Plan Review Details - Permit 12080396
Plan Review Stops For Permit 12080396
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-08-13 Cont ID  
Sent By shill Date 2012-08-13 Time 13:25 Rev Time 0.00
Received By shill Date 2012-08-13 Time 13:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-13 Cont ID  
Sent By shill Date 2012-08-13 Time 12:13 Rev Time 0.00
Received By shill Date 2012-08-13 Time 12:13 Sent To  
Notes
2012-08-13 12:16:26****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. CITY OF WEST PALM BEACH IS IN THE 170MPH V(ULT) WIND
 ZONE, NOT 140MPH, FBC R 301.1..
  
 YOU MAY USE THE DESIGN PRESSURE CHART FROM THE 2007
 RESIDENTIAL CODE, 140MPH, AS IT EXCEEDS THE
 REQUIREMENTS (170MPH V(ULT) = 132MPH V(ASD), FBC
 RESIDENTIAL TABLE 301.2.1.3.
  
 WORST CASE FOR THIS JOB ARE -54.1PSF ZONE 5, -43.8PSF
 ZONE 4.
  
 PLEASE REVISE INSTALLATION SCHEDULE; -40PSF TOO LOW FOR
 THIS JOB.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-13 Cont ID  
Sent By shill Date 2012-08-13 Time 12:16 Rev Time  
Received By shill Date   Time   Sent To  
Notes
***NONE***