| Plan Review Stops For Permit 12080707 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2012-08-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-08-24 |
Time |
08:36 |
Rev Time |
4.00 |
| Received By |
jwitmer |
Date |
2012-08-23 |
Time |
17:08 |
Sent To |
|
|
| Notes |
| 2012-08-23 18:57:42 | BUILDING PLAN REVIEW | | | PERMIT: 12080707 | | | ADD: 700 S ROSEMARY AVE SUITE # 100 | | | CONT: TO BE DETERMINED | | | TEL: (561)856-6655 NEYITA | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | BUILDING PROVISOS: | | | | | | 1) SHEET A2.5 DETAILS 1 & 2 AND SHEET A5.3 DETAILS 1 & | | | 2 THE DESIGNER OF RECORD TO PROVIDE TYPE OF FASTENERS | | | TO BE INSTALLED FOR THE DECORATIVE FEATURES TO THE | | | STRUCTURE ABOVE, PROVIDE SPACING, AND TYPE OF ANCHORS | | | BY THE TIME OF FRAMING INSPECTION. 2010 FBC-B 2506.2 | | | STEEL STUDS NON-LOAD BEARING. | | | | | | 2) UPDATE PLANS SHEET A0.2 HANDICAPPED RESTROOMS ARE | | | MISSING THE REQUIRED LAVATORY IN THE STALL, SHEET A4.3 | | | DETAIL # 1 INDICATES LAVATORY IN STALL. 2010 FBC-B | | | 604.8.1.6. | | | | | | 3) FIRE SPRINKLER PLANS ARE REQUIRED TO BE SUBMITTED, | | | TO UPDATE CHANGE OF HEAD LOCATION PER 2010FBC-B | | | 107.3.51.1(5) | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2012-09-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-09-20 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-09-20 |
Time |
14:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2012-08-28 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-08-28 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-08-24 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2012-08-27 10:29:36 | 12080707 | | | 700 S. ROSEMARY AVENUE # 100 | | | MELLOW YELLOW BUILD OUT | | | | | | PLEASE CLARIFY THE ELECTRICAL RISER PLAN AS NOTED. | | | | | | DISTRIBUTION PANEL ?LDP? AND PANEL ?LP1? MAY BE | | | MISLABELED. NEC 215.5 | | | | | | ?LP1 / LDP? REQUIRE A MAIN BREAKER. NEC 408.36 | | | | | | INDICATE THE SIZE OF THE XFMR. PROVIDE LINE AND LOAD | | | FEEDER CONDUCTOR SIZES. NEC 215.5 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2012-08-26 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-08-26 |
Time |
18:40 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-08-26 |
Time |
18:04 |
Sent To |
|
|
| Notes |
| 2012-08-26 18:39:57 | 700 SOUTH ROSEMARY AVENUE - SUITE #100 | | | PERMIT #12080707 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO - SUBMIT REVISION***** | | | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND | | | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT | | | 500 NORTH DIXIE HIGHWAY. | | | | | | ALL DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO | | | SMOKING" SIGNS POSTED. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | EVERY ASSEMBLY OCCUPANCY SHALL HAVE THE OCCUPANT LOAD | | | OF THE ROOM POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN | | | EXIT FROM THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE | | | THE NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM. | | | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION | | | 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES | | | SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE | | | DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE | | | SPRINKLERS. AFTER THE BUILDING PERMIT HAS BEEN ISSUED, | | | THE SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS | | | (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) | | | FOR A SUB-PERMIT. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR | | | THEMODIFICATION OF THE FIRE SPRINKLER SYSTEM, FIRE | | | ALARM SYSTEM, AND KITCHEN SUPPRESSION SYSTEM. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2012-09-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-09-20 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-09-18 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2012-09-19 09:42:51 | * * * * EXPEDITED * * * * | | | * * * * ROUND 2 * * * * |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-09-04 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2012-08-30 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2012-08-21 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2012-08-21 16:50:07 | EXPEDITED | | | C--2 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2012-09-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-09-24 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-09-24 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2012-09-24 13:45:03 | 9/24/2012 PLANS WERE TAKEN TO PALM BEACH COUNTY IMPACT | | | FEE OFFICE FOR IMPACT FEE ASSESSMENT, PLANS WERE | | | STAMPED NO FEE DUE. JW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2012-08-28 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2012-08-28 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2012-08-28 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2012-08-28 08:42:21 | PASS PROVISO | | | 1) SEPARATE PERMITS REQUIRED FOR HOODS,COOLERS & FIRE | | | SUPPRESSION. | | | 2) PROVIDE A DETAIL FROM THE ENGINEER FOR THE NEW | | | EXHAUST FAN # 1 | | | TIE DOWN TO THE CURB PER SECTION 301.12 WIND RESISTANCE | | | 2010 FBC (M) | | | 3) REFER TO SECTION 304.11 GUARDS 2010 FBC (M) | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2012-08-27 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2012-08-27 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2012-08-27 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2012-08-27 11:54:33 | ***PROVISO*** | | | 1. SHEET P1.0, P1.1 PLUMBING FOR HC LAVATORY SHALL | | | REMAIN. | | | FBC 2010 ACCESSIBILITY 202.3.1 PROHIBITED REDUCTION IN | | | ACCESS. AN ALTERATION THAT DECREASES OR HAS THE EFFECT | | | OF DECREASING THE ACCESSIBILITY OF A BUILDING OR | | | FACILITY BELOW THE REQUIREMENTS FOR NEW CONSTRUCTION AT | | | THE TIME OF THE ALTERATION IS PROHIBITED. | | | | | | 2. SHEET P2.2, P2.1 | | | EXISTING HC LAVATORIES SHALL REMAIN. | | | FBC 2010 ACCESSIBILITY 202.3.1 PROHIBITED REDUCTION IN | | | ACCESS. AN ALTERATION THAT DECREASES OR HAS THE EFFECT | | | OF DECREASING THE ACCESSIBILITY OF A BUILDING OR | | | FACILITY BELOW THE REQUIREMENTS FOR NEW CONSTRUCTION AT | | | THE TIME OF THE ALTERATION IS PROHIBITED. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2012-10-02 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2012-10-02 |
Time |
16:00 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2012-10-02 |
Time |
16:00 |
Sent To |
PC |
|
| Notes |
| 2012-10-02 15:20:29 | PASSED W/PROVISO | | | | | | 1) PRIOR TO THE FIRST INSPECTION, FULL SIZED SHEETS | | | A0.3 (REVISED), A0.4, AND A2.6 SHALL BE SUBMITTED AS A | | | PERMIT REVISION TO REFLECT CHANGES AS SHOWN ON THE | | | REDUCED COPIES OF THE SHEETS INCLUDED IN THE APPROVED | | | PERMIT. | | | | | | 2) SIGNS REQUIRE A SEPARATE PERMIT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2012-09-20 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2012-09-20 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2012-09-20 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2012-09-20 11:48:09 | FAILED | | | | | | PROVIDE WRITTEN RESPONSE TO COMMENTS. | | | | | | 1) REPEAT COMMENT - THE PLANS MENTION THAT THERE ARE | | | CONDENSERS AND COMPRESSORS WHICH HAVE LOCATIONS THAT | | | NEED TO BE VERIFIED. WHERE ARE THESE ITEMS? ARE THEY ON | | | THE ROOF TOP OR GROUND MOUNTED OR INSIDE THE BUILDING? | | | IF ROOFTOP OR OUTSIDE AND NEW OR REPLACEMENT INSTALL, | | | THEN THEY SHALL BE SCREENED IN ACCORDANCE WITH THE | | | CITYPLACE DRI REGULATIONS: ALL ROOFTOP AND GROUND LEVEL | | | MECHANICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO SUCH | | | ITEMS AS PUBLIC AND PRIVATE UTILITY SERVICE | | | CONNECTIONS; HEATING, VENTILATING, AND AIR CONDITIONING | | | SYSTEMS; COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT, | | | SHALL BE SCREENED FROM PUBLIC VIEW THROUGH ANY | | | COMBINATION OF LANDSCAPING, WALLS AND EQUIPMENT | | | LOCATION. PROVIDE VERIFICATION THAT THE SCREENING | | | REQUIREMENT IS MET. | | | | | | 2) REPEAT COMMENT - THE NEW FAN SHOWN TO BE INSTALLED | | | ON THE ROOFTOP SHALL BE SCREENED IN ACCORDANCE WITH THE | | | CTIYPLACE DRI REQUIREMENTS. PROVIDE VERIFICATION THAT | | | THE SCREENING REQUIREMENT IS MET. | | | | | | 3) REPEAT COMMENT - THE PLANS SHOW OUTDOOR SEATING | | | ALONG ROSEMARY AVENUE (LOUNGE ON PLANS). PLEASE PROVIDE | | | DETAILS ON THIS AREA, INCLUDING DIMENSIONS, WHAT THE | | | ITEMS SHOWN ARE (BIG SQUARES), AND A SURVEY TO SHOW | | | WHERE THE OUTDOOR FEATURES ARE LOCATED IN RELATIONSHIP | | | TO THE PEDESTRIAN EASEMENT AND PUBLIC RIGHT-OF-WAY. | | | | | | 4) REPEAT COMMENT - PLEASE EXPLAIN THE TAKE-OUT ("TO | | | GO") COUNTER OPERATIONS ON THE EAST SIDE OF THE | | | BUILDING. IS THIS INTENDED FOR CURBSIDE PICK-UP OR | | | DELIVERY? IF SO PLEASE SHOW ON A PLAN THE PROPOSED | | | VEHICULAR CIRCULATION IN THE IMMEDIATE AREA. | | | | | | PLEASE NOTE THAT SIGNAGE SHALL COMPLY WITH THE | | | CITYPLACE MASTER SIGN PLAN AND REQUIRES A SEPARATE | | | PERMIT. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2012-08-30 |
|
|
Cont ID |
|
| Sent By |
Eschneid |
Date |
2012-08-30 |
Time |
09:57 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2012-08-30 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2012-08-30 10:21:48 | FAILED | | | | | | PROVIDE WRITTEN RESPONSE TO COMMENTS. | | | | | | 1) THE PLANS MENTION THAT THERE ARE CONDENSERS AND | | | COMPRESSORS WHICH HAVE LOCATIONS TO BE VERIFIED. WERE | | | ARE THE ITEMS? ARE THEY ON THE ROOF TOP OR GROUND | | | MOUNTED OR INSIDE THE BUILDING? IF ROOFTOP OR OUTSIDE | | | AND NEW OR REPLACEMENT INSTALL, THEN THEY SHALL BE | | | SCREENED IN ACCORDANCE WITH THE CITYPLACE DRI | | | REGULATIONS: ALL ROOFTOP AND GROUND LEVEL MECHANICAL | | | EQUIPMENT, INCLUDING BUT NOT LIMITED TO SUCH ITEMS AS | | | PUBLIC AND PRIVATE UTILITY SERVICE CONNECTIONS; | | | HEATING, VENTILATING, AND AIR CONDITIONING SYSTEMS; | | | COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT, SHALL BE | | | SCREENED FROM PUBLIC VIEW THROUGH ANY COMBINATION OF | | | LANDSCAPING, WALLS AND EQUIPMENT LOCATION. PROVIDE | | | VERIFICATION THAT THE SCREENING REQUIREMENT IS MET. | | | | | | 2) THE NEW FAN SHOWN TO BE INSTALLED ON THE ROOFTOP | | | SHALL BE SCREENED IN ACCORDANCE WITH THE CTIYPLACE DRI | | | REQUIREMENTS. PROVIDE VERIFICATION THAT THE SCREENING | | | REQUIREMENT IS MET. | | | | | | 3) THE PLANS SHOW OUTDOOR SEATING ALONG ROSEMARY AVENUE | | | (LOUNGE ON PLANS). PLEASE PROVIDE DETAILS ON THIS AREA, | | | INCLUDING DIMENSIONS, WHAT THE ITEMS SHOWN ARE (BIG | | | SQUARES), AND A SURVEY TO SHOW WHERE THE OUTDOOR | | | FEATURES ARE LOCATED IN RELATIONSHIP TO THE PEDESTRIAN | | | EASEMENT AND PUBLIC RIGHT-OF-WAY. | | | | | | 4) PLEASE EXPLAIN THE TAKE-OUT COUNTER OPERATIONS ON | | | THE EAST SIDE OF THE BUILDING. IS THIS INTENDED FOR | | | CURBSIDE PICK-UP OR DELIVERY? IF SO PLEASE SHOW ON A | | | PLAN THE PROPOSED VEHICULAR CIRCULATION IN THE | | | IMMEDIATE AREA. | | | | | | PLEASE NOTE THAT SIGNAGE SHALL COMPLY WITH THE | | | CITYPLACE MASTER SIGN PLAN AND REQUIRES A SEPARATE | | | PERMIT. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|