Plan Review Details - Permit 12090235
Plan Review Stops For Permit 12090235
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-01-16 Cont ID  
Sent By shill Date 2013-01-16 Time 15:12 Rev Time 0.00
Received By shill Date 2013-01-16 Time 15:12 Sent To  
Notes
2013-01-16 15:13:19NOTE (DOES NOT NEED TO BE ADDRESSED) - ROOF NOA
 REVIEWED - 12-0410.07, JOHNS MANVILLE JM PVC SINGLE PLY
 ROOF SYSTEM OVER CONCRETE DECKS
 OK TO ISSUE ROOF SUB PERMIT
  
  
 ***PROVISOS***
  
 SAMANTHA HILL, 561-805-6724, [email protected]
  
  
 FOR THE ROOF EQUIPMENT STAND, FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED, FAC 9N-3. SUBMIT AS A
 REVISION PRIOR TO INSTALLATION.
  
 REGARDING THE ELEVATION CERTIFICATE, PLEASE REVISE AND
 SUBMIT PRIOR TO FIRST INSPECTION:
  
 ITEM A2, ADDRESS IS INCORRECT. PLEASE REVISE TO 3101
 OKEECHOBEE BOULEVARD OR PLEASE CONTACT ME TO DISCUSS
 THE ADDRESS DISCREPANCY. REVISE BOTH PAGES.
  
 ITEM A5. LATITUDE AND LONGITUDE IS TO INCLUDE SECONDS
 TO 1 DECIMAL PLACE OR BETTER PER INSTRUCTIONS.
  
 ITEM A5. WHEN THE LATITUDE AND LONGITUDE ARE PROVIDED
 BY A SURVEYOR, CHECK THE "YES" BOX IN SECTION D AND
 INDICATE THE METHOD USED TO DETERMINE THE LATITUDE
 AND LONGITUDE IN THE COMMENTS AREA OF SECTION D.
  
 ITEM C2E, PROVIDE ELEVATION OF MECHANICAL EQUIPMENT
 WHICH SERVES THE BUILDING AND DESCRIBE TYPE OF
 EQUIPMENT AND LOCATION IN COMMENTS. IF THE EQUIPMENT IS
 LOCATED ON THE ROOFTOP, EITHER PROVIDE THE ELEVATION OR
 NOTE LOCATION IN COMMENTS AREA OF SECTION D.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-01-14 Cont ID  
Sent By shill Date 2013-01-14 Time 17:55 Rev Time 0.00
Received By shill Date 2013-01-14 Time 17:55 Sent To  
Notes
2013-01-14 17:55:15***CORRECTIONS***
  
 SAMANTHA HILL, 561-805-6724, [email protected]
  
 1. SEE PREVIOUS LISTS. THE DOCUMENT WHICH WAS UPLOADED
 ON 10/24/12 NAMED LOADENERGYCALCULATIONS IS THE CIVIL
 COST ESTIMATE. PLEASE PROVIDE ENERGY CALCS PER FBC 2010
 ENERGY CONSERVATION 103.2.3. NOTE THAT THIS IS ALSO A
 STATUTORY REQUIREMENT.
  
 2. PERMIT WILL BE ISSUED WITH PROVISOS:
  
 FOR THE ROOF EQUIPMENT STAND, FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED, FAC 9N-3. SUBMIT AS A
 REVISION PRIOR TO INSTALLATION.
  
 REGARDING THE ELEVATION CERTIFICATE, PLEASE REVISE AND
 SUBMIT PRIOR TO FIRST INSPECTION:
  
 ITEM A2, ADDRESS IS INCORRECT. PLEASE REVISE TO 3101
 OKEECHOBEE BOULEVARD OR PLEASE CONTACT ME TO DISCUSS
 THE ADDRESS DISCREPANCY. REVISE BOTH PAGES.
  
 ITEM A5. LATITUDE AND LONGITUDE IS TO INCLUDE SECONDS
 TO 1 DECIMAL PLACE OR BETTER PER INSTRUCTIONS.
  
 ITEM A5. WHEN THE LATITUDE AND LONGITUDE ARE PROVIDED
 BY A SURVEYOR, CHECK THE "YES" BOX IN SECTION D AND
 INDICATE THE METHOD USED TO DETERMINE THE LATITUDE
 AND LONGITUDE IN THE COMMENTS AREA OF SECTION D.
  
 ITEM C2E, PROVIDE ELEVATION OF MECHANICAL EQUIPMENT
 WHICH SERVES THE BUILDING AND DESCRIBE TYPE OF
 EQUIPMENT AND LOCATION IN COMMENTS. IF THE EQUIPMENT IS
 LOCATED ON THE ROOFTOP, EITHER PROVIDE THE ELEVATION OR
 NOTE LOCATION IN COMMENTS AREA OF SECTION D.
  
 3. NOTE (DOES NOT NEED TO BE ADDRESSED) - ROOF NOA
 REVIEWED - 12-0410.07, JOHNS MANVILLE JM PVC SINGLE PLY
 ROOF SYSTEM OVER CONCRETE DECKS
 OK TO ISSUE ROOF SUB PERMIT
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-12-10 Cont ID  
Sent By shill Date 2012-12-10 Time 09:50 Rev Time 0.00
Received By shill Date 2012-12-10 Time 09:50 Sent To  
Notes
2012-12-10 11:26:55****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. THIS PARCEL IS LOCATED IN SPECIAL HAZARD FLOOD ZONE
 A8. WPB MUNICIPAL CODE 94 546(B), ALL NEW IMPROVEMENTS
 TO COMPLY WITH REQUIREMENTS FOR NEW CONSTRUCTION.
 FINISHED FLOOR SLAB TO BE AT A MINIMUM OF 16.5 FT. THE
 GRADING PLAN AND OTHER SHEETS SHOW A BUILDING ELEVATION
 OF 20.40 FT. PROPOSED CONSTRUCTION APPEARS TO COMPLY;
 PLEASE PROVIDE A SIGNED AND SEALED ELEVATION
 CERTIFICATE (CONSTRUCTION DRAWINGS). AN ADDITIONAL
 ELEVATION CERTIFICATE WILL BE REQUIRED PRIOR TO C.O.
 (FINAL CONSTRUCTION). THE ELEVATION CERTIFICATE CAN BE
 EITHER THE FEMA 2009 ELEVATION CERTIFICATE FORM (OMB
 NO. 1660-0008, EXPIRES MARCH 31, 2012) OR ON THE NEW
 FORM WHICH WILL BE AVAILABLE NEXT WEEK ON THE FEMA
 WEBSITE. THERE WILL BE A ONE YEAR PHASE IN PERIOD
 DURING WHICH THE NEW FORM WILL BE VOLUNTARY.
  
 2ND REVIEW, PLEASE PROVIDE ELEVATION CERTIFICATE
 (CONSTRUCTION DRAWINGS) AS REQUESTED. INFORMATION SUCH
 AS PROPOSED ELEVATION, MECHANICAL EQUIPMENT ELEVATION,
 AND OTHER ITEMS WILL BE REVIEWED.
  
 2. LS 1.0, ARRANGEMENTS OF EXITS, SEE FBC 1015.2.1,
 EXIT DOORS TO BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN ONE HALF OF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE SERVED
 (ONE THIRD DISTANCE IF BUILDING IS SPRINKLERED, SEE
 EXCEPTION).
  
 PLEASE REVISE NOTE (WHICH STATES 1/3 DIAGONAL) AND
 DIMENSIONS AS REQUIRED.
  
 3. OK.
  
 4. LS 1.0, TRAVEL DISTANCE OF 114 FT 4 IN SHOWN FROM
 ONE CORNER TO OPPOSITE EXIT. PLEASE ALSO SHOW COMMON
 PATH AS IT APPEARS TO EXCEED 75 FEET, FBC 1014.3.
  
 2ND REVIEW, PLEASE REVISE TO SHOW COMMON PATH AS
 DEFINED BY FBC 1002:
  
 "THAT PORTION OF EXIT ACCESS WHICH THE OCCUPANTS ARE
 REQUIRED TO TRAVERSE BEFORE TWO SEPARATE AND DISTINCT
 PATHS OF EGRESS TRAVEL TO TWO EXITS ARE AVAILABLE" (NOT
 VISIBLE AS STATED ON PLAN). PLEASE CONTACT ME IF YOU
 WISH TO DISCUSS.
  
 5. OK
  
 6. NOTE THE FOLLOWING REGARDING PRODUCT APPROVALS
 FAC9N-3, FBC 1609:
  
 AC STAND - IF MANUFACTURED ONSITE, PROVIDE A DETAIL. IF
 MANUFACTURED OFF SITE, FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED
  
 ALUMINUM IMPACT BI PARTING CAR DOOR SYSTEM - PROVIDE
 PRODUCT APPROVAL TO VERIFY DESIGN PRESSURES, IMPACT,
 AND METHOD OF INSTALLATION. THIS MAY HAVE BEEN PROVIDED
 TO YOU WITH THE RECORDS RESEARCH REQUEST INFORMATION.
  
 PAIR 4X8 IMPACT STOREFRONT DOOR SYSTEM (DOOR A) - OK
  
 WINDOW WALL SYSTEM WITH DOOR (DOOR B) - OK
  
 IMPACT SINGLE DOOR (DOOR C) - OK
  
 ROOF - ULTRAGARD PVC SR 50 - THE ASSEMBLY SELECTED IS
 FOR WOOD DECK, PLAN SHOWS DOUBLE TEES. ENGINEERING
 REQUIRED FOR ZONES 2 AND 3 IF ASSEMBLY DESIGN PRESSURE
 DOES NOT MEET MINIMUMS SPECIFIED BY ENGINEER.
  
 NEW EIFS WALL SYSTEM - OK
  
 BUTT GLAZED WINDOW WALL SYSTEM (PRODUCT APPROVAL OR
 TEST REPORT AS PER A 5.0) - OK
  
 ANY INFORMATION NOT SUBMITTED PRIOR TO PERMIT ISSUANCE
 WILL BE REQUIRED TO BE SUBMITTED AS A REVISION. DESIGN
 PRESSURES TO MEET REQUIREMENTS ON S 7.1.
  
 7. OK.
  
 8. PLEASE PROVIDE THE ENERGY CALCS. THE DOCUMENT WHICH
 WAS UPLOADED WHICH IS NAMED LOADENERGYCALCULATIONS.PDF
 IS THE SAME DOCUMENT AS THE CIVIL COST ESTIMATE. SEE
 FBC 2010 ENERGY 103.2.3.
  
 9. OK.
  
 10. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY
 REQUIRED. PLEASE CONTACT 561-233-5025 FOR MORE
 INFORMATION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-10-25 Cont ID  
Sent By shill Date 2012-10-25 Time 16:26 Rev Time 0.00
Received By shill Date 2012-10-25 Time 12:57 Sent To  
Notes
2012-10-25 16:27:44****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THIS PARCEL IS LOCATED IN SPECIAL HAZARD FLOOD ZONE
 A8. WPB MUNICIPAL CODE 94 546(B), ALL NEW IMPROVEMENTS
 TO COMPLY WITH REQUIREMENTS FOR NEW CONSTRUCTION.
 FINISHED FLOOR SLAB TO BE AT A MINIMUM OF 16.5 FT. THE
 GRADING PLAN AND OTHER SHEETS SHOW A BUILDING ELEVATION
 OF 20.40 FT. PROPOSED CONSTRUCTION APPEARS TO COMPLY;
 PLEASE PROVIDE A SIGNED AND SEALED ELEVATION
 CERTIFICATE (CONSTRUCTION DRAWINGS). AN ADDITIONAL
 ELEVATION CERTIFICATE WILL BE REQUIRED PRIOR TO C.O.
 (FINAL CONSTRUCTION). THE ELEVATION CERTIFICATE CAN BE
 EITHER THE FEMA 2009 ELEVATION CERTIFICATE FORM (OMB
 NO. 1660-0008, EXPIRES MARCH 31, 2012) OR ON THE NEW
 FORM WHICH WILL BE AVAILABLE NEXT WEEK ON THE FEMA
 WEBSITE. THERE WILL BE A ONE YEAR PHASE IN PERIOD
 DURING WHICH THE NEW FORM WILL BE VOLUNTARY.
  
 2. LS 1.0, ARRANGEMENTS OF EXITS, SEE FBC 1015.2.1,
 EXIT DOORS TO BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN ONE HALF OF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE SERVED
 (ONE THIRD DISTANCE IF BUILDING IS SPRINKLERED, SEE
 EXCEPTION). IT APPEARS THAT ITEMS 2 AND 4 WOULD BE
 RESOLVED BY INCLUDING THE ADDITIONAL DOUBLE DOOR AS AN
 EXIT, NOT CLEAR WHY THIS WAS EXCLUDED FROM LS PLAN AS
 AN EXIT.
  
 3. LS 1.0, THE HALLWAY TO THE BATHROOMS APPEARS TO BE A
 DEAD END, PLEASE PROVIDE DIMENSION ON THE LS PLAN.
  
 4. LS 1.0, TRAVEL DISTANCE OF 114 FT 4 IN SHOWN FROM
 ONE CORNER TO OPPOSITE EXIT. PLEASE ALSO SHOW COMMON
 PATH AS IT APPEARS TO EXCEED 75 FEET, FBC 1014.3.
  
 5. SECTION 2 A 4.0 AND OTHER DETAILS SHOW A WOOD TRUSS.
 PLEASE CLARIFY AND CONFIRM TYPE II B BUILDING TYPE OR
 REVISE ACCORDINGLY.
  
 6. NEED PRODUCT APPROVALS FOR:
  
 AC STAND
 ALUMINUM IMPACT BI PARTING CAR DOOR SYSTEM
 PAIR 4X8 IMPACT STOREFRONT DOOR SYSTEM (DOOR A)
 WINDOW WALL SYSTEM WITH DOOR (DOOR B)
 IMPACT SINGLE DOOR (DOOR C)
 ROOF - ULTRAGARD PVC SR 50
 NEW EIFS WALL SYSTEM
 BUTT GLAZED WINDOW WALL SYSTEM (PRODUCT APPROVAL OR
 TEST REPORT AS PER A 5.0)
  
 ANY INFORMATION NOT SUBMITTED PRIOR TO PERMIT ISSUANCE
 WILL BE REQUIRED TO BE SUBMITTED AS A REVISION. DESIGN
 PRESSURES TO MEET REQUIREMENTS ON S 7.1.
  
 7. INTERIOR WALL AND CEILING FINISH TO COMPLY WITH FBC
 803 (SEE ALSO 803.2). PROVIDE INFORMATION FOR THE WOOD
 GRAIN PLASTIC LAMINATE VENEER AS WELL AS METHOD OF
 ATTACHMENT, FBC 803.10.
  
 8. PLEASE PROVIDE THE ENERGY CALCS. THE DOCUMENT WHICH
 WAS UPLOADED WHICH IS NAMED LOADENERGYCALCULATIONS.PDF
 IS THE SAME DOCUMENT AS THE CIVIL COST ESTIMATE. SEE
 FBC 2010 ENERGY 103.2.3.
  
 9. OCCUPANCY CLASSIFICATION IS SHOWN AS BUSINESS;
 PLEASE INCLUDE THE PARTS AREA IN THE OCCUPANCY AS THIS
 BUILDING APPEARS TO BE MIXED USE. SEE FBC 508 REGARDING
 MIXED USE BUILDINGS, OCCUPANCY SEPARATIONS, AND
 NONSEPARATED OCCUPANCIES.
  
 10. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY
 REQUIRED. PLEASE CONTACT 561-233-5025 FOR MORE
 INFORMATION.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-10-25 Cont ID  
Sent By rlecky Date 2012-10-25 Time 15:00 Rev Time 0.00
Received By rlecky Date 2012-10-25 Time 14:40 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2012-10-31 Cont ID  
Sent By   Date 2012-10-31 Time   Rev Time 1.00
Received By   Date 2012-10-31 Time   Sent To Z
Notes
2012-10-31 16:14:13PASSED WITH PROVISO:
  
 PROVIDE CHANGES AS PER CITY OF WPB PLANNING COMMENTS.
  
 EVEN THOUGH THE SITE DRAINAGE ELEMENTS ARE VERTY SMALL
 SCALE THE PROJECT WILL BE REQUIRED TO COMPLY WITH
 POLLUTION PREVENTION AND PROVIDE BMP'S DURING
 CONSTRUCTION.
 FOR ASSISTANCE PLEASE REFER TO:
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-01-23 Cont ID  
Sent By wjolin Date 2013-01-17 Time 10:28 Rev Time 0.00
Received By wjolin Date 2013-01-17 Time 09:55 Sent To  
Notes
2013-01-17 10:23:443101 OKEECHOBEE BOULEVARD
 PERMIT #12090235
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 RESPONSE COMMENT:
 THE LIFE SAFETY CODE REQUIRES EACH OCCUPANCY CHAPTER TO
 BE REVIEWED INDEPENDENTLY WITH THE MOST RESTRICTIVE
 REQUIREMENTS APPLYING WHEN THE SPACE IS MIXED USE. IN
 THIS CASE, THE MOST RESTRICTIVE REQUIREMENT IS A HAZARD
 SEPARATION BETWEEN THE STORAGE AND BUSINESS AREAS.
  
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION
 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED,
 UNLESS SEPARATE SAFEGUARDS ARE APPROVED.
  
 ORIGINAL COMMENT:THERE DOES NOT APPEAR TO BE AN
 EXISTING FIRE BARRIER SEPARATING THE PARTS AREA
 (STORAGE OCCUPANCY) FROM THE BUSINESS OCCUPANCY.
 PROVIDE A FIRE BARRIER. ALL OPENINGS AND PENETRATIONS
 TO BE PROTECTED.
  
 ADDITIONAL INFORMATION: NFPA 101 SECTION 39.3.2 -
 PROTECTION FROM HAZARDS: "HAZARDOUS AREAS INCLUDING,
 BUT NOT LIMITED TO, AREAS USED FOR GENERAL
 STORAGE...SHALL BE PROTECTED IN ACCORDANCE WITH SECTION
 8.7."
  
 NFPA 101 SECTION 8.7.1.1 "PROTECTION FROM ANY AREA
 HAVING A DEGREE OF HAZARD GREATER THAN THAT NORMAL TO
 THE GENERAL OCCUPANCY OF THE BUILDING OR STRUCTURE
 SHALL BE PROVIDED BY ONE OF THE FOLLOWING MEANS:
 (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT
 WINDOWS THAT HAS A 1-HOUR FIRE RESISTANCE RATING IN
 ACCORDANCE WITH SECTION 8.3
 (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING
 SYSTEMS IN ACCORDANCE WITH SECTION 9.7
 (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD
 IS SEVERE OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11
 THROUGH 43"
  
 WESLEY JOLIN
 WPB FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805 - 6730
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-12-04 Cont ID  
Sent By wjolin Date 2012-12-04 Time 12:02 Rev Time 0.00
Received By wjolin Date 2012-12-04 Time 11:32 Sent To  
Notes
2012-12-04 11:40:523101 OKEECHOBEE BOULEVARD
 PERMIT #12090235
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ORIGINAL COMMENT:THERE DOES NOT APPEAR TO BE AN
 EXISTING FIRE BARRIER SEPARATING THE PARTS AREA
 (STORAGE OCCUPANCY) FROM THE BUSINESS OCCUPANCY.
 PROVIDE A FIRE BARRIER. ALL OPENINGS AND PENETRATIONS
 TO BE PROTECTED.
  
 ADDITIONAL INFORMATION: NFPA 101 SECTION 39.3.2 -
 PROTECTION FROM HAZARDS: "HAZARDOUS AREAS INCLUDING,
 BUT NOT LIMITED TO, AREAS USED FOR GENERAL
 STORAGE...SHALL BE PROTECTED IN ACCORDANCE WITH SECTION
 8.7."
  
 NFPA 101 SECTION 8.7.1.1 "PROTECTION FROM ANY AREA
 HAVING A DEGREE OF HAZARD GREATER THAN THAT NORMAL TO
 THE GENERAL OCCUPANCY OF THE BUILDING OR STRUCTURE
 SHALL BE PROVIDED BY ONE OF THE FOLLOWING MEANS:
 (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT
 WINDOWS THAT HAS A 1-HOUR FIRE RESISTANCE RATING IN
 ACCORDANCE WITH SECTION 8.3
 (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING
 SYSTEMS IN ACCORDANCE WITH SECTION 9.7
 (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD
 IS SEVERE OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11
 THROUGH 43"
  
 WESLEY JOLIN
 WPB FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805 - 6730
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-10-25 Cont ID  
Sent By wjolin Date 2012-10-25 Time 09:18 Rev Time 0.00
Received By wjolin Date 2012-10-25 Time 07:51 Sent To  
Notes
2012-10-25 09:18:053101 OKEECHOBEE BOULEVARD
 PERMIT #12090235
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THERE DOES NOT APPEAR TO BE AN EXISTING FIRE BARRIER
 SEPARATING THE PARTS AREA (STORAGE OCCUPANCY) FROM THE
 BUSINESS OCCUPANCY. PROVIDE A FIRE BARRIER. ALL
 OPENINGS AND PENETRATIONS TO BE PROTECTED.
  
 PROVIDE AN EXIT SIGN AT THE MAIN ENTRANCE, OTHERWISE
 THE COMMON PATH OF TRAVEL EXCEEDS 75 FEET.
  
 WESLEY JOLIN
 WPB FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805 - 6730
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-01-23 Cont ID  
Sent By wjolin Date 2013-01-23 Time 10:24 Rev Time 0.00
Received By wjolin Date 2013-01-09 Time 11:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-10 Cont ID  
Sent By shill Date 2012-12-10 Time 11:13 Rev Time 0.00
Received By shill Date 2012-11-29 Time 09:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2012-11-01 Time   Rev Time 0.00
Received By rregueir Date 2012-09-17 Time 15:15 Sent To  
Notes
2012-10-24 15:15:55DIGITAL

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-01-14 Cont ID  
Sent By shill Date 2013-01-14 Time 15:18 Rev Time 0.00
Received By shill Date 2013-01-14 Time 15:18 Sent To  
Notes
2013-01-14 15:15:18MU-2012-022883-0000
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-10-25 Cont ID  
Sent By shill Date 2012-10-25 Time 16:44 Rev Time 0.00
Received By shill Date 2012-10-25 Time 16:44 Sent To  
Notes
2012-10-25 16:45:27IMPACT FEES DUE (ENCLOSING AREA UNDER EXISTING ROOF)
 561-233-5025
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-10-24 Cont ID  
Sent By rregueir Date 2012-10-24 Time 15:24 Rev Time 0.00
Received By rregueir Date 2012-10-24 Time 15:22 Sent To  
Notes
2012-10-24 15:24:10PROVISO:
  
 SUBMIT PRODUCT APPROVAL FOR PRE-ENGINEERED A/C STAND
 PRIOR TO INSTALLATION AND INSPECTION PER FBC-B 106.1
 AND FAC RULE 9N-3.
  
 RJR

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-10-25 Cont ID  
Sent By lwagner Date 2012-10-25 Time 15:03 Rev Time 0.00
Received By lwagner Date 2012-10-25 Time 15:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-01-31 Cont ID  
Sent By rregueir Date 2013-01-31 Time 11:47 Rev Time 0.00
Received By rregueir Date 2013-01-31 Time 11:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-11-01 Cont ID  
Sent By avann Date 2012-11-01 Time 09:53 Rev Time 0.00
Received By ajones Date 2012-11-01 Time 09:53 Sent To  
Notes
***NONE***