Plan Review Details - Permit 12100015
Plan Review Stops For Permit 12100015
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-11-27 Cont ID  
Sent By jwitmer Date 2012-11-27 Time 09:53 Rev Time 0.00
Received By jwitmer Date 2012-11-27 Time 10:01 Sent To  
Notes
2012-11-27 09:59:56BUILDING PLAN REVIEW
 PERMIT: 12100015
 ADD: 2316 S DIXIE HWY
 CONT: ARCA CONSTRUCTION
 TEL: (772)336-4296
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 4A) 11/21/2012 I SPOKE WITH THE DESIGNER OF RECORD A
 CORRECTED WIND DESIGN CRITERIA WILL NEED TO BE
 SUBMITTED , PLEASE CALCULATE TO AT LEAST THE MINIMUM
 FOR OUR WIND SPEED ZONE OF 170 MPH VULT.
 4B) KIOSK LETTER FOR FLOOR ANCHORING DOES NOT HAVE
 TYPED THE PERMIT NUMBER AND ADDRESS LOCATION, THESE ARE
 HAND WRITTEN IN, IT CAN BE TAKEN THIS IS A GENERIC
 LETTER, PLEASE INDICATE PERMIT AND LOCATION IN THE
 LETTER HEADING.
 4C) ROY BROWN IS INDICATED ON THE PLANS AS THE ENGINEER
 OF RECORD, SHOP DRAWING STAMP FROM MR BROWN IS MISSING
 INDICATING THAT HE HAS REVIEWED AND ACCEPTEDED THESE
 DOCUMENTS. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER
 SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO
 THE ENGINEER OF RECORD FOR REVIEW.
  
  
 6) COMPLIED.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-11-27 Cont ID  
Sent By jwitmer Date 2012-11-16 Time 14:18 Rev Time 0.00
Received By jwitmer Date 2012-11-15 Time 11:21 Sent To  
Notes
2012-11-16 14:04:20BUILDING PLAN REVIEW
 PERMIT: 12100015
 ADD: 2316 S DIXIE HWY
 CONT: ARCA CONSTRUCTION
 TEL: (772)336-4296
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 NOV. 16/ 2012
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4A) 2ND REVIEW , SUBMITTED WIND LOAD CALCULATIONS ARE
 DESIGNED AT 180 MPH VULT, COMPONENTS AND CLADDING ARE
 DESIGNED AT 160 MPH VULT, PLEASE CALCULATE TO AT LEAST
 THE MINIMUM FOR OUR WIND SPEED ZONE OF 170 MPH VULT.
 4B) KIOSK LETTER FOR FLOOR ANCHORING DOES NOT HAVE
 TYPED THE PERMIT NUMBER AND ADDRESS LOCATION, THESE ARE
 HAND WRITTEN IN, IT CANBE TAKEN THIS IS A GENARIC
 LETTER, PLEASE INDICATE PERMIT AND LOCATION IN THE
 LETTER HEADING.
 4C) ROY BROWN IS INDICATED ON THE PLANS AS THE ENGINEER
 OF RECORD, SHOP DRAWING STAMP FROM MR BROWN IS MISSING
 INDICATING THAT HE HAS REVIEWED AND ACCEPTEDED THESE
 DOCUMENTS. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER
 SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO
 THE ENGINEER OF RECORD FOR REVIEW.
  
 5) 2ND REQUEST, SHEET C-1 AND P-1 DOESN'T SPECIFY IF
 THIS BUILDING HOUSES 1 TENANT OR TWO TENANTS IF TWO
 TENANTS THEN 2010 FBC-B 709.1.6 APPLIES NEEDING 1 HOUR
 SEPERATION. C1 CODE / PROJECT INFORMATION NOTE # 9
 OCCUPANCY SEPERATION REQUIRED, THE CODE STATEMENT OF "
 NO DIMISSING WALL EXIST OR IS PROPOSED" DOES NOT ANSWER
 IF TWO TENANTS ARE TO OCCUPY THIS BUILDING REQUIRING
 TENANT SEPERATION WALL UNDER 2010 FBC-B 709.1(6).
  
 6) COMPLIED.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-10-10 Cont ID  
Sent By jwitmer Date 2012-10-10 Time 16:08 Rev Time 0.00
Received By jwitmer Date 2012-10-10 Time 16:08 Sent To  
Notes
2012-10-10 16:38:22BUILDING PLAN REVIEW
 PERMIT: 12100015
 ADD: 2316 S DIXIE HWY
 CONT: ARCA CONSTRUCTION
 TEL: (772)336-4296
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 OCT. 10/ 2012
 ACTION: DENIED
  
 1) SHEET P-2 THE MODIFIED WINDOW DETAIL INDICATES THE
 USE OF A SIMPSON ABU66 POST BASEFOR USE WITH THE BUILT
 UP POST/ COLUMN. PLEASE PROVIDE FLORIDA PRODUCT
 APPROVAL FOR SIMPSON ABU66 AND PROVIDE TYPE OF ANCHORS
 TO BE INSTALLED IN THE SLAB AND BEAM ABOVE. PROVIDE
 QUANITY OF ANCHORS, DIAMETER AND LENGTH OF ANCHOR TYPE.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: 9N-3
 (31)(G) STRUCTURAL COMPONENTS.
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS, ...
  
 3) P-2 INDICATES THE REMOVAL OF WINDOW, THE MULLION
 WILL STILL BE PART OF THE COMPONENTS AND CLADDING HOW
 WILL THE MULLION AND NEW POST/ COLUMN BE COMBINED, OLD
 MULLIONS DID NOT TRANSFER LOADS WITH TOP AND BOTTOM
 ANGLE PLATES? ADDITIONAL INFORMATION REQUIRED
 107.2.1.3.
  
 4)PROVISO: P-2 INDICATES THE KIOSK ENGINEERING BY
 OTHERS, PLEASE PROVIDE ENGINEERING BEFORE FRAMING
 INSPECTION. THE KIOSK IS PART OF COMPEONENTS & CLADDING
 AND WILL REQUIRE ENGINEERING FOR 170 MPH 3ECOND GUST V
 ULTIMATE. 2010 FBC-B 1609.4.4.1.
  
 5) SHEET C-1 AND P-1 DOESN'T SPECIFY IF THIS BUILDING
 HOUSES 1 TENANT OR TWO TENANTS IF TWO TENANTS THEN 2010
 FBC-B 709.1.6 APPLIES NEEDING 1 HOUR SEPERATION.
  
 6) THE OTHER ISSUE C-1 & P-1 DOESN'T INDICATE THIS TO
 BE A MIXED USE OCCUPANCY , PLEASE NOTE TABLE 508.4 DOES
 NOT REQUIRE RATING BETWEEN THE TWO OCCUPANCIES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-11-19 Cont ID  
Sent By rlecky Date 2012-11-19 Time 14:53 Rev Time 0.00
Received By rlecky Date 2012-11-19 Time 12:46 Sent To  
Notes
2012-11-19 12:52:52THE FOLLOWING CODE REQUIREMENTS WERE NOTED ON THE PLAN.
  
 ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GFCI PROTECTION. NEC 422.52
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-10-11 Cont ID  
Sent By rlecky Date 2012-10-11 Time 12:25 Rev Time 0.00
Received By rlecky Date 2012-10-11 Time 12:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-11-26 Cont ID  
Sent By wjolin Date 2012-11-20 Time 13:17 Rev Time 0.00
Received By wjolin Date 2012-11-20 Time 13:09 Sent To  
Notes
2012-11-20 13:17:052316 SOUTH DIXIE HIGHWAY
 PERMIT #12100015
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 CONFIRM THIS BUILDING IS HOUSING THE SAME TENANT AND NO
 FIRE-RATED TENANT SEPARATION IS REQUIRED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-10-06 Cont ID  
Sent By wjolin Date 2012-10-06 Time 21:10 Rev Time 0.00
Received By wjolin Date 2012-10-06 Time 20:44 Sent To  
Notes
2012-10-06 21:10:012316 SOUTH DIXIE HIGHWAY
 PERMIT #12100015
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO FIRE-RATED TENANT SEPARATION PROVIDED.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 CONFIRM NO DRY CLEANING (ONLY PICK-UP) WILL OCCUR AT
 THIS LOCATION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-11-20 Cont ID  
Sent By jwitmer Date 2012-11-20 Time 09:34 Rev Time 0.00
Received By jwitmer Date 2012-11-14 Time 11:14 Sent To  
Notes
2012-11-15 11:15:53SUBMITTED ENG. FOR KIOSK
 PUT WITH PACKAGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date 2012-11-27 Cont ID  
Sent By jwitmer Date 2012-11-20 Time 09:33 Rev Time 0.00
Received By jwitmer Date 2012-11-13 Time 12:33 Sent To  
Notes
2012-11-13 12:36:25B8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-10-22 Cont ID  
Sent By rlecky Date 2012-10-22 Time 14:15 Rev Time 0.00
Received By rlecky Date 2012-10-01 Time 11:25 Sent To  
Notes
2012-10-03 11:28:02B--16

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-11-19 Cont ID  
Sent By lwagner Date 2012-11-19 Time 16:02 Rev Time 0.00
Received By lwagner Date 2012-11-19 Time 16:02 Sent To  
Notes
2012-11-19 16:02:56PLUMBING ON E-1

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-10-10 Cont ID  
Sent By lwagner Date 2012-10-10 Time 11:20 Rev Time 0.00
Received By lwagner Date 2012-10-10 Time 10:22 Sent To  
Notes
2012-10-10 11:17:55FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. A FORWARD APPROACH COMPLYING WITH 606.2 OR A
 PARALLEL APPROACH FOR THE BREAK SINK IS REQUIRED (24"
 CENTER).
 FBC 2010 ACCESSIBILITY CODE 606.2 (1)
  
 2. NO PLUMBING DRAWINGS WERE SHOWN ON PLAN.
 FBC LOCAL AMENDMENTS 107.3.5.1.3 (3, 4, 13)
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-10-17 Cont ID  
Sent By avann Date 2012-10-17 Time 11:40 Rev Time 0.00
Received By ajones Date 2012-10-17 Time 11:40 Sent To  
Notes
2012-10-17 11:44:03PRIOR TO THE FINAL BUILDING INSPECTION, APPLICANT MUST
 COMPLY WITH THE CONDITIONS OF APPROVAL OF ZBA CASE NO.
 3291 AS FOLLOWS:
  
 A. THE ACCESS DRIVE ALONG VALENCIA ROAD SHALL BE
 DESIGNATED AS ENTRANCE ONLY. PROPER SIGNAGE SHALL BE
 INSTALLED TO DIRECT TRAFFIC CIRCULATION ON THE SITE.
 B. THE HOURS OF OPERATION OF THE KIOSK SHALL BE LIMITED
 TO 6:00 A.M. TO 12 MIDNIGHT.
 C. THE APPLICANT SHALL WORK WITH THE CITY ARBORIST TO
 EVALUATE THE CONDITION OF THE LANDSCAPING ON THE SITE
 AND BRING IT UP TO CODE REQUIREMENTS AND/OR A HEALTHY
 CONDITION.
 D. THE APPLICANT WILL CREATE A SECURE AND WELL-LIT AREA
 FOR AFTER-HOURS PICK-UP AND DROP-OFF, INCLUDING BUT NOT
 LIMITED TO LIGHTING AND SECURITY CAMERAS.
  
 ANGELLA VANN, PLANNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]
  