Plan Review Details - Permit 12080707
Plan Review Stops For Permit 12080707
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-08-24 Cont ID  
Sent By jwitmer Date 2012-08-24 Time 08:36 Rev Time 4.00
Received By jwitmer Date 2012-08-23 Time 17:08 Sent To  
Notes
2012-08-23 18:57:42BUILDING PLAN REVIEW
 PERMIT: 12080707
 ADD: 700 S ROSEMARY AVE SUITE # 100
 CONT: TO BE DETERMINED
 TEL: (561)856-6655 NEYITA
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING PROVISOS:
  
 1) SHEET A2.5 DETAILS 1 & 2 AND SHEET A5.3 DETAILS 1 &
 2 THE DESIGNER OF RECORD TO PROVIDE TYPE OF FASTENERS
 TO BE INSTALLED FOR THE DECORATIVE FEATURES TO THE
 STRUCTURE ABOVE, PROVIDE SPACING, AND TYPE OF ANCHORS
 BY THE TIME OF FRAMING INSPECTION. 2010 FBC-B 2506.2
 STEEL STUDS NON-LOAD BEARING.
  
 2) UPDATE PLANS SHEET A0.2 HANDICAPPED RESTROOMS ARE
 MISSING THE REQUIRED LAVATORY IN THE STALL, SHEET A4.3
 DETAIL # 1 INDICATES LAVATORY IN STALL. 2010 FBC-B
 604.8.1.6.
  
 3) FIRE SPRINKLER PLANS ARE REQUIRED TO BE SUBMITTED,
 TO UPDATE CHANGE OF HEAD LOCATION PER 2010FBC-B
 107.3.51.1(5)
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-09-20 Cont ID  
Sent By rlecky Date 2012-09-20 Time 15:55 Rev Time 0.00
Received By rlecky Date 2012-09-20 Time 14:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-08-28 Cont ID  
Sent By rlecky Date 2012-08-28 Time 13:13 Rev Time 0.00
Received By rlecky Date 2012-08-24 Time 16:51 Sent To  
Notes
2012-08-27 10:29:3612080707
 700 S. ROSEMARY AVENUE # 100
 MELLOW YELLOW BUILD OUT
  
 PLEASE CLARIFY THE ELECTRICAL RISER PLAN AS NOTED.
  
 DISTRIBUTION PANEL ?LDP? AND PANEL ?LP1? MAY BE
 MISLABELED. NEC 215.5
  
 ?LP1 / LDP? REQUIRE A MAIN BREAKER. NEC 408.36
  
 INDICATE THE SIZE OF THE XFMR. PROVIDE LINE AND LOAD
 FEEDER CONDUCTOR SIZES. NEC 215.5
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-08-26 Cont ID  
Sent By wjolin Date 2012-08-26 Time 18:40 Rev Time 0.00
Received By wjolin Date 2012-08-26 Time 18:04 Sent To  
Notes
2012-08-26 18:39:57700 SOUTH ROSEMARY AVENUE - SUITE #100
 PERMIT #12080707
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ALL DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 EVERY ASSEMBLY OCCUPANCY SHALL HAVE THE OCCUPANT LOAD
 OF THE ROOM POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN
 EXIT FROM THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE
 THE NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS. AFTER THE BUILDING PERMIT HAS BEEN ISSUED,
 THE SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR
 THEMODIFICATION OF THE FIRE SPRINKLER SYSTEM, FIRE
 ALARM SYSTEM, AND KITCHEN SUPPRESSION SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-20 Cont ID  
Sent By rlecky Date 2012-09-20 Time 15:55 Rev Time 0.00
Received By rlecky Date 2012-09-18 Time 09:37 Sent To  
Notes
2012-09-19 09:42:51* * * * EXPEDITED * * * *
 * * * * ROUND 2 * * * *

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-09-04 Cont ID  
Sent By lmartine Date 2012-08-30 Time 09:23 Rev Time 0.00
Received By lmartine Date 2012-08-21 Time 16:49 Sent To  
Notes
2012-08-21 16:50:07EXPEDITED
 C--2

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2012-09-24 Cont ID  
Sent By jwitmer Date 2012-09-24 Time 13:38 Rev Time 0.00
Received By jwitmer Date 2012-09-24 Time 13:38 Sent To  
Notes
2012-09-24 13:45:039/24/2012 PLANS WERE TAKEN TO PALM BEACH COUNTY IMPACT
 FEE OFFICE FOR IMPACT FEE ASSESSMENT, PLANS WERE
 STAMPED NO FEE DUE. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-08-28 Cont ID  
Sent By hmoser Date 2012-08-28 Time 08:42 Rev Time 0.00
Received By hmoser Date 2012-08-28 Time 07:49 Sent To  
Notes
2012-08-28 08:42:21PASS PROVISO
 1) SEPARATE PERMITS REQUIRED FOR HOODS,COOLERS & FIRE
 SUPPRESSION.
 2) PROVIDE A DETAIL FROM THE ENGINEER FOR THE NEW
 EXHAUST FAN # 1
 TIE DOWN TO THE CURB PER SECTION 301.12 WIND RESISTANCE
 2010 FBC (M)
 3) REFER TO SECTION 304.11 GUARDS 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-08-27 Cont ID  
Sent By lwagner Date 2012-08-27 Time 14:08 Rev Time 0.00
Received By lwagner Date 2012-08-27 Time 10:42 Sent To  
Notes
2012-08-27 11:54:33***PROVISO***
 1. SHEET P1.0, P1.1 PLUMBING FOR HC LAVATORY SHALL
 REMAIN.
 FBC 2010 ACCESSIBILITY 202.3.1 PROHIBITED REDUCTION IN
 ACCESS. AN ALTERATION THAT DECREASES OR HAS THE EFFECT
 OF DECREASING THE ACCESSIBILITY OF A BUILDING OR
 FACILITY BELOW THE REQUIREMENTS FOR NEW CONSTRUCTION AT
 THE TIME OF THE ALTERATION IS PROHIBITED.
  
 2. SHEET P2.2, P2.1
 EXISTING HC LAVATORIES SHALL REMAIN.
 FBC 2010 ACCESSIBILITY 202.3.1 PROHIBITED REDUCTION IN
 ACCESS. AN ALTERATION THAT DECREASES OR HAS THE EFFECT
 OF DECREASING THE ACCESSIBILITY OF A BUILDING OR
 FACILITY BELOW THE REQUIREMENTS FOR NEW CONSTRUCTION AT
 THE TIME OF THE ALTERATION IS PROHIBITED.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2012-10-02 Cont ID  
Sent By eschneid Date 2012-10-02 Time 16:00 Rev Time 1.00
Received By eschneid Date 2012-10-02 Time 16:00 Sent To PC
Notes
2012-10-02 15:20:29PASSED W/PROVISO
  
 1) PRIOR TO THE FIRST INSPECTION, FULL SIZED SHEETS
 A0.3 (REVISED), A0.4, AND A2.6 SHALL BE SUBMITTED AS A
 PERMIT REVISION TO REFLECT CHANGES AS SHOWN ON THE
 REDUCED COPIES OF THE SHEETS INCLUDED IN THE APPROVED
 PERMIT.
  
 2) SIGNS REQUIRE A SEPARATE PERMIT.

Review Stop Z ZONING
Rev No 2 Status F Date 2012-09-20 Cont ID  
Sent By eschneid Date 2012-09-20 Time 11:45 Rev Time 0.00
Received By eschneid Date 2012-09-20 Time 11:45 Sent To  
Notes
2012-09-20 11:48:09FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) REPEAT COMMENT - THE PLANS MENTION THAT THERE ARE
 CONDENSERS AND COMPRESSORS WHICH HAVE LOCATIONS THAT
 NEED TO BE VERIFIED. WHERE ARE THESE ITEMS? ARE THEY ON
 THE ROOF TOP OR GROUND MOUNTED OR INSIDE THE BUILDING?
 IF ROOFTOP OR OUTSIDE AND NEW OR REPLACEMENT INSTALL,
 THEN THEY SHALL BE SCREENED IN ACCORDANCE WITH THE
 CITYPLACE DRI REGULATIONS: ALL ROOFTOP AND GROUND LEVEL
 MECHANICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO SUCH
 ITEMS AS PUBLIC AND PRIVATE UTILITY SERVICE
 CONNECTIONS; HEATING, VENTILATING, AND AIR CONDITIONING
 SYSTEMS; COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT,
 SHALL BE SCREENED FROM PUBLIC VIEW THROUGH ANY
 COMBINATION OF LANDSCAPING, WALLS AND EQUIPMENT
 LOCATION. PROVIDE VERIFICATION THAT THE SCREENING
 REQUIREMENT IS MET.
  
 2) REPEAT COMMENT - THE NEW FAN SHOWN TO BE INSTALLED
 ON THE ROOFTOP SHALL BE SCREENED IN ACCORDANCE WITH THE
 CTIYPLACE DRI REQUIREMENTS. PROVIDE VERIFICATION THAT
 THE SCREENING REQUIREMENT IS MET.
  
 3) REPEAT COMMENT - THE PLANS SHOW OUTDOOR SEATING
 ALONG ROSEMARY AVENUE (LOUNGE ON PLANS). PLEASE PROVIDE
 DETAILS ON THIS AREA, INCLUDING DIMENSIONS, WHAT THE
 ITEMS SHOWN ARE (BIG SQUARES), AND A SURVEY TO SHOW
 WHERE THE OUTDOOR FEATURES ARE LOCATED IN RELATIONSHIP
 TO THE PEDESTRIAN EASEMENT AND PUBLIC RIGHT-OF-WAY.
  
 4) REPEAT COMMENT - PLEASE EXPLAIN THE TAKE-OUT ("TO
 GO") COUNTER OPERATIONS ON THE EAST SIDE OF THE
 BUILDING. IS THIS INTENDED FOR CURBSIDE PICK-UP OR
 DELIVERY? IF SO PLEASE SHOW ON A PLAN THE PROPOSED
 VEHICULAR CIRCULATION IN THE IMMEDIATE AREA.
  
 PLEASE NOTE THAT SIGNAGE SHALL COMPLY WITH THE
 CITYPLACE MASTER SIGN PLAN AND REQUIRES A SEPARATE
 PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-08-30 Cont ID  
Sent By Eschneid Date 2012-08-30 Time 09:57 Rev Time 1.00
Received By eschneid Date 2012-08-30 Time 09:57 Sent To  
Notes
2012-08-30 10:21:48FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) THE PLANS MENTION THAT THERE ARE CONDENSERS AND
 COMPRESSORS WHICH HAVE LOCATIONS TO BE VERIFIED. WERE
 ARE THE ITEMS? ARE THEY ON THE ROOF TOP OR GROUND
 MOUNTED OR INSIDE THE BUILDING? IF ROOFTOP OR OUTSIDE
 AND NEW OR REPLACEMENT INSTALL, THEN THEY SHALL BE
 SCREENED IN ACCORDANCE WITH THE CITYPLACE DRI
 REGULATIONS: ALL ROOFTOP AND GROUND LEVEL MECHANICAL
 EQUIPMENT, INCLUDING BUT NOT LIMITED TO SUCH ITEMS AS
 PUBLIC AND PRIVATE UTILITY SERVICE CONNECTIONS;
 HEATING, VENTILATING, AND AIR CONDITIONING SYSTEMS;
 COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT, SHALL BE
 SCREENED FROM PUBLIC VIEW THROUGH ANY COMBINATION OF
 LANDSCAPING, WALLS AND EQUIPMENT LOCATION. PROVIDE
 VERIFICATION THAT THE SCREENING REQUIREMENT IS MET.
  
 2) THE NEW FAN SHOWN TO BE INSTALLED ON THE ROOFTOP
 SHALL BE SCREENED IN ACCORDANCE WITH THE CTIYPLACE DRI
 REQUIREMENTS. PROVIDE VERIFICATION THAT THE SCREENING
 REQUIREMENT IS MET.
  
 3) THE PLANS SHOW OUTDOOR SEATING ALONG ROSEMARY AVENUE
 (LOUNGE ON PLANS). PLEASE PROVIDE DETAILS ON THIS AREA,
 INCLUDING DIMENSIONS, WHAT THE ITEMS SHOWN ARE (BIG
 SQUARES), AND A SURVEY TO SHOW WHERE THE OUTDOOR
 FEATURES ARE LOCATED IN RELATIONSHIP TO THE PEDESTRIAN
 EASEMENT AND PUBLIC RIGHT-OF-WAY.
  
 4) PLEASE EXPLAIN THE TAKE-OUT COUNTER OPERATIONS ON
 THE EAST SIDE OF THE BUILDING. IS THIS INTENDED FOR
 CURBSIDE PICK-UP OR DELIVERY? IF SO PLEASE SHOW ON A
 PLAN THE PROPOSED VEHICULAR CIRCULATION IN THE
 IMMEDIATE AREA.
  
 PLEASE NOTE THAT SIGNAGE SHALL COMPLY WITH THE
 CITYPLACE MASTER SIGN PLAN AND REQUIRES A SEPARATE
 PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.