| 2012-12-11 11:22:14 | BUILDING PLAN REVIEW |
| | PERMIT: 112080469 |
| | ADD: 6751 N JOG ROAD |
| | CONT: CDM CONSTRUCTORS |
| | TEL: (561)689-3336 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DEC. 11/2012 |
| | ACTION: DENIED |
| | |
| | 1)2ND REQUEST, SHEET710- A1-300 THIRD STORY ROOF TOP |
| | GARDEN AREA, TO DATE THE PLANS ONLY SHOW ONE MEANS OF |
| | EGRASS FROM THE 3RD STORY ROOFTOP GARDEN, PLEASE REVIEW |
| | SECTION 2010 FBC-B TABLE 1021.2 FOR ASSEMBLY |
| | OCCUPANCIES AND SINGLE EXIT. TRUE THERE IS AN ATTACHED |
| | SKYBRIDGE, THAT TO DATE ONLY HAS BEEN REVIEWED FOR THE |
| | PILING AND PILE CAP. THE SUBMITTED PLANS FOR THE |
| | SKYBRIDGE ARE MORE OF CONCEPT DRAWINGS. |
| | PLEASE PROVIDE THE LENGTH OF THE SKYBRIDGE FROM WHERE |
| | IT ATTACHES TO THE VISITORS CENTER OPEN VERTICAL STAIRS |
| | AND THE TOTAL OVERALL LENGTH OF THE SKYBRIDGE WHERE IT |
| | AJOINS TO THE POWER BLOCK BUILDING.. THE PLANS |
| | SUBMIITED FOR THE SKYBRIDGE DO NOT STATE THEY ARE FIRE |
| | SPRINKLERED, THE 2010 FBC-B 3104.9 LIMIT THE LENGTH TO |
| | 200 FEEET OF EXIT ACCESS TRAVEL, EXCEPTION FOR FIRE |
| | SPRINKLERS IS 250 FT. |
| | |
| | 2) 2ND REQUEST, THIS SAME SHEET A1-300 INDICATES A |
| | SKYBRIDEGE TO THE POWER BLOCK, SHEET 710-SS-103 ALSO |
| | MAKES REFERENECE TO THE SKYBRIDGE AND A NOTE |
| | INDICATEING SEE SHEET 710-S3-301 FOR WIND LOADING ON |
| | SKYBRIDGE AND SKYBRIDGE STAIR TOWER. THIS SHEET IS NOT |
| | INCLUDED IN THIS SUBMITION, AT THIS TIME WE CAN ONLY |
| | VIEW THIS AREA AS A SINGLE EXIT FROM THE THIRD FLOOR. |
| | UNTIL THE SKYBRIDGE IS REVIEWED BY BOTH THE BUILDING |
| | DEPARTMENT AND FIRE DEPARTMENT FOR CODE COMPLIANCE AND |
| | PASS THE SKYBRIDGE THE THIRD FLOOR ONLY HAS A SINGLE |
| | EXIT. THERE ARE GOING TO BE AREAS OF QUESTION TO CODE |
| | COMPLIANCE WITH THE OPENESS OF THE SKYBRIDGE AND BEING |
| | WITHIN TEN FEET OF THE POWER BLOCK BUILDING. AGAIN THE |
| | DESIN TEAM IS INDICATING THE POWER BLOCK BUILDING BEING |
| | A TYPE II-B BUILDING EXTERIOR WALLS NOT RATED AND THE |
| | SKYBRIDGE BEING WITHIN 10'-0" PARALLELING THIS |
| | BUILDING. 2010 FBC-B 3104.5 NEEDS TO BE ADDRESSED. |
| | |
| | 3) 2ND REQUEST. SHEET 710-A1-300 INDICATES THE USE OF A |
| | SKYBRIDGE TO THE POWER BLOCK, PLESE REVIEW 2010 FBC-B |
| | 3104.2 SEPERATE STRUCTURES, 3104.3 CONSTRUCTION, 3104.4 |
| | CONTENTS & 3104.5 FIRE BARRIERS BETWEEN PEDESTRIAN |
| | WALKWAYS AND BUILDINGS. THE RESPONSE STATEMENT IS |
| | REFERENECING 3104.5 EXCEPTION# 2 WHICH I AGREE YOU CAN |
| | TAKE FOR THE ELEVATED WALKWAY. |
| | THE 2007 FBC-B CODE COMMENTARY STATES, THESE FOUR |
| | EXCEPTIONS APPLY TO THE WALKWAY RATHER THAN THE |
| | BUILDING THAT THE WALKWAY CONNECTS. SINCE THIS IS THE |
| | SECOND MEANS OF EGRESS FOR THE THIRD FLOOR IT IS |
| | NECCESSARY TO PROTECT THE GLAZED AREA ADJACENT TO THE |
| | WALKWAY WITH 3/4 HR OPENING PROTECTIVES AND AT THE |
| | FLOOR LEVEL |
| | AND TEN FOOT OUT AND TEN FOOT DOWN 2 HOUR PROTECTION |
| | FOR FIRE BARRIER PLEASE REVIEW 2007 FBC-B CODE |
| | COMMENTARY FIGURE 3104.5. |
| | |
| | |
| | |
| | |
| | 4) 2ND REVIEW, SHEET 710-A1-307 & 710-HC-104, THE EAST |
| | STAIR TOWER HAS TWO ISSUES: |
| | 4A) THE MECHANICAL ROOM IS NOT SEPERATED FROM THE |
| | VERTICAL EXIT ENCLOSURE BY A ONE HOUR RATED WALL PER |
| | 2010 FBC-B 1022.1. THERE IS NO CEILING IN THE |
| | MECHANICAL ROOM SEPERATING THE MECHANICAL ROOM FROM THE |
| | STAIRWELL. |
| | |
| | 4B) COMPLIED. |
| | |
| | 4C) NEW COMMENT: SHEET 710-HC-104 WITH THE MECHANICAL |
| | ROOM NOT HAVING WALLS THAT GO TO THE DECK ABOVE THE |
| | INTAKE DUCT WORK AS WELL AS THE MECHANICAL ROOM |
| | EQUIPMENT ARE STILL LOCATED IN THE STAIRWELL. IF THE |
| | PLANS DID HAVE A RATED CEILING INTHE MECHANICAL ROOM, |
| | AS IT APPEARS THE DESIGNER IS TRYING BECAUSE OF THE |
| | FIRE DAMPER SHOWN PLEASE REVIEW 2010 FBC-B 1022.4 |
| | PENETRATIONS, THE FRESH AIR DUCT CAN NOT BE WITHIN THE |
| | STAIRWWELL, IT DOES NOT SERVE THE STAIRWELL. |
| | |
| | 5) 2ND REQUEST MAY OR MAY NOT BE A ISSUE DEPENDING ON |
| | THE REDESIGN. SHEET 710-A1-303 IS MISSING FIRE DAMPER, |
| | PLEASE REVIEW 2010 FBC-B 1022.4. 1022.5 EXIT ENCLOSURE |
| | VENTILATION SYSTEMS SHALL BE INDEPENDENT OF OTHER |
| | BUILDING VENTILATION SYSTEMS. |
| | |
| | 6) 2ND REQUEST. EAST STAIR TOWER SHEET 710-A1-203 |
| | PLEASE PROVIDE ADDITIONAL INFORMATION REQUIRED FOR |
| | SUSPENDED ACCENT CANOPY, 2010 FBC-B TABLE 803.9 |
| | INTERIOR WALL & CEILING FINISHES. |
| | |
| | 7)COMPLIED. |
| | |
| | 8) SEMI-COMPLIED 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 9) PRODUCT APPROVALS WERE SUBMITTED AT THIS TIME. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. CIRCLE TYPE OF GLAZING ,SIZE OF |
| | DOORS AND ASSOCIATED PRESSUES |
| | (B) WINDOWS CIRCLE TYPES OF GLAZING, SIZE OF GLASS, |
| | TYPE OF MULLIONS, TYPES OF CONNECTIONS USED AND |
| | PRESSURES |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, CIRCLE TYPES OF GLAZING, SIZE OF |
| | GLASS, TYPE OF MULLIONS, TYPES OF CONNECTIONS USED AND |
| | PRESSURES |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES CIRCLE WHICH |
| | SUBSYSTEM TO BE INSTALLED VARIUOS PRESSURES INDICATED |
| | |
| | 10) NEW COMMENT) PLEASE SEE DESCREPANCY BETWEEN THE |
| | ARCHITECTURAL SHEET710-A1-300 AND MECHANICAL SHEET |
| | 710-HC-103, THE MECHANICAL SHEET HAS THE THIRD FLOOR |
| | STAIR RUNNING DIRECTLY INTO THE MECHANICAL ROOM. PLEASE |
| | REVISE. |
| | |
| | 11) NEW COMMENT. IN THE FOLDER WE FIND VARIOUS SPECS, |
| | PLEASE REMOVE THE SPECS, THE PERMIT WILL NOT BE ISSUED |
| | SINCE THEY END UP BEING BATCHED STAMPED. WE DO NOT |
| | REVIEW SPECIFICATIONS!!!!!! PLEASE SEPERATE THE REVIEW |
| | COMMENTS INTO A SEPERATE FOLDER FROM THE PRODUCT |
| | APPROVALS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |