Plan Review Details - Permit 12100028
Plan Review Stops For Permit 12100028
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-12-14 Cont ID  
Sent By jgomez Date 2012-12-14 Time 13:32 Rev Time 0.00
Received By jgomez Date 2012-12-14 Time 13:41 Sent To  
Notes
2012-12-14 13:34:27BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- SHEET 1.2:
 A) UTILITY AREA NEW OUTDOOR STEPS: (1) PROVIDE COMPLETE
 HANDRAILS DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE
 WITH LIVE LOAD ON TABLE R301.5 AND SEC. R311.7.7 OF
 2010 FBC-RESIDENTIAL. ENGINEER PLANS ONLY SAYS NEW
 HANDRAIL DESIGNED BY OTHERS. NO INFORMATION WAS
 PROVIDED FOR REVIEW.
  
 B) NEW STEPS ON REAR SHOWS TREAD SIZE AS 8". MINIMUM
 TREAD SIZE IS 10". SEE SEC. R311.7.4.2 OF 2010
 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
2012-12-14 13:32:0812/14/12 AS PER PHONE CONVERSATION WITH KARI IT'S OK TO
 ISSUE THE PERMIT WITH PROVISO AND REVISION FEES WILL
 APPLY. ALSO, PER KARI TOTAL WORK VALUE IS $16,000. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-12-07 Cont ID  
Sent By jgomez Date 2012-12-07 Time 11:00 Rev Time 0.00
Received By jgomez Date 2012-12-07 Time 11:00 Sent To  
Notes
2012-12-07 11:03:29RESIDENTIAL (R3) ALTERATION SECOND BUILDING REVIEW
 COMMENTS.
 CODE; 2010 FBC.
  
 1- SHEET 1.2:
 A) UTILITY AREA NEW OUTDOOR STEPS: (1) PROVIDE COMPLETE
 HANDRAILS DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE
 WITH LIVE LOAD ON TABLE R301.5 AND SEC. R311.7.7 OF
 2010 FBC-RESIDENTIAL. ENGINEER PLANS ONLY SAYS NEW
 HANDRAIL DESIGNED BY OTHERS. NO INFORMATION WAS
 PROVIDED FOR REVIEW.
  
 B) NEW STEPS ON REAR SHOWS TREAD SIZE AS 8". MINIMUM
 TREAD SIZE IS 10". SEE SEC. R311.7.4.2 OF 2010
 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON THE SCOPE OF WORK TO BE DONE. SEC. 109.3
 CITY AMENDMENTS TO FBC. UPDATE VALUATIONS AS REQUIRED.
 VALUATION TO INCLUDE ALL PROFESSIONAL DESIGN FEES, ALL
 LABOR AND MATERIALS AND CONTRACTOR'S OVERHEAD AND
 PROFIT. PROVIDE COPY OF SIGNED CONTRACT SIGNED BY OWNER
 AND CONTRACTOR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-02 Cont ID  
Sent By jgomez Date 2012-11-02 Time 15:05 Rev Time 0.00
Received By jgomez Date 2012-11-02 Time 13:51 Sent To  
Notes
2012-11-02 16:14:44RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.3 AND SEC. 103.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- BEDROOM #1: FRONT WINDOW IS GOING TO BE ENCLOSED.
 SPECIFY SIZE OF EXISTING WINDOW TO BE ENCLOSED. EGRESS
 CAN'T BE REDUCED. SEC. 601.2 OF 2010 FBC-EXISTING
 BUILDING. PROVIDE WINDOW MANUFACTURER CUT SHEETS FOR
 OTHER WINDOW ON THIS BEDROOM TO DEMONSTRATE THAT THIS
 WINDOW WILL MEET THE EGRESS REQUIREMENTS OF SEC. R310
 OF 2010 FBC-RESIDENTIAL.
  
 3- SHEET 1.2:
 A) DESIGN PARAMETERS: (1) REVISE THE ROOF LIVE LOAD.
 SEE TABLE R301.6 OF 2010 FBC-RESIDENTIAL AND REVISE AS
 REQUIRED. (2) ALSO REVISE THE ROOF LIVE LOAD SHOWN ON
 STRUCTURAL NOTE #2(A).
  
 B) REVISE STRUCTURAL NOTE #2(C). DESIGN PARAMETERS
 SPECIFY EXPOSURE "D" NOT "B". REVISE AS REQUIRED TO
 MATCH.
  
 C) SPECIFY SAFETY GLASS AS REQUIRED BY SEC. R308.4 FOR
 EAST WINDOWS ON BOTH BEDROOMS. AND, FOR BATHROOM
 WINDOW. THIS APPLIES IF WINDOWS DON'T HAVE IMPACT
 GLASS. PRODUCT APPROVAL WAS NOT SUBMITTED.
  
 D) UTILITY AREA NEW OUTDOOR STEPS: (1) PROVIDE LANDING
 AS REQUIRED BY SEC. R311.3. (2) PROVIDE HANDRAILS AS
 REQUIRED BY SEC. R311.7.7.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL WINDOWS AS SHOWN ON PLANS.
  
 B) ALL EXTERIOR DOORS AS SHOWN ON PLANS.
  
 C) ALL WINDOW MULLIONS AS SHOWN ON PLANS.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND
 PAGE SHOWING THE CONNECTOR.
  
 E) STORM SHUTTERS IF WINDOWS AND DOORS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. UPDATE
 VALUATIONS AS REQUIRED. VA;LUATION TO INCLUDE ALL
 PROFESSIONAL DESIGN FEES, ALL LABOR AND MATERIALS AND
 CONTRACTOR'S OVERHEAD AND PROFIT. PROVIDE COPY OF
 SIGNED CONTRACT SIGNED BY OWNER AND CONTRACTOR.
  
 7- SHEET 2.2:
 A) DESIGN PRESSURES FOR DOORS AND WINDOWS DON'T
 CORRESPOND TO EXPOSURE "D' AS SPECIFIED ON THE DESIGN
 CRITERIA ON SHEET 1.2. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 B) TYPICAL WOOD FRAME DETAILS FOR WINDOWS, DOORS AND
 WALLS: (1) SPECIFY SIZE OF HEADERS. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC. (2) BELOW THE WINDOW OPENINGS THERE
 IS A NOTE SAYING THAT NO CONNECTORS ARE REQUIRED.
 CLARIFY WHY NOT. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 8- PROVIDE COMPLETE WALL SECTION SHOWING ALL FRAMING
 MEMBERS, CONNECTORS, INSULATION, WALL SHEATHING, DOUBLE
 VAPOR BARRIER, STUCCO THICKNESS, ETC. AS REQUIRED BY
 SEC. 107.3.5.3(5) CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-12-05 Cont ID  
Sent By rlecky Date 2012-12-05 Time 11:16 Rev Time 0.00
Received By rlecky Date 2012-12-05 Time 11:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-11-05 Cont ID  
Sent By rlecky Date 2012-11-05 Time 08:42 Rev Time 0.00
Received By rlecky Date 2012-11-05 Time 08:10 Sent To  
Notes
2012-11-05 08:45:2612100028
 317 KENILWORTH BLVD.
 SFD REMODEL
  
 PLEASE PROVIDE A RESPONSE TO THE FOLLOWING ELECTRICAL
 REVIEW COMMENTS.
  
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. 2010 FBC R314, 315
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 FRONT AND BACK ENTRANCE AREA. NEC 210.70
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2012-12-14 Cont ID  
Sent By jroach Date 2012-12-14 Time 11:43 Rev Time 0.00
Received By jroach Date 2012-12-14 Time 11:43 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2012-10-03 Cont ID  
Sent By fmittner Date 2012-10-03 Time 16:40 Rev Time 0.00
Received By fmittner Date 2012-10-03 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-07 Cont ID  
Sent By jgomez Date 2012-12-07 Time 17:02 Rev Time 0.00
Received By jgomez Date 2012-12-04 Time 14:41 Sent To  
Notes
2012-12-04 14:42:01EXPEDITED
 R--8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-05 Cont ID  
Sent By rlecky Date 2012-11-05 Time 08:42 Rev Time 0.00
Received By rlecky Date 2012-10-02 Time 12:31 Sent To  
Notes
2012-10-04 14:34:26R--8
2012-10-03 12:32:49SENT TO ZONING FOR HISTORICAL REVIEW

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2012-12-14 Cont ID  
Sent By lmartine Date 2012-12-14 Time 13:14 Rev Time 0.00
Received By lmartine Date 2012-12-14 Time 13:14 Sent To  
Notes
2012-12-14 13:18:05*** NOTE: ***
  
 1) PROVIDE MECHANICAL PLANS AND INFORMATION ASKED FOR
 BELOW WHEN APPLYING FOR THE MECHANICAL PERMIT.
 1) SUBMIT COMPLETE COOLING LOAD CAL'S. NOT JUST A ONE
 PAGE SUMMARY UNLESS IT IS SEALED AND SIGNED BY AN
 ENGINEER. SEE 2010 FBC/ENERGY 403.6.1 EXCEPTION 2 AND
 FBC/ R M1401.3.
 2) PROVIDE COMBUSTION AIR CAL'S. OR COMBUSTION AIR FOR
 GAS CLOTHES DRYER IN THE UTILITY ROOM. PER 2010 FBC/R
 G2407.1
  
 MECHANICAL PLAN REVIEW BY: TOM GORDON (HY-BYRD INC.)
 FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-12-06 Cont ID  
Sent By lmartine Date 2012-12-06 Time 15:22 Rev Time 0.00
Received By lmartine Date 2012-12-06 Time 15:22 Sent To  
Notes
2012-12-06 15:43:38*** CORRECTIONS NEEDED TO MECHANICAL PLANS ***
  
 1) SUBMIT COMPLETE COOLING LOAD CAL'S. NOT JUST A ONE
 PAGE SUMMARY UNLESS IT IS SEALED AND SIGNED BY AN
 ENGINEER. SEE 2010 FBC/ENERGY 403.6.1 EXCEPTION 2 AND
 FBC/ R M1401.3.
 2) PROVIDE COMBUSTION AIR CAL'S. OR COMBUSTION AIR FOR
 GAS CLOTHES DRYER IN THE UTILITY ROOM. PER 2010 FBC/R
 G2407.1
  
 MECHANICAL PLAN REVIEW BY: TOM GORDON (HY-BYRD INC.)
 FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-10-25 Cont ID  
Sent By hmoser Date 2012-10-25 Time 10:56 Rev Time 0.00
Received By hmoser Date 2012-10-25 Time 10:40 Sent To  
Notes
2012-10-25 10:56:27PLANS DENIED
 PROVIDE ENERGY CALCULATIONS WITH THE PLANS.
 PER SECTION 403.6.1 EQUIPMENT SIZING. FLORIDA
 ENERGY CODE 2010
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-11-02 Cont ID  
Sent By jgomez Date 2012-11-02 Time 16:15 Rev Time 0.00
Received By jgomez Date 2012-11-02 Time 16:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-12-14 Cont ID  
Sent By jroach Date 2012-12-14 Time 11:43 Rev Time 0.00
Received By jroach Date 2012-12-14 Time 11:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-10-03 Cont ID  
Sent By fmittner Date 2012-10-03 Time 16:40 Rev Time 0.00
Received By fmittner Date 2012-10-03 Time 16:09 Sent To  
Notes
2012-10-03 16:09:29GAVE TO F.M.