Plan Review Details - Permit 12090272
Plan Review Stops For Permit 12090272
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-10-31 Cont ID  
Sent By rmcdouga Date 2012-10-31 Time 15:51 Rev Time 0.00
Received By rmcdouga Date 2012-10-31 Time 15:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-10-11 Cont ID  
Sent By rmcdouga Date 2012-10-11 Time 10:55 Rev Time 0.00
Received By rmcdouga Date 2012-10-11 Time 15:51 Sent To  
Notes
2012-10-11 11:16:01THE ROOFING PRODUCT APPROVAL THAT WAS SUBMITTED IS NOA
 11-1122.04 FOR GAF ASPHALT SHINGLES.
  
  
  
2012-10-11 11:13:55REVISIONS ARE REQUIRED FOR THE FOLLOWING PRODUCT
 APPROVALS.
  
 1) THE SINGLE HUNG WINDOW NOA 09-1008.05 HAS BEEN
 SUPERSEDED. SUBMIT CURRENT NOA 12-0223.42.
  
 2) THE FL# IS NOT LISTED ON THE PRODUCT APPROVAL
 SUBMITTED FOR THE JELD-WEN EXTERIOR DOOR WITH REPORT
 NO. 2035. SUBMIT THE PRODUCT APPROVAL WITH THE FL# FOR
 THIS DOOR.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-10-31 Cont ID  
Sent By rlecky Date 2012-10-31 Time 16:13 Rev Time 0.00
Received By rlecky Date 2012-10-31 Time 15:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-09-24 Cont ID  
Sent By rlecky Date 2012-09-24 Time 16:51 Rev Time 0.00
Received By rlecky Date 2012-09-24 Time 16:14 Sent To  
Notes
2012-09-24 16:52:2712090272
 633 52ND ST.
 ELECTRIC REPAIR
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 ADD RECEPTACLES SO THAT AT NO POINT ALONG THE FLOOR IN
 ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET
 AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC 210.52
  
 THE BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 BATH #2 REQUIRES A GROUND FAULT PROTECTED RECEPTACLE.
 NEC 210.52 (D)
  
 THE HALL WAY REQUIRES A RECEPTACLE. NEC 210.52 (H)
  
 PROVIDE AN ELECTRICAL RISER PLAN AND PANEL SCHEDULE.
 NEC 215.5
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-11-01 Cont ID  
Sent By rmcdouga Date 2012-11-01 Time 09:23 Rev Time 0.00
Received By rmcdouga Date 2012-10-25 Time 14:06 Sent To  
Notes
2012-10-25 14:06:39GAVE TO MCDOUGLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-10-11 Cont ID  
Sent By rmcdouga Date 2012-10-11 Time 11:17 Rev Time 0.00
Received By rmcdouga Date 2012-09-11 Time 16:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-10-11 Cont ID  
Sent By rmcdouga Date 2012-10-11 Time 09:55 Rev Time 0.00
Received By rmcdouga Date 2012-10-11 Time 09:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-10-31 Cont ID  
Sent By rmcdouga Date 2012-10-31 Time 15:51 Rev Time 0.00
Received By rmcdouga Date 2012-10-31 Time 15:51 Sent To  
Notes
2012-10-31 15:52:29CHANGE OUT FIXTURES IN THE SAME LOCATIONS.