Plan Review Details - Permit 12090615
Plan Review Stops For Permit 12090615
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-01-16 Cont ID  
Sent By rlecky Date 2013-01-16 Time 11:27 Rev Time 0.00
Received By rlecky Date 2013-01-16 Time 11:27 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2012-10-03 Cont ID  
Sent By rlecky Date 2012-10-03 Time 13:30 Rev Time 0.00
Received By rlecky Date 2012-10-03 Time 13:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-01-15 Cont ID  
Sent By rferguso Date 2013-01-15 Time 15:01 Rev Time 0.00
Received By rferguso Date 2013-01-15 Time 15:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-11-17 Cont ID  
Sent By wjolin Date 2012-11-17 Time 15:53 Rev Time 0.00
Received By wjolin Date 2012-11-17 Time 15:49 Sent To  
Notes
2012-11-17 15:53:012716 OKEECHOBEE BLVD
 PERMIT # 12040166
 TRACKING #12090615
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FLORIDA BUILDING CODE SECTION 105.3.1.2 REQUIRES THE
 PLANS TO BE DESIGNED AND SIGNED/SEALED BY A
 PROFESSIONAL ENGINEER, NOT AN ARCHITECT (REFERENCE
 FLORIDA STATUTE 471).
  
 REPEAT COMMENT: FIRE ALARM PLANS SHALL BE SIGNED AND
 SEALED BY A PROFESSIONAL ENGINEER WHEN THE JOB VALUE
 EXCEEDS $5,000.
  
 BATTERY CALCULATIONS NOT SUBMITTED FOR ANY NAC
 CIRCUITS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-10-02 Cont ID  
Sent By wjolin Date 2012-10-02 Time 12:30 Rev Time 0.00
Received By wjolin Date 2012-10-02 Time 12:12 Sent To E
Notes
2012-10-02 12:30:232716 OKEECHOBEE BLVD
 PERMIT # 12040166
 TRACKING #12090615
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE ALARM PLANS SHALL BE SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER WHEN THE JOB VALUE EXCEEDS
 $5,000.
  
 THE REVISION CLOUDS DO NOT MATCH THE INCREASED SCOPE OF
 WORK.
  
 VOLTAGE DROP AND BATTERY CALCULATIONS NOT SUBMITTED.
  
 PLANS DO NOT INDICATE ROOM NAMES/NUMBERS, CEILING
 HEIGHTS ETC.
  
 SPACING AND LOCATION OF FIRE ALARM NOTIFICATION
 APPLIANCES LEAVE SEVERAL AREAS WITH INSUFFICIENT
 NOTIFCATION. FOR EXAMPLE THE SOUTHWEST ROOM HAS ONLY
 ONE APPLIANCE AND IS LOCATED A GREAT DISTANCE FROM THE
 EAST WALL.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-01-16 Cont ID  
Sent By shill Date 2013-01-16 Time 14:15 Rev Time 0.00
Received By tgordon Date 2013-01-14 Time 10:22 Sent To  
Notes
2013-01-14 10:22:36TO FIRE BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-11-17 Cont ID  
Sent By wjolin Date 2012-11-17 Time 15:53 Rev Time 0.00
Received By wjolin Date 2012-11-08 Time 10:16 Sent To  
Notes
2012-11-13 08:13:48SENT TO FIRE BOX
2012-11-09 10:16:41RESUB OF A REVISION WITH NO FEES APPLIED. GAVE TO SANDY
 WURAFTIC. RM

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-10-03 Cont ID  
Sent By rlecky Date 2012-10-03 Time 13:32 Rev Time 0.00
Received By rlecky Date 2012-09-25 Time 11:00 Sent To  
Notes
2012-09-25 11:01:12TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-01-16 Cont ID  
Sent By tgordon Date 2013-01-16 Time 14:14 Rev Time 0.00
Received By tgordon Date 2013-01-16 Time 14:14 Sent To  
Notes
2013-01-16 14:15:07REV. TO FIRE ALARM PLANS 1 OF 2, & 2 OF 2.