| 2012-09-12 07:07:54 | BUILDING PLAN REVIEW |
| | PERMIT: 12090015 |
| | ADD: 412 CLEMATIS ST. |
| | CONT: ANDERSON-MOORE CORP |
| | TEL: (561)662-1819 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | SEPT. 12/ 2012 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1 GENERAL BUILDING CODE ANALYSIS INDICATES |
| | THIS TO BE A CHANGE OF OCCUPANCY, PLEASE UPDATE THE |
| | PERMIT APPLICATION TO INDICATE A CHANGE OF OCCUPANCY, |
| | 2010 EXISTING BLDG CODE : |
| | 901.3.1 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION. |
| | WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A |
| | NEW OCCUPANCY CLASSIFICATION, SECTION 912 SHALL APPLY. |
| | |
| | 901.4 CERTIFICATE OF OCCUPANCY REQUIRED. |
| | A CERTIFICATE OF OCCUPANCY SHALL BE ISSUED WHERE A |
| | CHANGE OF OCCUPANCY OCCURS THAT RESULTS IN A DIFFERENT |
| | OCCUPANCY CLASSIFICATION AS DETERMINED BY THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2) SHEET A1 THE CURRENT CONFIGURATION OF THE EXISTING |
| | RESTROOMS DOES NOT MEET THE REQUIREMENTS OF THE 2010 |
| | FLORIDA ACCESSIBILITY CODE WITH THE REQUIRED 60 INCHES |
| | WHERE NO OTHER FIXTURES (LAVATORY) OR OBSTRUCTIONS |
| | SHALL BE LOCATED WITHIN THE WATER CLOSET CLERANCES. SEE |
| | FIGURE 604.8.1.6. |
| | PLEASE REVIEW SECTION S 2010 FL ACCESSIBLITY SECTIONS |
| | 202.4.1 DISPROPORTIONATE COST AND 202.4.2 ACCESSIBLE |
| | FEATURES IN THE EVENT OF DISPROPORTIONALITY. |
| | AN ADDITIONAL $19,000.00 WILL NEED TO BE SPENT IN |
| | UPGRADING TO MEET THE 2010 ACCESSIBILITY CODE. |
| | |
| | 3) PLEASE UPDATE CODE SECTIONS LISTED UNDER THE HEADING |
| | LIFE SAFETY LEGEND WITH 2007 FBC REFERENCES. SEE 2010 |
| | FBC-B 1018.2. CORRIDOR WIDTH. |
| | |
| | 4) SHEET A-3 FRONT COUNTER DETAIL WITH SOFFIT ABOVE, |
| | THE DETAIL DOE NOT PROVIDE ANCHORING OF THE SOFFIT |
| | FRAMING TO FRAMING MEMBERS ABOVE, TYPE OF ANCHOR, SIZE |
| | NOR SPACING OF ANCHORS, 2010 FBC-B TABLE 2506.2 STEEL |
| | STUDS NON-LOAD BEARING. |
| | |
| | 5) POINT OF CONSIDERATION/ UNDER SEPERATE PERMIT: 2010 |
| | FBC-B: |
| | |
| | 904.2.1 COMMERCIAL HOOD AND DUCT SYSTEMS. [F] |
| | EACH REQUIRED COMMERCIAL KITCHEN EXHAUST HOOD AND DUCT |
| | SYSTEM REQUIRED BY THE FLORIDA FIRE PREVENTION CODE OR |
| | CHAPTER 5 OF THE FLORIDA BUILDING CODE, MECHANICAL TO |
| | HAVE A TYPE I HOOD SHALL BE PROTECTED WITH AN APPROVED |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEM INSTALLED IN |
| | ACCORDANCE WITH THIS CODE. |
| | |
| | 904.3.2 ACTUATION. [F] |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS SHALL BE |
| | AUTOMATICALLY ACTUATED AND PROVIDED WITH A MANUAL MEANS |
| | OF ACTUATION IN ACCORDANCE WITH SECTION 904.11.1. |
| | |
| | 904.11.1 MANUAL SYSTEM OPERATION. [F] |
| | A MANUAL ACTUATION DEVICE SHALL BE LOCATED AT OR NEAR A |
| | MEANS OF EGRESS FROM THE COOKING AREA A MINIMUM OF 10 |
| | FEET (3048 MM) AND A MAXIMUM OF 20 FEET (6096 MM) FROM |
| | THE KITCHEN EXHAUST SYSTEM. THE MANUAL ACTUATION DEVICE |
| | SHALL BE INSTALLED NOT MORE THAN 48 INCHES (1200 MM) OR |
| | LESS THAN 42 INCHES (1067 MM) ABOVE THE FLOOR AND SHALL |
| | CLEARLY IDENTIFY THE HAZARD PROTECTED. THE MANUAL |
| | ACTUATION SHALL REQUIRE A MAXIMUM FORCE OF 40 POUNDS |
| | (178 N) AND A MAXIMUM MOVEMENT OF 14 INCHES (356 MM) TO |
| | ACTUATE THE FIRE SUPPRESSION SYSTEM. |
| | |
| | 6) SHEET M-1 A/C UNIT RACK DETAIL: |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(F)PRE-ENGINEERED A/C STANDS |
| | |
| | 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 8) SHEET M-2 UP-BLAST/ EXHAUST FAN DETAIL: WILL HAVE TO |
| | PROVIDE COMPLIANCE WITH SECTION 2010 FBC-B 1609.8 |
| | ROOFTOP EQUIPMENT, PROVIDE DOCUMENTATION. |
| | |
| | 9) SHEET M-2 ROOF CURB DETAIL DOES NOT PROVIDE |
| | ANCHORAGE TO THE ROOF FRAMING NOR DOES THE PLANS |
| | INDICATE THE TYPE OF ROOF FRAMING AND DECKING THE CURB |
| | WILL BE ATTACHED TOO. 2010 FBC-B 1609.8 ROOFTOP |
| | EQUIPMENT. |
| | |
| | 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |