Plan Review Details - Permit 12090413
Plan Review Stops For Permit 12090413
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-11-09 Cont ID  
Sent By jwitmer Date 2012-11-09 Time 15:03 Rev Time 0.00
Received By jwitmer Date 2012-11-09 Time 13:45 Sent To  
Notes
2012-11-09 15:05:05NO ROOFING CONTRACTOR NOR ROOFING PRODUST APPROVALS
 HAVE BEEN SUBMITTED TO DATE. SEPERATE PERMIT , REVIEW
 AND ASSOCIATED FEES SHALL APPLY. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-09-25 Cont ID  
Sent By jwitmer Date 2012-09-25 Time 14:42 Rev Time 0.00
Received By jwitmer Date 2012-09-24 Time 16:00 Sent To  
Notes
2012-09-24 16:18:04BUILDING PLAN REVIEW
 PERMIT: 12090413
 ADD: 3201 S DIXIE HWY
 CONT: MARION CONSTRUCTION
 TEL: (561)659-5292
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE DESIGNER OF RECORD DOES INDICATE THE PROPOSED
 BUILDING DESIGN WAS DESIGNED TO THE 2010 FBC-B, BUT THE
 PLANS ARE DEFICIENT IN REGARDS TO THE 2010
 EXISTING BUILDING CODE SECTION 101.5 COMPLIANCE
 METHODS. THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY,
 ADDITION OR RELOCATION OF ALL EXISTING BUILDINGS SHALL
 COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 101.5.1 THROUGH 101.5.3 AS SELECTED BY THE APPLICANT.
 APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR
 ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A
 SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE
 OFFICIAL. SECTIONS 101.5.1 THROUGH 101.5.3 SHALL NOT BE
 APPLIED IN COMBINATION WITH EACH OTHER.
  
 2) SHEET 1-A:
  
 2A) IN BOTH OF THE ACCESSIBLE RESTROOMS THE DOOR # 107
 & 203 BOTH SWING OVER THE CLEAR FLOOR SPACE REQUIRED
 FOR THE LAVOTORY.
 213.3 PLUMBING FIXTURES AND ACCESSORIES. PLUMBING
 FIXTURES AND ACCESSORIES PROVIDED IN A TOILET ROOM OR
 BATHING ROOM REQUIRED TO COMPLY WITH 213.2 SHALL COMPLY
 WITH 213.3. 213.2 TOILET ROOMS AND BATHING ROOMS. WHERE
 TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL
 COMPLY WITH 603.
 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE.
  
 2B) COMPLIED.
  
 3) 2010 ACCESSIBILITY CODE: 202.4.1 DISPROPORTIONATE
 COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 3A) SHEET SP-1 DOES NOT INDICATE AN ACCESSIBLE
 ENTRANCE, 2010 ACCESSIBILITY CODE 202.4.1.
  
 3B) IF THE FUNDS HAVE NOT BEEN USED UP UNDER THE
 DISPROPORTIONATE COST, THE LAST ITEM ON THE LIST IS THE
 PARKING LOT, AS THE PLANS SHOW THE ACCESSIBLE PARKING
 SPACE IS NOT THE CLOSEST SPACE TO THE BUILDING FORCING
 THE USER OF THIS SPACE TO TRAVEL BEHIND PARKED CARS,
 THE OTHER ISSUE WITH THE PARKING SPACE IS NO ACCESSIBLE
 AISLE IS INDICATED ON THE PLANS.
  
 4) SHEET A2 THE ELEVATIONS INDICATE THERE IS NO
 OVERHANG, 2010 FBC-B 1503.7 PROTECTION AGAINST DECAY
 AND TERMITES. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 5) A-3 THE WEST ELEVATION DEPICTS AN EXTERIOR STAIR AND
 HANDRAIL GAURDRAIL SYSTEM THAT DOES NOT CONFORM TO THE
 2010 FBC-B. 2010 EXIST BLDG CODE 912.4.2 MEANS OF
 EGRESS FOR CHANGE OF USE TO EQUAL OR LOWER HAZARD
 CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO AN
 EQUAL OR LESSER HAZARD CATEGORY (HIGHER NUMBER) AS
 SHOWN IN TABLE 912.4, EXISTING ELEMENTS OF THE MEANS OF
 EGRESS SHALL COMPLY WITH THE REQUIREMENTS OF SECTION
 805 FOR THE NEW OCCUPANCY CLASSIFICATION. NEWLY
 CONSTRUCTED OR CONFIGURED MEANS OF EGRESS SHALL COMPLY
 WITH THE REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 912.4.5 GUARDS.
 EXISTING GUARDS SHALL COMPLY WITH THE REQUIREMENTS IN
 SECTION 705.10 IN THE AREA OF THE CHANGE OF OCCUPANCY
 CLASSIFICATION.705.10 GUARDS.
  
 THE REQUIREMENTS OF SECTIONS 705.10.1 AND 705.10.2
 SHALL APPLY TO GUARDS FROM THE WORK AREA FLOOR TO, AND
 INCLUDING, THE LEVEL OF EXIT DISCHARGE BUT SHALL BE
 CONFINED TO THE EGRESS PATH OF ANY WORK AREA.
  
  
 705.10.1 MINIMUM REQUIREMENT.
  
 EVERY OPEN PORTION OF A STAIR, LANDING, OR BALCONY THAT
 IS MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR OR
 GRADE BELOW AND IS NOT PROVIDED WITH GUARDS, OR THOSE
 PORTIONS IN WHICH EXISTING GUARDS ARE JUDGED TO BE IN
 DANGER OF COLLAPSING, SHALL BE PROVIDED WITH GUARDS.
 705.10.2 DESIGN.
 GUARDS REQUIRED IN ACCORDANCE WITH SECTION 705.10.1
 SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE
 PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY.
 EXCEPTION: GUARDS BEING REPLACED IN PART MAY MATCH THE
 EXISTING DESIGN.
  
 6) SHEET A4 INDICATES CUT SECTIONS OF INTERIOR
 ELEVATIONS AND FLOOR TRUSSES, PLANS WILL NEED TO
 INCLUDE FIREBLOCKING AT THE FLOOR LINE PER 2010 FBC-B
 717.2 <>. IN COMBUSTIBLE CONSTRUCTION,
 <> SHALL BE INSTALLED TO CUT OFF
 CONCEALED DRAFT OPENINGS (BOTH VERTICAL AND HORIZONTAL)
 AND SHALL FORM AN EFFECTIVE BARRIER BETWEEN FLOORS,
 BETWEEN A TOP STORY AND A ROOF OR ATTIC SPACE.
 <> SHALL BE INSTALLED IN THE LOCATIONS
 SPECIFIED IN SECTIONS 717.2.2 THROUGH 717.2.7.
  
 7) PLEASE PROVIDE MANUFACTURERS TESTING REPORT FOR
 ICYNENE INSULATION, SHEET A4 INDICATES THE ICYNENE TO
 BE INSTALLED ON THE TOP CHORD OF TRUSS WITH A DROPPED
 ACOUSTICAL CEILING. THERE ARE TWO CONCERNS:
  
 7A) 2010 FBC-B SECTION 2603.4.1.6 THE FIRST ISSUE IS
 ICYNENE IS TO BE PROTECTED WITH AN IGNITION BARRIER.
 THE IGNITION BARRIER IS TO SEPERATE THE ATTIC SPACE
 FROM THE INSULATION ITSELF, THE CODE READS THAT THE
 BARRIER IS TO BE INSTALLED IN A MANNER THAT THE FOAM
 PLASTIC INSULATION IS NOT EXPOSED.
  
 7B) THE PLANS INDICATE THE USE OF A DROP CEILING ON THE
 SECOND FLOOR WITH EXCEPTION TO THE STAIRWELL. 2010
 FBC-B SSECTION REQUIRES THE USE OF A THERMAL BARRIER
 THE FOAM PLASTIC SHALL BE SEPERATED FROM THE INTEIOR OF
 A BUILDING BY AN APPROVED THERMAL BARRIER OF 1/2 INCH
 GYPSUM WALLBOARD OR EQUIVALENT THERMAL BARRIER ...
  
 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-11-08 Cont ID  
Sent By rlecky Date 2012-11-08 Time 15:31 Rev Time 0.00
Received By rlecky Date 2012-11-08 Time 14:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-09-28 Cont ID  
Sent By rlecky Date 2012-09-28 Time 08:54 Rev Time 0.00
Received By rlecky Date 2012-09-27 Time 15:26 Sent To  
Notes
2012-09-28 08:55:1512090413
 3201 SOUTH DIXIE
 COMMERCIAL RENOVATION
  
 PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW
 COMMENTS.
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION AS APPROPRIATE TO
 THE DESIGN. NEC 110.22, 110.16
  
 VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED
 WORKING SPACE HAS BEEN PROVIDED AT THE ELECTRICAL
 SERVICE. NEC 110.26, 240.24
  
 INDICATE THE LOCATION OF THE ELEVATOR PANELBOARD. NEC
 215.5
  
 ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GFCI PROTECTION. NEC 422.52
  
 RECEPTACLES IN ELEVATOR EQUIPMENT ROOMS AND PITS
 REQUIRE GFCI PROTECTION. NEC 620.23, 620.85
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2012-11-08 Cont ID  
Sent By mgonzale Date 2012-11-08 Time   Rev Time 0.25
Received By mgonzale Date 2012-11-08 Time   Sent To  
Notes
2012-11-08 15:39:34PASSED
  
 ALL COMMENTS HAVE BEEN RESPONDED TOO.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2012-10-18 Cont ID  
Sent By mgonzale Date 2012-10-18 Time   Rev Time 1.00
Received By mgonzale Date 2012-10-18 Time   Sent To I
Notes
2012-10-18 17:18:07RESPOND TO COMMENTS IN WRITING:
  
 #1 PROVIDE LOCATION OF WATER SERVICE LINE AND IDENTIFY
 BACKFLOW (RPPA)
  
 #2 PROVIDE LOCATION OF SANITARY SEWER CLEAN-OUT AT
 PROPERTY LINE.
  
 #3 PARKING AREA DOES NOT CLEARLY SHOW ADA ACCESSABILITY
 AND ADA PARKING AS PER CITY OF WPB REQUIRES.
  
 #4 PROVIDE PERVIOUS AND IMPERVIOUS AREA CALCULATIONS.
  
 #5 SEPARATE PERMITS MAY BE REQUIRED FOR PARKING PAVING
 OVERLAY OR SEALCOAT.
  
 #6 ANY DRANAGE IMPROVEMENTS MUST BE PERMITTED WITH THE
 CITY OF WEST PALM BEACH ENGINEERING SERVICES
 DEPARTMENT.
 OWNER WILL BE REQUIRED THAT ALL PRIVATE SITE
 IMPROVEMENTS BE DESIGNED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-11-03 Cont ID  
Sent By wjolin Date 2012-11-03 Time 17:23 Rev Time 0.00
Received By wjolin Date 2012-11-03 Time 17:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-09-27 Cont ID  
Sent By wjolin Date 2012-09-27 Time 12:13 Rev Time 0.00
Received By wjolin Date 2012-09-27 Time 10:30 Sent To  
Notes
2012-09-27 11:04:013201 SOUTH DIXIE HIGHWAY
 PERMIT #12090413
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTERS "RF" DESIGNATION
 PER FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE
 CODE 69A-60.0081.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 EXTERIOR STAIR: GUARDS, AT LEAST 42-INCHES TALL, SHALL
 BE PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS THAT
 EXCEED 30-INCHES ABOVE THE FLOOR. OPEN GUARDS SHALL
 PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER SPHERE UP TO
 A HEIGHT OF 34-INCHES. THE TRIANGULAR OPENINGS FORMED
 BY THE RISER, TREAD AND BOTTOM ELEMENT OF THE GUARDRAIL
 SHALL PROHIBIT THE PASSAGE OF A 6-INCH DIAMETER SPHERE.
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND
 NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES.
  
 PROVIDE A FURNITURE LAYOUT FOR THE SECOND FLOOR STAFF
 TRAINING ROOM.
  
 WHILE THERE ARE EXIT SIGNS LEADING TO THE INTERIOR
 STAIR, IT IS UNCLEAR IF THE SECOND FLOOR ENCLOSED STAIR
 IS BEING DESIGNED AS A REQUIRED EGRESS STAIR OR SIMPLY
 A CONVENIENCE OPENING. A SINGLE EXTERIOR MEANS OF
 EGRESS FOR A BUSINESS OCCUPANCY MAY BE PERMITTED;
 HOWEVER, THE CURRENT DESIGN OF THE ENCLOSED STAIR DOES
 NOT COMPLY (AS AN EXIT STAIR) WITH THE LIFE SAFETY CODE
 AS THE STAIR IS UNENCLOSED AT THE TOP OF THE SHAFT AND
 THE STAIR DOES NOT DISCHARGE TO THE EXTERIOR OF THE
 BUILDING AT THE BOTTOM OF THE SHAFT.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-11-16 Cont ID  
Sent By hmoser Date 2012-11-16 Time 09:14 Rev Time 0.00
Received By hmoser Date 2012-10-30 Time 11:14 Sent To  
Notes
2012-10-31 11:15:19SENT TO C7 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-10-19 Cont ID  
Sent By lmartine Date 2012-10-18 Time 11:09 Rev Time 0.00
Received By lmartine Date 2012-09-18 Time 08:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-11-16 Cont ID  
Sent By hmoser Date 2012-11-16 Time 09:14 Rev Time 0.00
Received By hmoser Date 2012-11-14 Time 15:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-10-10 Cont ID  
Sent By hmoser Date 2012-10-10 Time 14:44 Rev Time 0.00
Received By hmoser Date 2012-10-10 Time 13:56 Sent To  
Notes
2012-10-10 14:44:53PLANS DENIED
 1) PROVIDE THE FRESH AIR DUCT SIZE AND
 FRESH AIR CALCULATIONS ON THE PLANS .PER
 TABLE 403.3 FBC (M) 2010
 2) PROVIDE A DETAIL FROM THE ENGINEER
 ON THE CONDENSER TO SLAB TIE DOWN.PER
 SECTION 301.12 WIND RESISTANCE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-11-09 Cont ID  
Sent By lwagner Date 2012-11-09 Time 08:40 Rev Time 0.00
Received By lwagner Date 2012-11-08 Time 16:03 Sent To  
Notes
2012-10-31 11:17:42REVISED SHEETS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-10-02 Cont ID  
Sent By lwagner Date 2012-10-02 Time 13:25 Rev Time 0.00
Received By lwagner Date 2012-10-01 Time 14:37 Sent To  
Notes
2012-10-02 14:58:38****PROVISO****
 1. P-607.1 HOT WATER REQUIRED FOR WASHING & CULINARY
 PURPOSES.
  
 2. MED GAS IS NOT INCLUDED IN THIS REVIEW. SEPARATE
 APPLICATION, PLAN, REVIEW, FEES, AND PERMIT REQUIRED.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2012-11-08 Cont ID  
Sent By eschenid Date 2012-11-08 Time 14:00 Rev Time 0.00
Received By ajones Date 2012-11-05 Time   Sent To  
Notes
2012-11-08 14:16:56PRIOR TO THE ISSUANCE OF A CO OR FINAL INSPECTION THE
 CONTRACTOR MUST DO THE FOLLOWING:
 1). A LANDSCAPE & IRRIGATION PERMIT WILL NEED TO BE
 SUBMITTED, REVIEWED AND APPROVED AND THE WORK PERFORMED
 PRIOR TO FINAL INSPECTIONS.
 2). OBTAIN A PERMIT FROM THE ENGINEERING DEPARTMENT FOR
 THE FOUR (4) NEW ON-STREET PARKING SPACES PROPOSED FOR
 HAMPTION STREET.
 3). OBTAIN A PERMIT FROM FDOT FOR THE ONE (1) NEW
 ON-STREET PARKING SPACE PROPOSED FOR SOUTH DIXIE
 HIGHWAY.
 4). SCREEN THE NEW CONDENSING UNITS ALONG THE NORTH
 PROPERTY LINE.
 5). UNITY OF TITLE MUST BE SUBMITTED AND APPROVED.
  
 ANGELLA VANN, PLANNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2012-10-04 Cont ID  
Sent By eschneid Date 2012-10-04 Time 16:52 Rev Time 2.00
Received By eschneid Date 2012-10-03 Time 19:36 Sent To  
Notes
2012-10-04 12:49:26FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE VALUE OF THE CONSTRUCTION ($420,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($184,932) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 2) THE LANDSCAPE PLAN SHALL VERIFY THAT THE SITE
 CONFORMS TO THE MINIMUM LANDSCAPE PERCENTAGE AFTER THE
 ADDITIONAL SQUARE FOOTAGE AND ANY OTHER HARDSCAPE IS
 ADDED TO THE SITE.
  
 3) THE EXISTING SITE HAS 16 PARKING SPACES THAT THE
 CITY CAN RECOGNIZE AS MEETING CITY STANDARDS. THE
 EXISTING BUILDING REQUIRES 19 PARKING SPACES, SO THE
 SITE IS GRANDFATHERED TO ONLY REQUIRE 16 PARKING
 SPACES. THE ADDITION OF 140 SQUARE FEET OF MEDICAL
 OFFICE USE REQUIRES THE PROVISION OF ONE ADDITIONAL
 PARKING SPACE. PLEASE SHOW WHERE THIS ADDITIONAL
 PARKING SPACE WILL BE PROVIDED. NOTE THAT RESURFACING,
 SEALCOATING OR STRIPING THE PARKING ALL REQUIRES A
 SEPARATE PERMIT.
  
 4) PLEASE EXPLAIN THE LOCATION OF THE 4 NEW CONDENSING
 UNITS. THE SHEET SP-1 DOES NOT SHOW ANY, YET IT APPEARS
 ON SHEETS A-1 AND M-1 THAT THEY WILL BE LOCATED ALONG
 THE NORTH PROPERTY LINE WEST OF THE BUILDING WITHING
 THE REQUIRED LANDSCAPE BUFFER AND SETBACK. THE
 CONDENSING UNITS WILL NEED TO BE SCREENED.
  
 5) WHY IS THERE SO LITTLE FENESTRATION BEING PROPOSED
 ON ANY OF THE FACADES? THERE SEEMS TO BE OPPORTUNITY TO
 INTRODUCE NATURAL LIGHT TO MORE OF THE BUILDING
 (RELATIONSHIP TO FLOOR PLAN).
  
 6) HOW IS TRASH COLLECTION BEING HANDLED? NO DUMPSTER
 OR ENCLOSURE FOR CAN PICK UP (IF APPROVED BY THE CITY'S
 SANITATION DEPARTMENT) IS SHOWN ON THE PLANS.
  
 7) A UNITY OF TITLE IS REQUIRED FOR THE PROPERTY.
 PLEASE CONTACT VINCE NOEL, CITY SURVEYOR, AT (561)
 494-1096 FOR INFORMATION.
  
 8) PLEASE CONSIDER REPLACING THE CHAIN LINK FENCE
 AROUND THE PROPERTY LINE AS IT PRESENTS A RUSTY
 APPEARANCE.
  
 9) THE SIGNAGE REQUIRES A SEPARATE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.