Plan Review Details - Permit 12090076
Plan Review Stops For Permit 12090076
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-10-18 Cont ID  
Sent By jwitmer Date 2012-10-18 Time 08:23 Rev Time 0.00
Received By jwitmer Date 2012-10-17 Time 12:16 Sent To  
Notes
2012-10-18 07:50:14BUILDING PLAN REVIEW
 PERMIT: 12090076
 ADD: 931 VILLAGE BLVD # 901
 CONT: PM BUILDERS
 TEL: (954)916-2655
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) PROVIDE SHOP DRAWINGS BEFORE FRAMING INSPECTION .
 SHEET A1 & A2 REFRENECE MAGNETIC SHIELDING DESIGN BY
 UNIVERSAL SHIELDING, PLEASE PROVIDE COMPLIANCE WITH
 2010 FBC-B:
 435.13.5.1 SHIELDING.
 EACH X-RAY FACILITY SHALL HAVE PRIMARY AND SECONDARY
 PROTECTIVE BARRIERS AS NEEDED TO ASSURE THAT AN
 INDIVIDUAL WILL NOT RECEIVE A RADIATION DOSE IN EXCESS
 OF THE LIMITS SPECIFIED IN PART III OF CHAPTER 64E-5,
 FLORIDA ADMINISTRATIVE CODE.
 435.5.1.1
 STRUCTURAL SHIELDING IN WALLS AND OTHER VERTICAL
 BARRIERS REQUIRED FOR PERSONNEL PROTECTION SHALL EXTEND
 WITHOUT BREACH FROM THE FLOOR TO A HEIGHT OF AT LEAST 7
 FEET (2.1 M).
 435.5.1.2
 DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL
 HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT
 REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE
 INSTALLED.
  
 -------------------------------------------------------
 ----------------------------------------------
 PRODUCT APPROVALS SUBMITTED FOR EXTERIOR GLAZING;
 FL# 12522.1 YKK AP IMPACT "35H DG OUTSWING ENTRANCE
 DOOR +/- 90
 FL# 14218.3 YKK AP IMACT "YHS-50" DG AL FLUSH GLAZED
 STOREFRONT +/- 65.0
 ANCHOR SPACING +/- 57.6
 DOOR MULLION 120X 72 +/- 77.3
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-09-10 Cont ID  
Sent By jwitmer Date 2012-09-10 Time 14:10 Rev Time 0.00
Received By jwitmer Date 2012-09-06 Time 16:19 Sent To  
Notes
2012-09-10 14:10:20BUILDING PLAN REVIEW
 PERMIT: 12090076
 ADD: 931 VILLAGE BLVD # 901
 CONT: PM BUILDERS
 TEL: (954)916-2655
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 SEPT. 10/2011
 ACTION: DENIED
  
 1) SHEET A-1 NOTE "N" INDICATES THE DEMOLITION OF A
 PORTION OF WALL, BUT NO INFORMATION IS PROVIDED FOR THE
 REBUILDING OF BLOCK WALL, WILL NEW COLUMNS BE REQUIRED,
 CELLS GROUTED, HORIZONTAL 2010 FBC-B 2101.2.2 STRENGTH
 DESIGN.
  
 2) SHEET A-4 INDICATES NEW STOREFRONT WINDOWS, MULLIONS
 & DOORS. 1609.1.2 PROTECTION OF OPENINGS. GLAZED
 OPENINGS IN BUILDINGS LOCATED IN WIND-BORNE DEBRIS
 REGIONS SHALL BE PROTECTED FROM WIND-BORNE DEBRIS.
 GLAZED OPENING PROTECTION FOR WIND-BORNE DEBRIS SHALL
 MEET THE REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM
 E 1996, ANSI/DASMA 115 (FOR GARAGE DOORS AND ROLLING
 DOORS) OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED
 THEREIN.
 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF
 GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE
 TEST OF ASTM E 1996.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (E) SHUTTERS
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) SHEET A1 & A2 REFRENECE MAGNETIC SHIELDING DESIGN BY
 UNIVERSAL SHIELDING, PLEASE PROVIDE COMPLIANCE WITH
 2010 FBC-B:
 435.13.5.1 SHIELDING.
  
 EACH X-RAY FACILITY SHALL HAVE PRIMARY AND SECONDARY
 PROTECTIVE BARRIERS AS NEEDED TO ASSURE THAT AN
 INDIVIDUAL WILL NOT RECEIVE A RADIATION DOSE IN EXCESS
 OF THE LIMITS SPECIFIED IN PART III OF CHAPTER 64E-5,
 FLORIDA ADMINISTRATIVE CODE.
 435.5.1.1
  
 STRUCTURAL SHIELDING IN WALLS AND OTHER VERTICAL
 BARRIERS REQUIRED FOR PERSONNEL PROTECTION SHALL EXTEND
 WITHOUT BREACH FROM THE FLOOR TO A HEIGHT OF AT LEAST 7
 FEET (2.1 M).
 435.5.1.2
  
 DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL
 HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT
 REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE
 INSTALLED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-10-23 Cont ID  
Sent By rlecky Date 2012-10-23 Time 17:56 Rev Time 0.00
Received By rlecky Date 2012-10-23 Time 17:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-09-27 Cont ID  
Sent By rlecky Date 2012-09-27 Time 11:05 Rev Time 0.00
Received By rlecky Date 2012-09-26 Time 14:52 Sent To  
Notes
2012-09-27 11:37:2112090076
 931 VILLAGE BLVD. #702
 MEDICAL OFFICE
  
 PLEASE ADDRESS THE FOLLOWING PLAN REVIEW COMMENTS.
  
 VERIFY THE INDICATED FAULT CURRENT CAPACITY OF THE
 ELECTRIC SERVICE AND SWITCH GEAR IS ADEQUATE. NEC
 110.9, 110.10
  
 VERIFY THE EXISTING SERVICE GUTTER IS ADEQUATELY SIZED
 FOR THE NEW SERVICE CONDUCTORS. NEC 366.22, 366.56
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 EQUIPMENT. NEC 110.22, 110.16
  
 PROVIDE AN ADDITIONAL NOTE ON THE POWER PLAN WHICH
 INDICATES ALL PATIENT CARE AREAS / EXAM ROOMS REQUIRE A
 SPECIFIC LISTED WIRING METHOD THAT PROVIDES REDUNDANT
 GROUNDING AND INCLUDES AN INSULATED COPPER EQUIPMENT
 GROUND . NEC 517.13
  
 FEEDERS TO PANELS A AND P APPEAR TO BE INCORRECTLY
 SIZED. NEC 215.5
  
 MDP 2 REQUIRES A MAIN DISCONNECT OR MAIN BREAKER. NEC
 240.21
  
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
  
 VERIFY X-RAY ROOMS WILL HAVE REQUIRED SAFETY WARNING
 DEVICES, SIGNS, WARNING LIGHTS AND ELECTRICAL
 INTERLOCKS. FBC 435.9
  
 PROVIDE A LIGHTING DENSITY SUMMARY VERIFYING COMPLIANCE
 WITH THE 2010 FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC EC 505.5.3
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-10-22 Cont ID  
Sent By wjolin Date 2012-10-22 Time 13:43 Rev Time 0.00
Received By wjolin Date 2012-10-22 Time 13:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-09-25 Cont ID  
Sent By wjolin Date 2012-09-25 Time 13:44 Rev Time 0.00
Received By wjolin Date 2012-09-25 Time 13:11 Sent To  
Notes
2012-09-25 13:44:11901 VILLAGE BOULEVARD - SUITE #702
 PERMIT #12090076
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS PROVIDED ON THE PLANS (901 VILLAGE) DOES
 NOT MATCH THE ADDRESS PROVIDED ON THE PERMIT
 APPLICATION (931 VILLAGE).
  
 PROVIDE A SUITE NUMBER IN THE TITLEBLOCK INFORMATION.
  
 INDICATE THE PREVIOUS USE/OCCUPANCY OF THIS SUITE.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED AND SHALL HAVE "NO SMOKING" SIGNS
 POSTED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 ALL EXTERIOR DOORS NOT FUNCTIONING AS EXITS SHALL BE
 PERMANENTLY MARKED AND CLEARLY INDICATED AS, "NOT AN
 EXIT."
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-10-23 Cont ID  
Sent By rlecky Date 2012-10-23 Time 17:56 Rev Time 0.00
Received By rlecky Date 2012-10-15 Time 16:50 Sent To  
Notes
2012-10-15 16:50:46EXPEDITED
 C--6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-10-10 Cont ID  
Sent By hmoser Date 2012-10-10 Time 12:10 Rev Time 0.00
Received By hmoser Date 2012-09-05 Time 10:54 Sent To  
Notes
2012-09-06 10:55:57C06

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-10-18 Cont ID  
Sent By jwitmer Date 2012-10-18 Time 08:40 Rev Time 0.00
Received By jwitmer Date 2012-10-18 Time 08:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-10-10 Cont ID  
Sent By hmoser Date 2012-10-10 Time 12:07 Rev Time 0.00
Received By hmoser Date 2012-10-09 Time 15:05 Sent To  
Notes
2012-10-10 12:07:22PLANS DENIED PROVIDE FRESH AIR CALCULATIONS ON THE
 PLANS.
 PER TABLE 403.3 FBC (M) 2010
 REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS
 FOR FRESH AIR 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-09-11 Cont ID  
Sent By lwagner Date 2012-09-11 Time 13:39 Rev Time 0.00
Received By lwagner Date 2012-09-11 Time 12:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-09-17 Cont ID  
Sent By jroach Date 2012-09-17 Time 14:46 Rev Time 0.00
Received By jroach Date 2012-09-17 Time 14:10 Sent To  
Notes
***NONE***