Plan Review Details - Permit 12080942
| Plan Review Stops For Permit 12080942 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2012-09-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-09-14 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-09-14 |
Time |
08:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-09-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-09-14 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-09-14 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2012-09-14 08:17:13 | ELECTRIC PROVISO | | | | | | THE POOL IS REQUIRED TO COMPLY WITH 2008 NEC 680.26 (B) | | | (2) FOR EQUIPOTENTIAL BONDING. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-09-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-09-14 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-09-11 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2012-09-11 16:12:20 | TO RM DESK | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2012-09-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-09-14 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-09-14 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2012-09-14 09:56:51 | 2010 FBCR | | | PLUMBING PROVISO | | | | | | 1) COMPLY FBCR4101.6.6 ENTRAPMENT PROTECTION FOR | | | SUCTION OUTLETS IN COMPLIANCE WITH ANSI/APSP-7 2006. | | | SECTION 4.5 WHICH REQUIRES LISTED SUCTION OUTLETS | | | COMPLYING WITH ASME/ANSI A112.19.8 AND INCLUDE A | | | PERMANENTLY MARKED FLOW RATING TESTED TO PREVENT HAIR | | | ENTRAPMENT. | | | | | | 2) COMPLY FBCR4101.6.6 ENTRAPMENT PROTECTION FOR | | | SUCTION OUTLETS WHICH SHALL BE INSTALLED IN ACCORDANCE | | | WITH ANSI/APSP-7 2006. SECTION 5.3 FOR DUAL OUTLETS AND | | | 5.5 FOR SINGLE UNBLOCKABLE SUCTION OUTLETS. | | | | | | 3) COMPLY WITH FBCR4101.6.3 AND ANSI/APSP-7 SECTION 4.4 | | | THAT REQUIRES THE WATER VELOCITY IN FIELD FABRICATED TO | | | BE BASED ON THE MAXIMUM SYSTEM FLOW RATE. THE MAXIMUM | | | WATER VELOCITY IN BRANCH SUCTION PIPING IS 6 FEET PER | | | SECOND AND 8 FT/SEC IN ALL OTHER SUCTION PIPING. | | | | | | 4) COMPLY WITH 2010 FBC ENERGY CONSERVATION SECTION | | | 403.9.4 (2) WHICH REQUIRES POOL PUMP MOTORS WITH A | | | TOTAL HORSE POWER (HP) OF 1 HP OR MORE TO HAVE THE | | | CAPABILITY OF OPERATING AT TWO OR MORE SPEEDS AND (3) | | | WHICH REQUIRES THE DEFAULT CIRCULATION SPEED TO BE THE | | | RESIDENTIAL CIRCULATION SPEED, WITH A HIGHER SPEED | | | OVERRIDE CAPABILITY FOR A TEMPORARY PERIOD NOT TO | | | EXCEED ONE NORMAL CYCLE OR 24 HOURS, WHICHEVER IS LESS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2012-09-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-09-14 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-09-14 |
Time |
07:31 |
Sent To |
|
|
| Notes |
| 2012-09-14 08:14:38 | THIS IS A RE-ISSUE PERMIT. ZONING WAS APPROVED | | | PREVIOUSLY UNDER PERMIT # 01020212. |
|
|
|