Plan Review Details - Permit 12100196
Plan Review Stops For Permit 12100196
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-12-03 Cont ID  
Sent By rmcdouga Date 2012-12-03 Time 10:58 Rev Time 0.00
Received By rmcdouga Date 2012-12-03 Time 10:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-11-26 Cont ID  
Sent By rmcdouga Date 2012-11-26 Time 09:18 Rev Time 0.00
Received By rmcdouga Date 2012-11-26 Time 09:18 Sent To  
Notes
2012-11-26 09:28:552010 FBC
  
 DENIED BY BUILDING
  
 1) THE EXPOSURE CATEGORY OF B SPECIFIED ON THE PLANS IS
 NOT CORRECT. FBCR 301.2.1.4.3 REQUIRES THE SURFACE
 ROUGHNESS B TO PREVAIL IN THE UPWIND DIRECTION FOR A
 DISTANCE OF AT LEAST 1500 FEET. THIS STRUCTURE IS
 WITHIN 800 FEET OF THE INTER-COASTAL WATERWAY,
 THEREFORE, IT IS EXPOSURE C. PLEASE CORRECT.
  
 2) THE COMPONENT AND CLADDING PRESSURES FOR THE WALL
 AREAS ON THE PLANS ARE FOR EXPOSURE B. PLEASE REVISE
 THE PRESSURES TO REFLECT EXPOSURE CATEGORY C AND A MEAN
 ROOF HEIGHT OF 20 FEET. FBCR 301.2.1
  
 3) PROVIDE STRUCTURAL DETAILS FOR THE WINDOW AND DOOR
 INFILL FRAMING ON THE PLANS. CITY AMENDMENTS 107.2.1
 (REPEAT COMMENT)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-07 Cont ID  
Sent By rmcdouga Date 2012-11-07 Time 11:30 Rev Time 0.00
Received By rmcdouga Date 2012-11-07 Time 11:11 Sent To Z
Notes
2012-11-07 11:30:142010 FBC
  
 DENIED BY BUILDING
  
 1) CITY AMENDMENTS 107.2.1 REQUIRES ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA TO BEAR
 THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. PLEASE CORRECT.
  
 2) SPECIFY THE WIND-SPEED DATA AND EXPOSURE CATEGORY ON
 THE PLANS. FBCR 301.2.1 AND 301.2.1.4.3
  
 3) SPECIFY THE COMPONENT AND CLADDING PRESSURE FOR THE
 WALL AREAS ON THE PLANS. FBCR 301.2.1
  
 4) PROVIDE STRUCTURAL DETAILS FOR THE WINDOW AND DOOR
 INFILL FRAMING ON THE PLANS. CITY AMENDMENTS 107.2.1
  
 5) IN ORDER TO EXPEDITE PLAN REVIEW TIME WHEN
 RESUBMITTING, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW THE REVIEW COMMENTS HAVE BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-10-09 Cont ID  
Sent By rlecky Date 2012-10-09 Time 16:19 Rev Time 0.00
Received By rlecky Date 2012-10-09 Time 16:15 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2012-11-07 Cont ID  
Sent By fmittner Date 2012-11-07 Time 16:48 Rev Time 0.00
Received By fmittner Date 2012-11-07 Time 16:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-12-03 Cont ID  
Sent By rmcdouga Date 2012-12-03 Time 10:58 Rev Time 0.00
Received By rmcdouga Date 2012-11-29 Time 12:56 Sent To  
Notes
2012-11-30 12:57:02GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-11-26 Cont ID  
Sent By rmcdouga Date 2012-11-26 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2012-11-15 Time 09:46 Sent To  
Notes
2012-11-19 09:46:40GAVE TO MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-08 Cont ID  
Sent By rmcdouga Date 2012-11-08 Time 08:45 Rev Time 0.00
Received By rmcdouga Date 2012-10-05 Time 16:12 Sent To  
Notes
2012-10-09 16:16:08R09

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2012-10-29 Cont ID  
Sent By hmoser Date 2012-10-29 Time 11:10 Rev Time 0.00
Received By hmoser Date 2012-10-29 Time 11:06 Sent To  
Notes
2012-10-29 11:10:09NO AIRCONDITIONING PLANS SUBMITTED
 AIRCONDITIONING CONTRACTOR MUST SUBMIT
 APPLICATION AND PLANS FOR PERMIT.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2012-12-03 Cont ID  
Sent By rmcdouga Date 2012-12-03 Time 10:57 Rev Time 0.00
Received By rmcdouga Date 2012-12-03 Time 10:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2012-11-26 Cont ID  
Sent By rmcdouga Date 2012-11-26 Time 09:02 Rev Time 0.00
Received By rmcdouga Date 2012-11-26 Time 08:40 Sent To  
Notes
2012-11-26 09:18:232010 FBC
  
 PLUMBING DENIED
  
 1) BOTH OF THE UPSTAIRS BATHROOMS ARE NOT PROPERLY
 VENTED. FBCR P3108.2.1 STATES THAT NOT MORE THAN ONE
 WET-VENTED FIXTURE IS ALLOWED TO DISCHARGE UPSTREAM OF
 THE DRY VENTED FIXTURE. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-11-07 Cont ID  
Sent By rmcdouga Date 2012-11-07 Time 10:46 Rev Time 0.00
Received By rmcdouga Date 2012-11-07 Time 10:46 Sent To  
Notes
2012-11-07 11:08:142010 FBC
  
 PLUMBING DENIED
  
 1) THE FIRST FLOOR POWDER ROOM IS NOT SHOWN ON THE
 PLUMBING RISER DIAGRAM. FBCR P3101 & CITY AMENDMENT
 107.2.1
  
 2) THE WATER CLOSET FOR BATH NUMBER 1 ON THE SECOND
 FLOOR IS NOT SHOWN ON THE PLUMBING RISER DIAGRAM. FBCR
 P3101 & CITY AMENDMENT 107.2.1
  
 3) THE SHOWER AND LAVATORY HORIZONTAL BRANCH IS NOT
 VENTED PROPERLY. FBCR P3108.2.1 STATES THAT NOT MORE
 THAN ONE WET-VENTED FIXTURE IS ALLOWED TO DISCHARGE
 UPSTREAM OF THE DRY VENTED FIXTURE. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2012-11-07 Cont ID  
Sent By fmittner Date 2012-11-07 Time 16:49 Rev Time 0.00
Received By fmittner Date 2012-11-07 Time 16:49 Sent To  
Notes
***NONE***