| 2012-10-12 10:40:39 | 444 WEST RAILROAD AVENUE - 5TH FLOOR |
| | PERMIT #12090138 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL: ALL DEMOLITION AND CONSTRUCTION AREAS SHALL |
| | HAVE "NO SMOKING" SIGNS POSTED. |
| | |
| | GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE |
| | DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE |
| | EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR |
| | MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING |
| | SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH |
| | REQUESTS MUST BE SUBMITTED IN WRITING AND APPROVED BY |
| | THE OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH |
| | DIXIE HIGHWAY. |
| | |
| | GENERAL: PORTABLE FIRE EXTINGUISHERS SHALL HAVE A |
| | MINIMUM RATING OF 2A:10BC AND SHALL BE TAGGED BY A |
| | LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL DISTANCE TO |
| | EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | SHEET LS1.1: EVERY DOOR ASSEMBLY IN A STAIR ENCLOSURE |
| | SERVING MORE THAN FOUR STORIES NEEDS TO ALLOW THE |
| | GENERAL PUBLIC AND EMERGENCY RESPONDERS UNRESTRICTED |
| | RE-ENTRY BACK ONTO TWO LEVELS. ONE OF THE RE-ENTRY |
| | FLOORS IS REQUIRED TO BE THE TOP STORY OR NEXT- TO-TOP |
| | STORY AND SUCH STORY SHALL ALLOW ACCESS TO ANOTHER |
| | EXIT. DOOR ASSEMBLIES ALLOWING RE-ENTRY SHALL BE |
| | IDENTIFIED AS SUCH ON THE STAIR SIDE OF THE DOOR LEAF |
| | (NFPA 101 SECTION 7.2.1.5.7). |
| | |
| | SHEET A1.6: DOOR ASSEMBLIES ALLOWING RE-ENTRY SHALL BE |
| | IDENTIFIED AS SUCH ON THE STAIR SIDE OF THE DOOR LEAF |
| | (NFPA 101 SECTION 7.2.1.5.7). |
| | |
| | SHEET A1.6: PROVIDE A KNOX KEY SWITCH TO ALLOW GATE |
| | ACCESS TO EMERGENCY RESPONDERS. KEY SWITCH CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | SHEET E3.1.1: PENETRATIONS INTO, AND OPENINGS THROUGH, |
| | AN EXIT ENCLOSURE ASSEMBLY SHALL BE LIMITED TO THE |
| | FOLLOWING: DOOR ASSEMBLIES, ELECTRICAL CONDUIT SERVING |
| | THE EXIT ENCLOSURE, REQUIRED EXIT DOOR OPENINGS, |
| | DUCTWORK AND EQUIPMENT NECESSARY FOR INDEPENDENT STAIR |
| | PRESSURIZATION, WATER OR STEAM PIPING NECESSARY FOR THE |
| | HEATING OR COOLING OF THE EXIT ENCLOSURE, SPRINKLER |
| | PIPING, STANDPIPES AND PENETRATIONS FOR FIRE ALARM |
| | CIRCUITS, WHERE THE CIRCUITS ARE INSTALLED IN METAL |
| | CONDUIT AND THE PENETRATIONS ARE PROTECTED IN |
| | ACCORDANCE WITH 8.3.5. (SECTION 7.1.3.2 OF NFPA 101). |
| | SECURITY CAMERAS AND CARD READERS ARE NOT ESSENTIAL |
| | FUNCTIONS SERVING THE STAIRS. |
| | |
| | SHEET FA0.1: PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS |
| | SHALL INITIATE A GENERAL FIRE ALARM CONDITION. |
| | |
| | FIRE SPRINKLER: FOR ISSUANCE OF A GENERAL BUILDING |
| | PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING |
| | CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION |
| | DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE |
| | AUTOMATIC FIRE SPRINKLERS. NO SPRINKLER PLANS |
| | SUBMITTED. PER FLORIDA ADMINISTRATIVE CODE SECTION |
| | 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS |
| | SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER |
| | SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE |
| | TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR |
| | EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN |
| | DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT |
| | FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION |
| | SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |