| 2012-09-27 12:24:37 | BUILDING PLAN REVIEW |
| | PERMIT: 12090709 |
| | ADD: 1483 N MANGONIA CIR |
| | CONT: LLOYD'S ROOFING |
| | TEL: (561)312-0803 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | PROVISO: |
| | 1507.2.5 ASPHALT SHINGLES. |
| | |
| | 1507.2.8 UNDERLAYMENT APPLICATION. |
| | |
| | FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS |
| | HORIZONTAL (17-PERCENT SLOPE) AND UP TO FOUR UNITS |
| | VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE), |
| | UNDERLAYMENT SHALL BE TWO LAYERS APPLIED IN THE |
| | FOLLOWING MANNER. APPLY A MINIMUM 19-INCH-WIDE (483 MM) |
| | STRIP OF UNDERLAYMENT FELT PARALLEL WITH AND STARTING |
| | AT THE EAVES, FASTENED SUFFICIENTLY TO HOLD IN PLACE. |
| | STARTING AT THE EAVE, APPLY 36-INCH-WIDE (914 MM) |
| | SHEETS OF UNDERLAYMENT OVERLAPPING SUCCESSIVE SHEETS 19 |
| | INCHES (483 MM), BY FASTENED SUFFICIENTLY TO HOLD IN |
| | PLACE. DISTORTIONS IN THE UNDERLAYMENT SHALL NOT |
| | INTERFERE WITH THE ABILITY OF THE SHINGLES TO SEAL. FOR |
| | ROOF SLOPES OF FOUR UNITS VERTICAL IN 12 UNITS |
| | HORIZONTAL (33-PERCENT SLOPE) OR GREATER, UNDERLAYMENT |
| | SHALL BE ONE LAYER APPLIED IN THE FOLLOWING MANNER. |
| | UNDERLAYMENT SHALL BE APPLIED SHINGLE FASHION, PARALLEL |
| | TO AND STARTING FROM THE EAVE AND LAPPED 2 INCHES (51 |
| | MM), FASTENED SUFFICIENTLY TO HOLD IN PLACE. |
| | DISTORTIONS IN THE UNDERLAYMENT SHALL NOT INTERFERE |
| | WITH THE ABILITY OF THE SHINGLES TO SEAL. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |