| 2012-09-05 16:46:54 | BUILDING PLAN REVIEW |
| | PERMIT: 12080803 |
| | ADD: 120 S OLIVE AVE SUITE # 105 |
| | CONT: ANDERSON-MOORE CONSTRUCTION |
| | TEL: (561)662-1819 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET SP1 PROJECT DATA INDICATES THIS TO BE A TYPE |
| | IIIB BUILDING, 2010 FBC-B TABLE 503 FOR A A2 |
| | OCCUPANCYWITH BUSSINESS OCCUPANCIES ABOVE ONLY ALLOWS |
| | FOR A UILDING HEIGHT OF 3 STORIES WITH A STORY INCREASE |
| | FOR A FULLY SPRINKLERED BUILDING. THIS BUILDING IS A |
| | MINIMUM OF 7 STORIES TALL, PLEASE CORRECT TTHE MINIMUM |
| | BUILDING TYPE. |
| | |
| | 2) THIS BUILDING IS ALSO A CONDOMINIUM ASSOCATION, |
| | SHEET SP-1 INDICATES THERE ARE TWO TENANT SPACES THAT |
| | ARE BEING COMBINED INTO ONE TENANTCY, A UNITY OF TITLE |
| | WILL BE REQUIRED. UNITY OF TITLE. THE PROPOSED BUILDING |
| | STRUCTURE TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE |
| | LOTS WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF |
| | TITLE' SHALL BE |
| | RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE |
| | RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE |
| | 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT |
| | APPLICABLE. |
| | SEE WEBSITE FOR APPLICATION: |
| | HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| | "APPLICATION FOR UNITY OF TITLE" |
| | |
| | HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| | -38-UNITYOFTITLE3.PDF |
| | |
| | VINCENT J NOEL |
| | SURVEYOR/REAL ESTATE SUPERVISOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 494-1040 EXT: 1096 |
| | FAX: 494-1116 |
| | E-MAIL: [email protected] |
| | |
| | ********************************************* |
| | |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | 3) SHEET A1.0 WITH AN OCCUPANT LOAD OF 50 OCCUPANTS OR |
| | MORE THE EXISTING FRONT DOOR SWINGS THE WRONG WAY, 2010 |
| | FBC-B 1008.1.2. PLEASE PROVIDE ON THIS PLAN THE |
| | LOCATION OF THE PROPERTY LINE, OUTSWING DOORS CAN'T |
| | SWING OUT OVER THE PROPERTY LINE. 2010 FBC-B 3202.2. |
| | |
| | 4) SHEET A1.0 DOOR SCHEDULE INDICATES THE FRONT DOOR |
| | HAS EXISING FIRE HARDWARE PLEASE PROVIDE COMPLIANCE |
| | WITH SECTION 2010 FBC-B 1008.1.10. |
| | |
| | 5) SHEET A1.0 THE BACK EXIT INTO A ENCLOSED EXIT |
| | PASSAGE WAY THAT OPENS TO AN EGRESS COURT THAT LEADS TO |
| | A PUBLIC ALLEY, IS THIS AREA USED FOR STORAGE AND OR |
| | USE OF ICE MAKERS OR OTHER EQUIPMENT? 1027.1(1.1)-(1.3) |
| | , 1027.6 ACCESS TO A PUBLIC WAY. THE EXIT DISCHARGE |
| | SHALL PROVIDE A DIRECT AND UNOBSTRUCTED ACCESS TO A |
| | PUBLIC WAY. IS THERE A CLEAR PATH WITH NO OBSTRUCTIONS, |
| | GATES TO THE PUBLIC ALLEY? |
| | |
| | 6) SHEET A1.0 ACCESSIBLE RESTROOM DETAIL INDICATES THE |
| | DIMENSIONS TO THE CENTERLINE, PLEASE NOTE IN THE NEW |
| | 2010 ACCESSIBLITY CODE THESE MEASUREMENTS ARE TAKEN TO |
| | THE TOP OF THE GRAB BARS 2010 FBC-ACCESSIBILITY CODE |
| | 609.3. |
| | |
| | 7) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 803.1.1 |
| | INTERIOR WALL AND CEILING FINISH MATERIALS. |
| | |
| | 8) SHEET A1.0 PLAN NOTE # 6 INDICATES THE PROJECT IS |
| | LOCATED WITHIN THE HVHZ, ONLY BROWARD & DADE COUNTIES |
| | ARE CONSIDERED TO BE THE HIGH VELOCITY HURRICANE ZONE. |
| | WITH COMMENT NUMBER (3) PRODUCT APPROVALS WILL BE |
| | REQUIRED FOR THE REPLACEMENT OF THE FRONT ENTRY DOOR( |
| | 1715.5.3) , IF GLAZED THEN PROTECTION OF GLAZED |
| | OPENINGS IN ACCORDANCE WITH 1609.1.2. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | |
| | 9) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 10) SHEET A2.0 DOES NOT INDICATE EXISTING FIRE |
| | SPRINKLERS LOCATED WITHIN THE EXIT PASSAGEWAY, PLEASE |
| | REVIEW SECTION 2010 FBC-B 1027.1.EXCEPTION 1.3. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |