Plan Review Details - Permit 12080803
Plan Review Stops For Permit 12080803
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-11-02 Cont ID  
Sent By lmartine Date 2012-11-02 Time 16:34 Rev Time 0.00
Received By lmartine Date 2012-11-02 Time 16:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-10-19 Cont ID  
Sent By jwitmer Date 2012-10-19 Time 14:19 Rev Time 0.00
Received By jwitmer Date 2012-10-19 Time 14:18 Sent To  
Notes
2012-10-19 14:25:37BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) CONTRACTOR DID NOT SUBMIT PRODUCT APPROVAL FOR NEW
 STOREFRONT ENTRY GLAZING OR DOOR. 2010 FBC-B
 1609.6.4.4.1 COMPONENTS &CLADDING.
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS,

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-09-05 Cont ID  
Sent By jwitmer Date 2012-09-05 Time 16:41 Rev Time 0.00
Received By jwitmer Date 2012-09-05 Time 16:39 Sent To  
Notes
2012-09-05 16:46:54BUILDING PLAN REVIEW
 PERMIT: 12080803
 ADD: 120 S OLIVE AVE SUITE # 105
 CONT: ANDERSON-MOORE CONSTRUCTION
 TEL: (561)662-1819
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET SP1 PROJECT DATA INDICATES THIS TO BE A TYPE
 IIIB BUILDING, 2010 FBC-B TABLE 503 FOR A A2
 OCCUPANCYWITH BUSSINESS OCCUPANCIES ABOVE ONLY ALLOWS
 FOR A UILDING HEIGHT OF 3 STORIES WITH A STORY INCREASE
 FOR A FULLY SPRINKLERED BUILDING. THIS BUILDING IS A
 MINIMUM OF 7 STORIES TALL, PLEASE CORRECT TTHE MINIMUM
 BUILDING TYPE.
  
 2) THIS BUILDING IS ALSO A CONDOMINIUM ASSOCATION,
 SHEET SP-1 INDICATES THERE ARE TWO TENANT SPACES THAT
 ARE BEING COMBINED INTO ONE TENANTCY, A UNITY OF TITLE
 WILL BE REQUIRED. UNITY OF TITLE. THE PROPOSED BUILDING
 STRUCTURE TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE
 LOTS WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF
 TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
  
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 3) SHEET A1.0 WITH AN OCCUPANT LOAD OF 50 OCCUPANTS OR
 MORE THE EXISTING FRONT DOOR SWINGS THE WRONG WAY, 2010
 FBC-B 1008.1.2. PLEASE PROVIDE ON THIS PLAN THE
 LOCATION OF THE PROPERTY LINE, OUTSWING DOORS CAN'T
 SWING OUT OVER THE PROPERTY LINE. 2010 FBC-B 3202.2.
  
 4) SHEET A1.0 DOOR SCHEDULE INDICATES THE FRONT DOOR
 HAS EXISING FIRE HARDWARE PLEASE PROVIDE COMPLIANCE
 WITH SECTION 2010 FBC-B 1008.1.10.
  
 5) SHEET A1.0 THE BACK EXIT INTO A ENCLOSED EXIT
 PASSAGE WAY THAT OPENS TO AN EGRESS COURT THAT LEADS TO
 A PUBLIC ALLEY, IS THIS AREA USED FOR STORAGE AND OR
 USE OF ICE MAKERS OR OTHER EQUIPMENT? 1027.1(1.1)-(1.3)
 , 1027.6 ACCESS TO A PUBLIC WAY. THE EXIT DISCHARGE
 SHALL PROVIDE A DIRECT AND UNOBSTRUCTED ACCESS TO A
 PUBLIC WAY. IS THERE A CLEAR PATH WITH NO OBSTRUCTIONS,
 GATES TO THE PUBLIC ALLEY?
  
 6) SHEET A1.0 ACCESSIBLE RESTROOM DETAIL INDICATES THE
 DIMENSIONS TO THE CENTERLINE, PLEASE NOTE IN THE NEW
 2010 ACCESSIBLITY CODE THESE MEASUREMENTS ARE TAKEN TO
 THE TOP OF THE GRAB BARS 2010 FBC-ACCESSIBILITY CODE
 609.3.
  
 7) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 803.1.1
 INTERIOR WALL AND CEILING FINISH MATERIALS.
  
 8) SHEET A1.0 PLAN NOTE # 6 INDICATES THE PROJECT IS
 LOCATED WITHIN THE HVHZ, ONLY BROWARD & DADE COUNTIES
 ARE CONSIDERED TO BE THE HIGH VELOCITY HURRICANE ZONE.
 WITH COMMENT NUMBER (3) PRODUCT APPROVALS WILL BE
 REQUIRED FOR THE REPLACEMENT OF THE FRONT ENTRY DOOR(
 1715.5.3) , IF GLAZED THEN PROTECTION OF GLAZED
 OPENINGS IN ACCORDANCE WITH 1609.1.2.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 9) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) SHEET A2.0 DOES NOT INDICATE EXISTING FIRE
 SPRINKLERS LOCATED WITHIN THE EXIT PASSAGEWAY, PLEASE
 REVIEW SECTION 2010 FBC-B 1027.1.EXCEPTION 1.3.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-11-01 Cont ID  
Sent By rlecky Date 2012-11-01 Time 15:11 Rev Time 0.00
Received By rlecky Date 2012-11-01 Time 15:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-09-04 Cont ID  
Sent By rlecky Date 2012-09-04 Time 15:00 Rev Time 0.00
Received By rlecky Date 2012-09-04 Time 14:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-10-22 Cont ID  
Sent By wjolin Date 2012-10-22 Time 14:22 Rev Time 0.00
Received By wjolin Date 2012-10-22 Time 14:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-09-01 Cont ID  
Sent By wjolin Date 2012-09-01 Time 17:10 Rev Time 0.00
Received By wjolin Date 2012-09-01 Time 16:44 Sent To  
Notes
2012-09-01 17:10:22105 SOUTH OLIVE AVENUE - SUITE #105
 PERMIT #12080803
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANT LOADS,
 FIRE RATED WALLS, EXIT SIGNS, EMERGENCY LIGHTING,
 TRAVEL DISTANCES, COMMON PATH OF TRAVEL, PORTABLE FIRE
 EXTINGUISHERS, ETC.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE THE INTERIOR FINISH CLASSIFICATION FOR
 MATERIALS TO BE USED ON WALLS AND CEILINGS.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 DOOR IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-11-02 Cont ID  
Sent By lmartine Date 2012-11-02 Time 16:34 Rev Time 0.00
Received By lmartine Date 2012-10-25 Time 16:38 Sent To  
Notes
2012-10-25 16:38:38SUBMITTED BUILDING REVIEW CHANGES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-11-02 Cont ID  
Sent By lmartine Date 2012-10-25 Time 16:34 Rev Time 0.00
Received By lmartine Date 2012-10-16 Time 09:30 Sent To  
Notes
2012-10-16 09:31:09SENT TO B14 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-09-13 Cont ID  
Sent By hmoser Date 2012-09-13 Time 10:44 Rev Time 0.00
Received By hmoser Date 2012-08-23 Time 18:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-11-01 Cont ID  
Sent By hmoser Date 2012-11-01 Time 13:04 Rev Time 0.00
Received By hmoser Date 2012-11-01 Time 12:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-09-13 Cont ID  
Sent By hmoser Date 2012-09-13 Time 10:43 Rev Time 0.00
Received By hmoser Date 2012-09-13 Time 09:41 Sent To  
Notes
2012-09-13 10:43:49PLANS DENIED
 1) ENERGY CALCULATIONS AND PLANS DO NOT MATCH.
 PLANS SHOW A/C # 1 AND 3 56200 BTU AND A/C # 2 1950
 BTU.
 ENERGY CALCULATION SHOW A/C 1,2 56000 AND A/C 3 1950
 BTU.
 2) DETAIL #2 NO PAGE M2.01 PROVIDE LAG BOLT SIZE FOR
 CONDENSER STAND.
 3) REFER TO SECTION 604.4.1 SUPERVISION 2010 FBC (M)
 4) PROVIDE PRODUCT APPROVAL FOR OUTDOOR LOUVER
 PER SECTION 107.3.4 GENERAL 2010 FBC
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-10-22 Cont ID  
Sent By lwagner Date 2012-10-22 Time 12:40 Rev Time 0.00
Received By lwagner Date 2012-10-22 Time 12:40 Sent To  
Notes
2012-10-22 12:41:57FUEL GAS IS NOT INCLUDED IN THIS REVIEW. SEPARATE
 APPLICATION, PLAN, REVIEW, FEES, AND PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-08-28 Cont ID  
Sent By lwagner Date 2012-08-28 Time 14:02 Rev Time 0.00
Received By lwagner Date 2012-08-28 Time 13:17 Sent To  
Notes
2012-08-28 14:04:12FUEL GAS IS NOT PART OF THIS REVIEW.
 SEPARATE GAS APPLICATION, DRAWING, PERMIT, AND FEE
 REQUIRED

Review Stop Z ZONING
Rev No 1 Status P Date 2012-09-11 Cont ID  
Sent By aaponte Date 2012-09-11 Time 10:43 Rev Time 0.00
Received By aaponte Date 2012-09-11 Time 10:40 Sent To  
Notes
***NONE***