| Plan Review Stops For Permit 12100015 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2012-11-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-11-27 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-11-27 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2012-11-27 09:59:56 | BUILDING PLAN REVIEW | | | PERMIT: 12100015 | | | ADD: 2316 S DIXIE HWY | | | CONT: ARCA CONSTRUCTION | | | TEL: (772)336-4296 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | PROVISO: | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | 4A) 11/21/2012 I SPOKE WITH THE DESIGNER OF RECORD A | | | CORRECTED WIND DESIGN CRITERIA WILL NEED TO BE | | | SUBMITTED , PLEASE CALCULATE TO AT LEAST THE MINIMUM | | | FOR OUR WIND SPEED ZONE OF 170 MPH VULT. | | | 4B) KIOSK LETTER FOR FLOOR ANCHORING DOES NOT HAVE | | | TYPED THE PERMIT NUMBER AND ADDRESS LOCATION, THESE ARE | | | HAND WRITTEN IN, IT CAN BE TAKEN THIS IS A GENERIC | | | LETTER, PLEASE INDICATE PERMIT AND LOCATION IN THE | | | LETTER HEADING. | | | 4C) ROY BROWN IS INDICATED ON THE PLANS AS THE ENGINEER | | | OF RECORD, SHOP DRAWING STAMP FROM MR BROWN IS MISSING | | | INDICATING THAT HE HAS REVIEWED AND ACCEPTEDED THESE | | | DOCUMENTS. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER | | | SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO | | | THE ENGINEER OF RECORD FOR REVIEW. | | | | | | | | | 6) COMPLIED. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2012-11-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-11-16 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-11-15 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2012-11-16 14:04:20 | BUILDING PLAN REVIEW | | | PERMIT: 12100015 | | | ADD: 2316 S DIXIE HWY | | | CONT: ARCA CONSTRUCTION | | | TEL: (772)336-4296 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | NOV. 16/ 2012 | | | ACTION: DENIED | | | | | | 1-3) COMPLIED. | | | | | | 4A) 2ND REVIEW , SUBMITTED WIND LOAD CALCULATIONS ARE | | | DESIGNED AT 180 MPH VULT, COMPONENTS AND CLADDING ARE | | | DESIGNED AT 160 MPH VULT, PLEASE CALCULATE TO AT LEAST | | | THE MINIMUM FOR OUR WIND SPEED ZONE OF 170 MPH VULT. | | | 4B) KIOSK LETTER FOR FLOOR ANCHORING DOES NOT HAVE | | | TYPED THE PERMIT NUMBER AND ADDRESS LOCATION, THESE ARE | | | HAND WRITTEN IN, IT CANBE TAKEN THIS IS A GENARIC | | | LETTER, PLEASE INDICATE PERMIT AND LOCATION IN THE | | | LETTER HEADING. | | | 4C) ROY BROWN IS INDICATED ON THE PLANS AS THE ENGINEER | | | OF RECORD, SHOP DRAWING STAMP FROM MR BROWN IS MISSING | | | INDICATING THAT HE HAS REVIEWED AND ACCEPTEDED THESE | | | DOCUMENTS. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER | | | SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO | | | THE ENGINEER OF RECORD FOR REVIEW. | | | | | | 5) 2ND REQUEST, SHEET C-1 AND P-1 DOESN'T SPECIFY IF | | | THIS BUILDING HOUSES 1 TENANT OR TWO TENANTS IF TWO | | | TENANTS THEN 2010 FBC-B 709.1.6 APPLIES NEEDING 1 HOUR | | | SEPERATION. C1 CODE / PROJECT INFORMATION NOTE # 9 | | | OCCUPANCY SEPERATION REQUIRED, THE CODE STATEMENT OF " | | | NO DIMISSING WALL EXIST OR IS PROPOSED" DOES NOT ANSWER | | | IF TWO TENANTS ARE TO OCCUPY THIS BUILDING REQUIRING | | | TENANT SEPERATION WALL UNDER 2010 FBC-B 709.1(6). | | | | | | 6) COMPLIED. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-10-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-10-10 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-10-10 |
Time |
16:08 |
Sent To |
|
|
| Notes |
| 2012-10-10 16:38:22 | BUILDING PLAN REVIEW | | | PERMIT: 12100015 | | | ADD: 2316 S DIXIE HWY | | | CONT: ARCA CONSTRUCTION | | | TEL: (772)336-4296 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | OCT. 10/ 2012 | | | ACTION: DENIED | | | | | | 1) SHEET P-2 THE MODIFIED WINDOW DETAIL INDICATES THE | | | USE OF A SIMPSON ABU66 POST BASEFOR USE WITH THE BUILT | | | UP POST/ COLUMN. PLEASE PROVIDE FLORIDA PRODUCT | | | APPROVAL FOR SIMPSON ABU66 AND PROVIDE TYPE OF ANCHORS | | | TO BE INSTALLED IN THE SLAB AND BEAM ABOVE. PROVIDE | | | QUANITY OF ANCHORS, DIAMETER AND LENGTH OF ANCHOR TYPE. | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: 9N-3 | | | (31)(G) STRUCTURAL COMPONENTS. | | | | | | 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS, ... | | | | | | 3) P-2 INDICATES THE REMOVAL OF WINDOW, THE MULLION | | | WILL STILL BE PART OF THE COMPONENTS AND CLADDING HOW | | | WILL THE MULLION AND NEW POST/ COLUMN BE COMBINED, OLD | | | MULLIONS DID NOT TRANSFER LOADS WITH TOP AND BOTTOM | | | ANGLE PLATES? ADDITIONAL INFORMATION REQUIRED | | | 107.2.1.3. | | | | | | 4)PROVISO: P-2 INDICATES THE KIOSK ENGINEERING BY | | | OTHERS, PLEASE PROVIDE ENGINEERING BEFORE FRAMING | | | INSPECTION. THE KIOSK IS PART OF COMPEONENTS & CLADDING | | | AND WILL REQUIRE ENGINEERING FOR 170 MPH 3ECOND GUST V | | | ULTIMATE. 2010 FBC-B 1609.4.4.1. | | | | | | 5) SHEET C-1 AND P-1 DOESN'T SPECIFY IF THIS BUILDING | | | HOUSES 1 TENANT OR TWO TENANTS IF TWO TENANTS THEN 2010 | | | FBC-B 709.1.6 APPLIES NEEDING 1 HOUR SEPERATION. | | | | | | 6) THE OTHER ISSUE C-1 & P-1 DOESN'T INDICATE THIS TO | | | BE A MIXED USE OCCUPANCY , PLEASE NOTE TABLE 508.4 DOES | | | NOT REQUIRE RATING BETWEEN THE TWO OCCUPANCIES. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2012-11-19 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-11-19 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-11-19 |
Time |
12:46 |
Sent To |
|
|
| Notes |
| 2012-11-19 12:52:52 | THE FOLLOWING CODE REQUIREMENTS WERE NOTED ON THE PLAN. | | | | | | ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH | | | GFCI PROTECTION. NEC 422.52 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-10-11 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-10-11 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-10-11 |
Time |
12:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2012-11-26 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-11-20 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-11-20 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2012-11-20 13:17:05 | 2316 SOUTH DIXIE HIGHWAY | | | PERMIT #12100015 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | CONFIRM THIS BUILDING IS HOUSING THE SAME TENANT AND NO | | | FIRE-RATED TENANT SEPARATION IS REQUIRED. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2012-10-06 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-10-06 |
Time |
21:10 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-10-06 |
Time |
20:44 |
Sent To |
|
|
| Notes |
| 2012-10-06 21:10:01 | 2316 SOUTH DIXIE HIGHWAY | | | PERMIT #12100015 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | NO FIRE-RATED TENANT SEPARATION PROVIDED. | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | CONFIRM NO DRY CLEANING (ONLY PICK-UP) WILL OCCUR AT | | | THIS LOCATION. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2012-11-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-11-20 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-11-14 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2012-11-15 11:15:53 | SUBMITTED ENG. FOR KIOSK | | | PUT WITH PACKAGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
|
Date |
2012-11-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-11-20 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-11-13 |
Time |
12:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-10-22 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-10-22 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-10-01 |
Time |
11:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2012-11-19 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2012-11-19 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2012-11-19 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2012-11-19 16:02:56 | PLUMBING ON E-1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2012-10-10 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2012-10-10 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2012-10-10 |
Time |
10:22 |
Sent To |
|
|
| Notes |
| 2012-10-10 11:17:55 | FBC 2010 EXISTING BUILDING CODE | | | FBC 2010 ACCESSIBILITY CODE | | | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. A FORWARD APPROACH COMPLYING WITH 606.2 OR A | | | PARALLEL APPROACH FOR THE BREAK SINK IS REQUIRED (24" | | | CENTER). | | | FBC 2010 ACCESSIBILITY CODE 606.2 (1) | | | | | | 2. NO PLUMBING DRAWINGS WERE SHOWN ON PLAN. | | | FBC LOCAL AMENDMENTS 107.3.5.1.3 (3, 4, 13) | | | | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2012-10-17 |
|
|
Cont ID |
|
| Sent By |
avann |
Date |
2012-10-17 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2012-10-17 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2012-10-17 11:44:03 | PRIOR TO THE FINAL BUILDING INSPECTION, APPLICANT MUST | | | COMPLY WITH THE CONDITIONS OF APPROVAL OF ZBA CASE NO. | | | 3291 AS FOLLOWS: | | | | | | A. THE ACCESS DRIVE ALONG VALENCIA ROAD SHALL BE | | | DESIGNATED AS ENTRANCE ONLY. PROPER SIGNAGE SHALL BE | | | INSTALLED TO DIRECT TRAFFIC CIRCULATION ON THE SITE. | | | B. THE HOURS OF OPERATION OF THE KIOSK SHALL BE LIMITED | | | TO 6:00 A.M. TO 12 MIDNIGHT. | | | C. THE APPLICANT SHALL WORK WITH THE CITY ARBORIST TO | | | EVALUATE THE CONDITION OF THE LANDSCAPING ON THE SITE | | | AND BRING IT UP TO CODE REQUIREMENTS AND/OR A HEALTHY | | | CONDITION. | | | D. THE APPLICANT WILL CREATE A SECURE AND WELL-LIT AREA | | | FOR AFTER-HOURS PICK-UP AND DROP-OFF, INCLUDING BUT NOT | | | LIMITED TO LIGHTING AND SECURITY CAMERAS. | | | | | | ANGELLA VANN, PLANNING AND ZONING ADMINISTRATOR | | | 561-822-1441 | | | [email protected] | | | |
|
|