Plan Review Details - Permit 12090357
Plan Review Stops For Permit 12090357
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-01-24 Cont ID  
Sent By jwitmer Date 2013-01-24 Time 08:32 Rev Time 0.00
Received By jwitmer Date 2013-01-23 Time 14:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-09-28 Cont ID  
Sent By jwitmer Date 2012-09-28 Time 11:13 Rev Time 0.00
Received By jwitmer Date 2012-09-28 Time 11:10 Sent To  
Notes
2012-09-28 11:49:23BUILDING PLAN REVIEW
 PERMIT: 12090357
 ADD: 2421 METROCENTRE BLVD E
 CONT: ABAT BUILDERS
 TEL: (773)491-3093
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 SEPT. 28/2012
 ACTION: DENIED
  
 1) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 .2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 .3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 .5. IF BUILDING IS FIRE SPRINKLERED OR NOT?
  
 2) 107.3.5.1.( 11) . INTERIOR REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 THE SECTION 804.4.1 WILL REQUIRE KNOWLEDGE OF IF THE
 BUILDING IS FIRE SPRINKLERED OR NOT SEE EXCEPTION FOR
 CPSC 16CFR, PART 1630.
 804.4.1 MINIMUM CRITICAL RADIANT FLUX.
 INTERIOR FLOOR FINISH AND FLOOR COVERING MATERIALS IN
 EXIT ENCLOSURES, EXIT PASSAGEWAYS AND CORRIDORS SHALL
 NOT BE LESS THAN CLASS I IN GROUPS I-1, I-2 AND I-3 AND
 NOT LESS THAN CLASS II IN GROUPS A, B, E, H, M, R-1,
 R-2 AND S. IN ALL AREAS, FLOOR COVERING MATERIALS SHALL
 COMPLY WITH THE DOCFF-1 "PILL TEST? (CPSC 16 CFR, PART
 1630).
  
 EXCEPTION: WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH
 AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1 OR 903.3.1.2, CLASS II MATERIALS ARE
 PERMITTED IN ANY AREA WHERE CLASS I MATERIALS ARE
 REQUIRED, AND MATERIALS COMPLYING WITH THE DOC FF-1
 "PILL TEST? (CPSC 16 CFR, PART 1630) ARE PERMITTED IN
 ANY AREA WHERE CLASS II MATERIALS ARE REQUIRED.
  
 3) THE PERMIT APPLICATION INDICATES UNDER THE HEADING
 OF DESSCSRIPTION OF WORK WALL SCONCE REPLACEMENT, THERE
 IS NO INFORMATION AS TO LOCATION OF WALL SCONCE,
 HEIGHTH OF SCONCE NOR HOW FAR FROM THE WALL THE SCONCE
 WILL PROTRUDE, PLEASE PROVIVE COMPLIANCE WITH 2010
 FLORIDA ACCESSIBILITY CODE SECTION 307.2 PROTRUSION
 LIMITS.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES (685 MM)
 AND NOT MORE THAN 80 INCHES (2030 MM) ABOVE THE FINISH
 FLOOR OR GROUND SHALL PROTRUDE 4 INCHES (100 MM)
 MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-01-31 Cont ID  
Sent By rlecky Date 2013-01-31 Time 13:53 Rev Time 0.00
Received By rlecky Date 2013-01-31 Time 13:15 Sent To  
Notes
2013-01-31 13:36:30CONTRACTOR INDICATED THAT THERE WILL BE NO NEW WIRING.
 NEW ENERGY INC. IS THE ELECTRICAL CONTRACTOR WHO WILL
 BE GETTING AN ELECTRIC PERMIT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-09-20 Cont ID  
Sent By rlecky Date 2012-09-20 Time 16:54 Rev Time 0.00
Received By rlecky Date 2012-09-20 Time 16:52 Sent To  
Notes
2012-09-20 16:58:02A SEPARATE ELECTRIC PERMIT IS REQUIRED TO INSTALL NEW
 FIXTURES. PROVIDE SCOPE OF WORK, TYPICAL PLAN LAYOUT
 AND FIXTURE SPECIFICATIONS.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2012-09-27 Cont ID  
Sent By wjolin Date 2012-09-27 Time 09:56 Rev Time 0.00
Received By wjolin Date 2012-09-27 Time 09:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-31 Cont ID  
Sent By rlecky Date 2013-01-31 Time 13:53 Rev Time 0.00
Received By rlecky Date 2013-01-22 Time 16:10 Sent To  
Notes
2013-01-22 16:38:34B--2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-09-28 Cont ID  
Sent By jwitmer Date 2012-09-28 Time 11:49 Rev Time 0.00
Received By jwitmer Date 2012-09-14 Time 11:28 Sent To  
Notes
2012-09-14 11:31:24B24

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-01-23 Cont ID  
Sent By lwagner Date 2013-01-23 Time 13:02 Rev Time 0.00
Received By lwagner Date 2013-01-23 Time 11:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2012-09-20 Cont ID  
Sent By lwagner Date 2012-09-20 Time 08:55 Rev Time 0.00
Received By lwagner Date 2012-09-17 Time 14:38 Sent To  
Notes
2012-09-20 08:59:40PLUMBING PERMIT REQUIRED TO CHANGE OUT OR INSTALL 15
 SINKS. PLEASE INCLUDE ROOM NUMBERS IN JOB DESCRIPTION.
 NO PLAN OR OTHER PLUMBING INFORMATION WAS INCLUDED WITH
 THE JOB SUBMITTALS.

Review Stop Z ZONING
Rev No 1 Status N Date 2012-09-27 Cont ID  
Sent By ajones Date 2012-09-27 Time 15:45 Rev Time 0.00
Received By ajones Date 2012-09-27 Time 15:45 Sent To  
Notes
***NONE***