS 107.2.1 | | | | | | 5) IN ORDER TO EXPEDITE PLAN REVIEW TIME WHEN | | | RESUBMITTING, PLEASE SUBMIT A RESPONSE LETTER | | | INDICATING HOW THE REVIEW COMMENTS HAVE BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-10-09 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-10-09 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-10-09 |
Time |
16:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
N |
Date |
2012-11-07 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2012-11-07 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2012-11-07 |
Time |
16:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2012-12-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-12-03 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-11-29 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2012-11-30 12:57:02 | GAVE TO ROBBIE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2012-11-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-11-26 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-11-15 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2012-11-19 09:46:40 | GAVE TO MCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-11-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-11-08 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-10-05 |
Time |
16:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2012-10-29 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2012-10-29 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2012-10-29 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2012-10-29 11:10:09 | NO AIRCONDITIONING PLANS SUBMITTED | | | AIRCONDITIONING CONTRACTOR MUST SUBMIT | | | APPLICATION AND PLANS FOR PERMIT. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2012-12-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-12-03 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-12-03 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2012-11-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-11-26 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-11-26 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2012-11-26 09:18:23 | 2010 FBC | | | | | | PLUMBING DENIED | | | | | | 1) BOTH OF THE UPSTAIRS BATHROOMS ARE NOT PROPERLY | | | VENTED. FBCR P3108.2.1 STATES THAT NOT MORE THAN ONE | | | WET-VENTED FIXTURE IS ALLOWED TO DISCHARGE UPSTREAM OF | | | THE DRY VENTED FIXTURE. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2012-11-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-11-07 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-11-07 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2012-11-07 11:08:14 | 2010 FBC | | | | | | PLUMBING DENIED | | | | | | 1) THE FIRST FLOOR POWDER ROOM IS NOT SHOWN ON THE | | | PLUMBING RISER DIAGRAM. FBCR P3101 & CITY AMENDMENT | | | 107.2.1 | | | | | | 2) THE WATER CLOSET FOR BATH NUMBER 1 ON THE SECOND | | | FLOOR IS NOT SHOWN ON THE PLUMBING RISER DIAGRAM. FBCR | | | P3101 & CITY AMENDMENT 107.2.1 | | | | | | 3) THE SHOWER AND LAVATORY HORIZONTAL BRANCH IS NOT | | | VENTED PROPERLY. FBCR P3108.2.1 STATES THAT NOT MORE | | | THAN ONE WET-VENTED FIXTURE IS ALLOWED TO DISCHARGE | | | UPSTREAM OF THE DRY VENTED FIXTURE. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2012-11-07 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2012-11-07 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2012-11-07 |
Time |
16:49 |
Sent To |
|
|
| Notes |
|
|