Plan Review Details - Permit 12080942
Plan Review Stops For Permit 12080942
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-09-14 Cont ID  
Sent By rmcdouga Date 2012-09-14 Time 08:17 Rev Time 0.00
Received By rmcdouga Date 2012-09-14 Time 08:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-09-14 Cont ID  
Sent By rmcdouga Date 2012-09-14 Time 08:14 Rev Time 0.00
Received By rmcdouga Date 2012-09-14 Time 08:14 Sent To  
Notes
2012-09-14 08:17:13ELECTRIC PROVISO
  
 THE POOL IS REQUIRED TO COMPLY WITH 2008 NEC 680.26 (B)
 (2) FOR EQUIPOTENTIAL BONDING.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-09-14 Cont ID  
Sent By rmcdouga Date 2012-09-14 Time 10:09 Rev Time 0.00
Received By rmcdouga Date 2012-09-11 Time 16:12 Sent To  
Notes
2012-09-11 16:12:20TO RM DESK
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-09-14 Cont ID  
Sent By rmcdouga Date 2012-09-14 Time 08:42 Rev Time 0.00
Received By rmcdouga Date 2012-09-14 Time 08:42 Sent To  
Notes
2012-09-14 09:56:512010 FBCR
 PLUMBING PROVISO
  
 1) COMPLY FBCR4101.6.6 ENTRAPMENT PROTECTION FOR
 SUCTION OUTLETS IN COMPLIANCE WITH ANSI/APSP-7 2006.
 SECTION 4.5 WHICH REQUIRES LISTED SUCTION OUTLETS
 COMPLYING WITH ASME/ANSI A112.19.8 AND INCLUDE A
 PERMANENTLY MARKED FLOW RATING TESTED TO PREVENT HAIR
 ENTRAPMENT.
  
 2) COMPLY FBCR4101.6.6 ENTRAPMENT PROTECTION FOR
 SUCTION OUTLETS WHICH SHALL BE INSTALLED IN ACCORDANCE
 WITH ANSI/APSP-7 2006. SECTION 5.3 FOR DUAL OUTLETS AND
 5.5 FOR SINGLE UNBLOCKABLE SUCTION OUTLETS.
  
 3) COMPLY WITH FBCR4101.6.3 AND ANSI/APSP-7 SECTION 4.4
 THAT REQUIRES THE WATER VELOCITY IN FIELD FABRICATED TO
 BE BASED ON THE MAXIMUM SYSTEM FLOW RATE. THE MAXIMUM
 WATER VELOCITY IN BRANCH SUCTION PIPING IS 6 FEET PER
 SECOND AND 8 FT/SEC IN ALL OTHER SUCTION PIPING.
  
 4) COMPLY WITH 2010 FBC ENERGY CONSERVATION SECTION
 403.9.4 (2) WHICH REQUIRES POOL PUMP MOTORS WITH A
 TOTAL HORSE POWER (HP) OF 1 HP OR MORE TO HAVE THE
 CAPABILITY OF OPERATING AT TWO OR MORE SPEEDS AND (3)
 WHICH REQUIRES THE DEFAULT CIRCULATION SPEED TO BE THE
 RESIDENTIAL CIRCULATION SPEED, WITH A HIGHER SPEED
 OVERRIDE CAPABILITY FOR A TEMPORARY PERIOD NOT TO
 EXCEED ONE NORMAL CYCLE OR 24 HOURS, WHICHEVER IS LESS.

Review Stop Z ZONING
Rev No 1 Status P Date 2012-09-14 Cont ID  
Sent By rmcdouga Date 2012-09-14 Time 07:31 Rev Time 0.00
Received By rmcdouga Date 2012-09-14 Time 07:31 Sent To  
Notes
2012-09-14 08:14:38THIS IS A RE-ISSUE PERMIT. ZONING WAS APPROVED
 PREVIOUSLY UNDER PERMIT # 01020212.