| 2012-10-15 11:14:44 | RESIDENTIAL (R3) RENOVATION BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- TRELLIS PLAN ON SHEET A-1: |
| | A) SPECIFY FASTENERS FOR 1/4" ALUM. BUCKET SUPPORTING |
| | THE 4X12 BEAM. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | B) SPECIFY HOW ARE THE 3X8 TRELLIS JOISTS ATTACHED TO |
| | EXISTING HOUSE. . SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- SHEET A-2: |
| | A) CLARIFY WHY THE NEW CONCRETE BLOCK WALL DOESN'T HAVE |
| | ANY REBAR REINFORCEMENT AT THE CORNERS AND AT THE ENDS |
| | OF THE OPENINGS. SEC. R609.3. |
| | |
| | B) ROOF FRAMING PLAN: REVISE THE ROOF SHEATHING NAIL |
| | SPACING. NEED TO BE 4"O.C. IN ROOF ZONE #3. AND, GABLE |
| | END ROOF SHEATHING IS 5'-0" WIDE MINIMUM. SEC. |
| | R803.2.3.1 AND FIGURE R803.2.3.1. |
| | |
| | 3- PROVIDE FRAMING DETAILS FOR NEW ROUND WINDOW. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- REVISE ENERGY CALCULATIONS: |
| | A) THERE ARE TWO SEPARATE BUILDINGS. PROVIDE ENERGY |
| | CALCULATIONS FOR EACH. ONE FOR THE MAIN HOUSE AND ONE |
| | FOR THE GUEST HOUSE. REVISE CONDITIONED FLOOR AREA |
| | ACCORDINGLY. SEC. 107.2.1 CITY AMENDMENTS. |
| | B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC. |
| | 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | C) THIS IS AN EXISTING HOUSE NOT NEW CONSTRUCTION. |
| | REVISE ITEM #1. SEC. 107.2.1 CITY AMENDMENTS. |
| | D) COMPLETE ALL THE INFORMATION ON TOP OF FORM. |
| | INCLUDING THE BUILDER'S NAME. SEC. 107.2.1 CITY |
| | AMENDMENTS |
| | E) THERE ARE NO EXTERIOR WOOD DOORS. SEE PRODUCT |
| | APPROVAL AND REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 5- THERE ARE TWO DIFFERENT PRODUCT APPROVALS SUBMITTED |
| | FOR THE ROOF TILE. ONE IS FLORIDA PRODUCT APPROVAL AND |
| | THE OTHER IS A DADE COUNTY NOA. CLARIFY WHICH ONE IS |
| | GOING TO BE USED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 6- SPECIFY SIZE AND TYPE OF EXISTING BEDROOM WINDOWS. |
| | (EG: CASEMENT, ETC.). NEED TO VERIFY EGRESS |
| | REQUIREMENTS. SEC. 601.2 AND SEC. 604.1 OF 2010 |
| | FBC-EXISTING BUILDING. COORDINATE WITH ITEM #7(A) |
| | BELOW. |
| | |
| | 7- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) THE CASEMENT WINDOWS. SEE HISTORIC COMMENTS ON SOUTH |
| | ELEVATION ON SHEET SP-1. |
| | |
| | B) ROOF TILE ADHESIVE. IF USING ADHESIVE. SEE CONCRETE |
| | TILE PRODUCT APPROVAL FOR LISTED ADHESIVE. |
| | |
| | C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS. PROVIDE ONLY THE COVER PAGE AND PAGE SHOWING THE |
| | CONNECTOR. |
| | |
| | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS |
| | (INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY |
| | SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 9- CLEARLY SPECIFY HOW ARE THE CONCRETE ROOF TILE GOING |
| | TO BE INSTALLED. SCREWS OR ADHESIVE. IF USING SCREWS |
| | SPECIFY SIZE AND NUMBER. IF USING ADHESIVE, THEN |
| | PROVIDE THE PRODUCT APPROVAL. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |