Plan Review Details - Permit 12100111
Plan Review Stops For Permit 12100111
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-11-07 Cont ID  
Sent By rmcdouga Date 2012-11-07 Time 09:39 Rev Time 0.00
Received By rmcdouga Date 2012-11-07 Time 09:39 Sent To  
Notes
2012-11-07 09:40:01OWNER CAME IN AND CHANGED TO A REVISION TO PERMIT #
 12100110.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-05 Cont ID  
Sent By rmcdouga Date 2012-11-05 Time 16:52 Rev Time 0.00
Received By rmcdouga Date 2012-11-05 Time 16:52 Sent To  
Notes
2012-11-05 16:58:012010 FBC
  
 DENIED BY BUILDING
  
 THERE IS AN OPEN PERMIT #12100110 AT THIS ADDRESS TO
 ENCLOSE A SCREEN ENCLOSURE INTO LIVING SPACE. THIS
 APPLICATION IS TO CONVERT A PORTION OF THAT ENCLOSED
 SPACE INTO A BATHROOM. THIS PERMIT CAN NOT BE ISSUED
 UNTIL ALL OF THE WORK ON THE ISSUED PERMIT IS COMPLETED
 AND ALL INSPECTIONS HAVE PASSED. THIS COULD BE
 SUBMITTED AS A REVISION TO THE OPEN PERMIT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-11-06 Cont ID  
Sent By rmcdouga Date 2012-11-06 Time 16:07 Rev Time 0.00
Received By rmcdouga Date 2012-11-06 Time 16:07 Sent To  
Notes
2012-11-06 16:07:40RELINED THE PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-06 Cont ID  
Sent By rmcdouga Date 2012-11-06 Time 16:18 Rev Time 0.00
Received By rmcdouga Date 2012-10-03 Time 14:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2012-10-25 Cont ID  
Sent By hmoser Date 2012-10-25 Time 12:21 Rev Time 0.00
Received By hmoser Date 2012-10-25 Time 12:14 Sent To  
Notes
2012-10-25 12:21:13NO MECHANICAL PLANS SUBMITTED. AIRCONDITIONING
 CONTRACTOR MUST SUBMIT AN APPLICATION AND PLANS
 FOR PERMIT.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-11-07 Cont ID  
Sent By rmcdouga Date 2012-11-06 Time 16:07 Rev Time 0.00
Received By rmcdouga Date 2012-11-06 Time 16:07 Sent To  
Notes
2012-11-06 16:18:21REDLINED PLANS. THE SHOWER AND SPA ARE NOT PROPERLY
 VENTED. FBCR P3108.1 REQUIRES EACH WET-FIXTURE DRAIN TO
 CONNECT INDEPENDENTLY TO THE HORIZONTAL WET VENT.
  
  