Plan Review Details - Permit 12080772
Plan Review Stops For Permit 12080772
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-10-15 Cont ID  
Sent By jgomez Date 2012-10-12 Time 15:18 Rev Time 0.00
Received By jgomez Date 2012-10-12 Time 15:18 Sent To  
Notes
2012-10-12 15:39:56BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS.
 ACCORDING TO SEC. R301.2.1.4.3 THIS HOUSE IS LOCATED ON
 EXPOSURE "D" NOT "C". REVISE AS REQUIRED.
  
  
  
 NOTE: ROOF SHEATHING AND TRUSSES DONE UNDER A SEPARATE
 PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-09-25 Cont ID  
Sent By jgomez Date 2012-09-20 Time 16:50 Rev Time 0.00
Received By jgomez Date 2012-09-24 Time 11:39 Sent To  
Notes
2012-09-21 15:57:13RESIDENTIAL (R3) REPAIRS BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- SHEET A-0:
 A) ACCORDING TO SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL CODE THIS BUILDING IS LOCATED ON
 EXPOSURE "D" NOT "C". ARCHITECT TO REVISE THE BUILDING
 EXPOSURE AND THE DOORS AND WINDOWS DESIGN PRESSURES.
  
 B) ARCHITECT TO REVISE THE WIND SPEED INFORMATION.
 SPECIFY THE ULTIMATE DESIGN WIND SPEED ( 170 MPH VULT)
 AND THE NOMINAL DESIGN WIND SPEED (132 MPH VASD). SEC.
 R301.2.1.3.
  
 C) ARCHITECT TO REVISE THE INFORMATION SHOWN ON THE
 "PROJECT DATA". ACCORDING TO PLANS SUBMITTED THERE IS
 NOT ADDITION SHOWN. ALSO, THE CONSTRUCTION TYPE IS NOT
 CONSTRUCTION TYPE IV. SEE SEC. 602.5 OF FBC-BUILDING
 CODE AND REVISE AS REQUIRED.
  
 D) AIR CONDITIONED SQUARE FOOTAGE SHOWN ON THE BUILDING
 AREA DOESN'T MATCH AIR CONDITIONED SQUARE FOOTAGE SHOWN
 ON THE ENERGY CALCULATIONS. COORDINATE AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- SHEET A-1:
 A) REVISE GENERAL NOTE #2. SPECIFY THE CURRENT CODE IN
 EFFECT AND REVISE THE WIND SPEED. SEE ITEM # 1(B)
 ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) ROOF NOTE #1 STATES THAT ROOF TRUSSES ARE TO BE
 REMOVED AND REPLACED. PROVIDE ROOF FRAMING PLAN AND
 TRUSS ANCHOR SCHEDULE. TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.2.1.4.3.
  
 C) PROVIDE ROOF SHEATHING FASTENING SPECIFICATIONS.
 INCLUDE NAILING TYPE AND SPACING FOR ROOF ZONE #3 AS
 REQUIRED BY SEC. R803.2.3.1.
  
 D) FLOOR PLAN: CLARIFY HOW TO ENTER BEDROOM #1 AND #2.
 THERE IS A WALL BLOCKING THE ENTRANCE. CLARIFY WHAT ARE
 THE ARROWS SHOWN ON THE MASTER BEDROOM CLOSET SHOWN
 FOR?. CLARIFY WHAT ARE THE LINES SHOWN ON THE WEST SIDE
 WINDOW OF THE LANAI SHOWN FOR?. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 E) PROVIDE SIZES OF WINDOWS AND DOORS TO VERIFY
 COMPLIANCE WITH THE ENERGY CALCULATIONS. SEC. 107.2.1
 CITY AMENDMENTS AND SEC. 405.5 OF FBC-ENERGY
 CONSERVATION.
  
 3- ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE CORRECT ADDRESS. THIS IS NOT 29TH STREET.
 SEC. 405.4.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) REVISE CONDITIONED FLOOR AREA. COORDINATE WITH ITEM
 #1D ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOW MULLIONS AS SHOWN ON PLANS.
  
 B) ROOF SHINGLES. FLORIDA PRODUCT APPROVAL FL5444-R3
 SUBMITTED IS FOR THE 2007 BUILDING CODE. NEED CURRENT
 2010 CODE.
  
 C) TRUSSES STRUCTURAL CONNECTORS SPECIFIED BY THE
 ARCHITECT FOR THE NEW TRUSSES. PROVIDE ONLY THE PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR.
  
 5- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 6- FLAT ROOF PRODUCT APPROVAL: PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS FOR THE NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF THE FLAT ROOF NOA
 08-0410.09 SUBMITTED. NEED CALCULATIONS TO MEET THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3.
  
 7- SPECIFY SIZE OF WINDOWS FOR BEDROOM #1 TO VERIFY
 COMPLIANCE WITH EGRESS REQUIREMENTS SEC. R310 AND SEC.
 601.2 AND SEC. 604.1 OF 2010 FBC-EXISTING BUILDING
 CODE. SPECIFY SIZE AND TYPE OF EXISTING WINDOW TO BE
 REPLACED AND PROPOSED WINDOW. WHAT'S THERE A SINGLE
 WINDOW REPLACED WITH 2 WINDOWS MULLED TOGETHER. THIS
 WILL REDUCE THE SIZE OPENING FROM THE WINDOW.
 THEREFORE, MAKING THE OPENING SMALLER THAN IT WAS.
  
 8- NEW TRUSSES. THEREFORE NEW ROOF:
 A) PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE ATTIC VENTILATION SEC. R806.
  
 B) PROVIDE DETAILS AND SPECIFICATIONS FOR ATTIC ACCESS
 TO SHOW COMPLIANCE WITH SEC. R807.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-08-24 Cont ID  
Sent By rlecky Date 2012-08-24 Time 12:51 Rev Time 0.00
Received By rlecky Date 2012-08-24 Time 12:32 Sent To  
Notes
2012-08-24 12:43:22PLEASE OBSERVE THE FOLLOWING CONDITIONS PLACED ON THE
 PLANS.
  
 PROVISO:
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. 2010 FBC R314,
 315
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS. NEC 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-10-15 Cont ID  
Sent By jgomez Date 2012-10-15 Time 09:32 Rev Time 0.00
Received By jgomez Date 2012-10-10 Time 13:18 Sent To  
Notes
2012-10-10 13:19:03RESUBMITTAL PACKAGE SENT TO JULIO'S DESK FOR REVIEW.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-09-28 Cont ID  
Sent By mdekle Date 2012-09-25 Time   Rev Time 0.00
Received By mdekle Date 2012-08-23 Time 09:42 Sent To  
Notes
2012-08-23 09:43:14R03

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-10-15 Cont ID  
Sent By jgomez Date 2012-10-15 Time 09:31 Rev Time 0.00
Received By jgomez Date 2012-10-15 Time 09:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-09-25 Cont ID  
Sent By jgomez Date 2012-09-21 Time 16:51 Rev Time 0.00
Received By jgomez Date 2012-09-21 Time 14:11 Sent To  
Notes
2012-09-25 11:09:12RESIDENTIAL (R3) REPAIRS MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE EQUIPMENT SIZING CALCULATIONS. COORDINATE
 WITH ARCHITECTURAL PLANS FOR TOTAL AIR CONDITIONED AREA
 AND REVISE CALCULATIONS AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 2- SHEET A-3:
 A) SPECIFY SIZES OF ALL THE TRANSFER DUCTS AND GRILLES
 TO VERIFY COMPLIANCE COMPLIANCE WITH THE BALANCED
 RETURN AIR SEC. M1602.4 OF 2010 FBC-RESIDENTIAL CODE.
  
 B) CLARIFY HOW IS THE LANAI AREA GOING TO BE AIR
 CONDITIONED. NOT GRILLES SHOWN ON THIS AREA AND THERE
 ARE PLENTY OF WINDOWS ON THIS AREA. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-09-21 Cont ID  
Sent By jgomez Date 2012-09-21 Time 14:11 Rev Time 0.00
Received By jgomez Date 2012-09-21 Time 14:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-10-12 Cont ID  
Sent By mdekle Date 2012-10-12 Time   Rev Time 0.00
Received By mdekle Date 2012-10-12 Time   Sent To  
Notes
2012-10-12 15:03:29PASSED PURSUANT TO (SEPERATE) PERMIT #12100366 FOR THE
 LANDSCAPING/IRRIGATION.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-09-25 Cont ID  
Sent By mdekle Date 2012-09-25 Time   Rev Time 0.00
Received By mdekle Date 2012-09-25 Time   Sent To  
Notes
2012-09-25 14:50:59PLANNING & ZONING: **** FAILED ****
 PLEASE RESPOND TO COMMENTS IN WRITING.
  
 1.PURSUANT TO SECTION SEC. 94-441 OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS ("ZLDR"), THE PROPOSED
 RENOVATION EXCEEDS 50 PERCENT OF THE VALUE OF THE
 STRUCTURE THEREFORE THE APPLICANT MUST SUBMIT A
 LANDSCAPE PLAN TO THE CITY WHICH DEMONSTRATES
 COMPLIANCE WITH SEC. 94-442 WHICH STATES THE FOLLOWING:
  
 94-442 (B) (2) A. SINGLE-FAMILY DWELLING UNITS. FOR
 SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHADE,
 FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR EACH 1,200
 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF. FOR
 SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHRUB SHALL
 BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF.
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AND/OR
 CONSULT THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA
 PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
  
  
  