Plan Review Details - Permit 12080871
Plan Review Stops For Permit 12080871
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-09-04 Cont ID  
Sent By rlecky Date 2012-09-04 Time 09:10 Rev Time 0.00
Received By rlecky Date 2012-09-04 Time 08:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2012-08-28 Cont ID  
Sent By rlecky Date 2012-08-28 Time 14:22 Rev Time 0.00
Received By rlecky Date 2012-08-28 Time 14:10 Sent To  
Notes
2012-08-28 14:30:51REQUESTED ADDITIONAL INFORMATION ON THE SERVICE DESIGN
 FROM THE CONTRACTOR.
  
 PROVIDE FAULT CURRENT CAPABILITES FOR THE ELECTRIC
 SERVICE. NWEC 110.9
 SHOW ALL WIRE AND CONDUIT SIZED. NEC 215.5
  
 ROBERT LECKY
 ELECTRIC PLANS REVIEW
 561-805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-08-27 Cont ID  
Sent By rlecky Date 2012-08-27 Time 12:20 Rev Time 0.00
Received By rlecky Date 2012-08-27 Time 11:47 Sent To  
Notes
2012-08-27 12:25:49NEC 215.5 MISSING ELECTRICAL RISER AND POWER PLAN. RL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-09-04 Cont ID  
Sent By rlecky Date 2012-09-04 Time 09:10 Rev Time 0.00
Received By rlecky Date 2012-09-04 Time 08:56 Sent To  
Notes
2012-09-04 08:57:08NEW INFORMATION SUBMITTED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-08-28 Cont ID  
Sent By rlecky Date 2012-08-28 Time 14:30 Rev Time 0.00
Received By rlecky Date 2012-08-28 Time 12:42 Sent To  
Notes
2012-08-28 12:43:09INCOMING SENT TO ELECTRIC BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-27 Cont ID  
Sent By rlecky Date 2012-08-27 Time 12:20 Rev Time 0.00
Received By rlecky Date 2012-08-24 Time 08:44 Sent To  
Notes
2012-08-27 08:44:39SENT TO ELECTRIC BOX