Plan Review Details - Permit 12080534
Plan Review Stops For Permit 12080534
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-09-12 Cont ID  
Sent By rmcdouga Date 2012-09-12 Time 09:38 Rev Time 0.00
Received By rmcdouga Date 2012-09-10 Time 07:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-22 Cont ID  
Sent By rmcdouga Date 2012-08-22 Time 08:38 Rev Time 0.00
Received By rmcdouga Date 2012-08-21 Time 06:33 Sent To  
Notes
2012-08-21 13:22:442010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO SETS OF ENERGY CALCULATIONS SHOWING
 COMPLIANCE WITH FBC ENERGY CONSERVATION CHAPTER 4.
  
 2) SHOW COMPLIANCE WITH FBC R310.1 FOR EMERGENCY ESCAPE
 AND RESCUE OPENINGS IN BEDROOMS NUMBER 1 AND 2.
  
 3) CLARIFY THE ROOF FRAMING OVER THE AREA BETWEEN THE
 FLORIDA ROOM AND THE EXISTING BATH SHOWN ON SHEET 2.1.
 EXPLAIN HOW THE TRUSSES ARE SUPPORTED AT THE OUTER
 ENDS.
  
 4) UNDER THE DESIGN PARAMETERS ON SHEET 1.1 PLEASE
 UPDATE THE EDITION OF ASCE 7 TO ASCE 7-10 WHICH IS THE
 ONE REFERENCED IN THE 2010 FBCR. FBCR CHAPTER 43.
  
 5) ON SHEET 3.1 THE COMPONENT AND CLADDING PRESSURE
 ZONE TABLE LISTS 140 MPH. THE WINDSPEED FOR WEST PALM
 BEACH IS 170 MPH VULT AND 132 VASD. FBC R301.2.1 &
 R301.2.1.3
  
 6) ON SHEET 4.1 THE TYPICAL GABLE END SECTION
 REINFORCEMENT TABLE SPECIFIES 140 MPH. PLEASE CORRECT.
 FBC R301.2.1 & R301.2.1.3
  
 7) THE WALL SECTION ON 3.1 AND 4.2 SPECIFY R-19 CEILING
 INSULATION. THE SECTION ON 4.1 HAS R-30. PLEASE
 COORDINATE THE R-VALUES ON THE PLANS WITH THE ENERGY
 CALCULATIONS. FBC ENERGY CONSERVATION CHAPTER 4
  
 8) THE DESIGNER OF RECORD FOR THE PROJECT IS REQUIRED
 TO REVIEW AND APPROVE THE PRODUCT APPROVALS IN WRITING.
 CITY AMENDMENTS 107.3.4.1
  
 9) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ROOF
 SHINGLES AS REQUIRED BY DCA RULE 9N-3.
  
 10) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SINGLE
 HUNG WINDOWS SPECIFIED ON THE PLANS. THE PRODUCT
 APPROVALS THAT WERE SUBMITTED ARE FOR HORIZONTAL
 SLIDING WINDOWS. DCA RULE 9N-3.
  
 11) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 GLAZED FRENCH DOORS ARE NOT IMPACT RATED AND REQUIRE
 IMPACT PROTECTION IN ACCORDANCE WITH FBC R301.2.1.2.
 SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE STORM
 PANELS THAT WILL BE USED ON THE SINGLE AND DOUBLE
 FRENCH DOORS. SPECIFY THE ATTACHMENT SYSTEM FROM THE
 PRODUCT APPROVAL THAT WILL BE USED. INCLUDE THE
 MOUNTING OPTION, THE FASTENER TYPE AND SPACING, SPAN
 AND GLASS CLEARANCE REQUIREMENTS.
  
 12) THE PLANS WILL BE REQUIRED TO HAVE AN IMPACT FEE
 REVIEW BY PALM BEACH COUNTY. THE STAMPED PLANS AND A
 COPY OF THE PAID RECEIPT WILL BE REQUIRED TO BE
 SUBMITTED BEFORE THE PERMIT IS ISSUED.
  
 13) IN ORDER TO SPEED THE REVIEW PROCESS, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS
 WERE ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-08-20 Cont ID  
Sent By rlecky Date 2012-08-20 Time 08:17 Rev Time 0.00
Received By rlecky Date 2012-08-20 Time 07:32 Sent To  
Notes
2012-08-20 08:16:44PLEASE OBSERVE THE FOLLOWING CONDITIONS PLACED ON THE
 PLANS.
  
 PROVISO:
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. 2010 FBC R314, 315
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR NEW
 GENERAL PURPOSE OUTLETS. NEC 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-12 Cont ID  
Sent By rmcdouga Date 2012-09-12 Time 09:38 Rev Time 0.00
Received By rmcdouga Date 2012-08-27 Time 10:37 Sent To  
Notes
2012-08-27 10:41:21EXPEDITED '2ND RUN'
2012-08-27 10:40:22IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-22 Cont ID  
Sent By rmcdouga Date 2012-08-22 Time 08:38 Rev Time 0.00
Received By rmcdouga Date 2012-08-16 Time 12:55 Sent To  
Notes
2012-08-16 12:58:13EXPEDITED
 R--3

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-09-12 Cont ID  
Sent By rmcdouga Date 2012-09-12 Time 15:51 Rev Time 0.00
Received By rmcdouga Date 2012-09-12 Time 15:51 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-08-21 Cont ID  
Sent By rmcdouga Date 2012-08-21 Time 06:33 Rev Time 0.00
Received By rmcdouga Date 2012-08-21 Time 06:33 Sent To  
Notes
2012-08-21 06:44:15IMPACT FEE REVIEW BY PALM BEAM COUNTY WILL BE REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-09-10 Cont ID  
Sent By rmcdouga Date 2012-09-10 Time 09:06 Rev Time 0.00
Received By rmcdouga Date 2012-09-10 Time 07:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-08-21 Cont ID  
Sent By rmcdouga Date 2012-08-21 Time 07:16 Rev Time 0.00
Received By rmcdouga Date 2012-08-21 Time 07:16 Sent To  
Notes
2012-08-21 09:04:222010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF ENERGY CALCULATIONS AND EQUIPMENT
 SIZING CALCULATIONS.FBC ENERGY CONSERVATION CHAPTER 4
 AND FBCR M1401.3
  
 2) THE TRANSFER DUCTS FOR NEW BEDROOM #2 AND THE NEW
 MASTER BEDROOM ARE NOT CORRECT. THE PLAN SHOWS THE
 RETURN DUCTS TIED BETWEEN THE TWO ROOMS. IN ORDER TO BE
 CODE COMPLIANT, THEY NEED TO TRANSFER THE AIR FROM EACH
 ROOM TO THE COMMON HALL OR BE TIED DIRECTLY INTO THE
 RETURN AIR AS REQUIRED BY FBCR M1602.4.
  
 3) SPECIFY THE EQUIPMENT, THE SEER AND THE LOADS IN THE
 EQUIPMENT SCHEDULE ON SHEET 5.1. FBC M1401.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-08-21 Cont ID  
Sent By rmcdouga Date 2012-08-21 Time 07:13 Rev Time 0.00
Received By rmcdouga Date 2012-08-21 Time 07:13 Sent To  
Notes
2012-08-21 10:37:33REDLINED PLANS.

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2012-09-07 Time   Rev Time 0.00
Received By   Date 2012-09-07 Time   Sent To  
Notes
2012-09-07 09:05:36GAVE TO MCDOUG.

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2012-08-28 Time   Rev Time 0.00
Received By   Date 2012-08-28 Time   Sent To M
Notes
2012-08-28 16:04:09SPOKE WITH APPLICANT - AWAITING LANDSCAPING SUBMITTAL.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-08-22 Cont ID  
Sent By mdekle Date 2012-08-22 Time   Rev Time 0.00
Received By mdekle Date 2012-08-22 Time 14:58 Sent To  
Notes
2012-08-22 14:58:00THE VALUATION OF THE PROPOSED WORK EXCEEDS 50% OF THE
 ASSESSED VALUE THUS, THE APPLICANT IS REQUIRED TO
 SUBMIT A LANDSCAPING PLAN IN ACCORDANCE WITH CHAPTER
 94, ARTICLE XIV OF THE CITY'S LAND DEVELOPMENT CODE.