| 2012-10-05 10:17:57 | 444 WEST RAILROAD AVENUE - SUITE #400 |
| | PERMIT #12090136 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL: ALL DEMOLITION AND CONSTRUCTION AREAS SHALL |
| | HAVE "NO SMOKING" SIGNS POSTED. |
| | |
| | GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE |
| | DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE |
| | EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR |
| | MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING |
| | SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH |
| | REQUESTS MUST BE SUBMITTED IN WRITING AND APPROVED BY |
| | THE OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH |
| | DIXIE HIGHWAY. |
| | |
| | GENERAL: PORTABLE FIRE EXTINGUISHERS SHALL HAVE A |
| | MINIMUM RATING OF 2A:10BC AND SHALL BE TAGGED BY A |
| | LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL DISTANCE TO |
| | EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | GENERAL: INDICATE THE MAXIMUM INCARCERATION TIME FOR |
| | INDIVIDUALS LOCATED IN THE HOLDING CELLS. |
| | |
| | SHEET LS1.1: A DEAD-END CORRIDOR OF 85 FEET IS CREATED |
| | WHEN MEASURED FROM THE DOOR OF TELEPHONE #415 TO THE |
| | END OF HALLWAY #412. |
| | |
| | SHEET LS1.1: A COMMON PATH OF TRAVEL OF 112 FEET IS |
| | CREATED WHEN MEASURED FROM MEN'S LOCKER #407 TO STAIR |
| | #A-2. |
| | |
| | SHEET LS1.1: WHERE EXIT ACCESS FROM ONE OCCUPANCY TYPE |
| | TRAVERSES ANOTHER OCCUPANCY TYPE, THE MULTIPLE |
| | OCCUPANCY SHALL BE TREATED AS A MIXED OCCUPANCY (NFPA |
| | 101 - 6.1.14.1.2). THIS FLOOR IS FUNCTIONING AS A |
| | NON-SEPARATED MIXED USE (BUSINESS, STORAGE AND |
| | ASSEMBLY) OCCUPANCY. PROVIDE AN OCCUPANT LOAD BREAKDOWN |
| | FOR EACH ROOM. THE MOST STRINGENT LIFE SAFETY |
| | REQUIREMENTS FOR EACH OCCUPANCY TYPE WILL APPLY. FOR |
| | EXAMPLE, ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD |
| | EXCEEDING 100 PERSONS SHALL HAVE PANIC OR FIRE EXIT |
| | HARDWARE ON EXIT AND EXIT ACCESS DOORS. |
| | |
| | SHEET LS1.1: STAIR DOOR A-1 APPEARS TO BE LOCKED FROM |
| | THE STAIR SIDE, WHICH IS ACCEPTABLE AS LONG AS STAIR |
| | RE-ENTRY IS PROVIDED FOR ALL STAIR DOORS ON THE 5TH |
| | FLOOR. STAIR SIGNAGE INDICATING WHICH FLOORS HAVE |
| | STAIRWELL RE-ENTRY TO BE PROVIDED. |
| | |
| | SHEET LS1.1: TRAINING ROOM #405 - DOORS SHALL SWING IN |
| | THE DIRECTION OF TRAVEL WHEN SERVING AN OCCUPANT LOAD |
| | OF 50 OR MORE PERSONS. |
| | |
| | SHEET E3.1.1: CARD READERS ARE NOT PERMITTED IN THE |
| | EXIT STAIR ENCLOSURE PER NFPA 101 SECTION 7.1.3.2.1(9). |
| | |
| | SHEET FA2.1.1: NO AUDIBLE FIRE ALARM NOTIFICATION |
| | APPLIANCES LOCATED TO THE EAST OF THE MAIN CORRIDOR. IT |
| | MAY BE DIFFICULT TO MEET THE MINIMUM AUDIBILITY |
| | REQUIREMENTS OF NFPA 72 WITH SO FEW APPLIANCES. |
| | |
| | SHEET FA2.1.2: PROVIDE SMOKE DETECTOR IN PROCESSING |
| | ROOM TO ALLOW EARLY FIRE DETECTION IN AREA OF HOLDING |
| | CELLS. PROVIDE A STROBE DEVICE IN THE SUPPLIES ROOM. |
| | |
| | FIRE SPRINKLER: FOR ISSUANCE OF A GENERAL BUILDING |
| | PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING |
| | CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION |
| | DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE |
| | AUTOMATIC FIRE SPRINKLERS. NO SPRINKLER PLANS |
| | SUBMITTED. PER FLORIDA ADMINISTRATIVE CODE SECTION |
| | 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS |
| | SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER |
| | SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE |
| | TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR |
| | EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN |
| | DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT |
| | FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION |
| | SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | (561) 805-6730 |
| | [email protected] |
| | |