Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-10-10 Cont ID  
Sent By rlecky Date 2012-10-10 Time 14:07 Rev Time 0.00
Received By rlecky Date 2012-10-10 Time 13:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-10-04 Cont ID  
Sent By rlecky Date 2012-10-04 Time 09:29 Rev Time 0.00
Received By rlecky Date 2012-10-04 Time 08:08 Sent To  
Notes
2012-10-04 09:53:5112100063
 3215 S. FLAGLER DRIVE
 LANDSCAPE LIGHTING
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE SITE
 LIGHTING PLAN.
  
 PROVIDE NUMBER AND THE SIZE OF BRANCH CIRCUIT?S
 INTENDED TO FEED THE SITE LIGHTING. NEC 240.4
  
 INDICATE THE VOLTAGE, WIRING METHOD AND DEPTH OF ALL
 CONDUCTORS. NEC 300.4, 411.3
  
 INDICATE THE REQUIRED SAFE WIRING DISTANCE OF ALL
 LIGHTING FIXTURES FROM THE NEAREST EDGE OF WATER FOR
 POOLS, FOUNTAINS OR SIMILAR LOCATIONS. NEC 411.4(A) AND
 (B)
  
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER