Plan Review Details - Permit 12080395
Plan Review Stops For Permit 12080395
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-10-30 Cont ID  
Sent By shill Date 2012-10-30 Time 11:53 Rev Time 0.00
Received By shill Date 2012-10-30 Time 11:53 Sent To  
Notes
2012-10-30 11:54:49****PROVISO****
 ****PROVIDE AT INSPECTION****
 ****REVISE PLAN AS NOTED****
 ****ISSUED AT OWNER/BUILDER'S RISK****
  
 ****REVISION REQUIRED SUBJECT TO FIELD INSPECTOR'S
 DISCRETION****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC 107.2.1, ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2. PLANS SPECIFY "STRAPS" - SEE FAC9N-3, PRODUCT
 APPROVAL REQUIRED FOR STRUCTURAL CONNECTORS, AND ALL
 ELEMENTS TO BE SPECIFIED TO SHOW RESISTANCE TO WIND
 LOADS FBC R 301.1, FBC 107.2.1. "STRAP" TO BE SPECIFIC
 TO A CONNECTOR WHICH CAN RESIST THE SPECIFIED DESIGN
 LOADS, PLEASE REVISE PLAN TO INCLUDE INFORMATION AND
 PROVIDE PRODUCT APPROVAL.
  
 3. THE PLAN IS CUT OFF ON THE RIGHT SIDE, PLEASE SUBMIT
 COMPLETE LEGIBLE PLANS, FBC 107.2.1.
  
 4. WALL FRAMING SPACING NOT INCLUDED IN PLAN (2X6
 BEARING WALL).
  
 5. RAFTER TIE IS NOTED ON THE PLAN, BUT NOT SHOWN
 GRAPHICALLY (SEC B-B), PROPOSED CONSTRUCTION NOT CLEAR
 FBC R 301.1, FBC 107.2.1.
  
 6. INCLUDE WIND DESIGN CRITERIA, FBC R 301.1. THIS
 SHOULD INCLUDE WIND SPEED AND EXPOSURE CLASSIFICATION.
 (170MPH EXPOSURE C).
  
 7. PROVIDE WINDOW PRODUCT APPROVAL IN FIELD. IF THIS IS
 NOT AN IMPACT PRODUCT, IMPACT PROTECTION (SHUTTER) WILL
 BE REQUIRED. IF A SHUTTER IS USED, PROVIDE A PRODUCT
 APPROVAL FOR THE SHUTTER AS WELL.
  
 SEPARATE PERMIT REQUIRED FOR ROOF (APPLICATION AND
 PRODUCT APPROVAL)
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-30 Cont ID  
Sent By shill Date 2012-08-30 Time 13:57 Rev Time 0.00
Received By shill Date 2012-08-30 Time 13:57 Sent To  
Notes
2012-08-30 14:34:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC 107.2.1, ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2. PLANS SPECIFY "STRAPS" - SEE FAC9N-3, PRODUCT
 APPROVAL REQUIRED FOR STRUCTURAL CONNECTORS, AND ALL
 ELEMENTS TO BE SPECIFIED TO SHOW RESISTANCE TO WIND
 LOADS FBC R 301.1, FBC 107.2.1. "STRAP" TO BE SPECIFIC
 TO A CONNECTOR WHICH CAN RESIST THE SPECIFIED DESIGN
 LOADS, PLEASE REVISE PLAN TO INCLUDE INFORMATION AND
 PROVIDE PRODUCT APPROVAL.
  
 3. THE PLAN IS CUT OFF ON THE RIGHT SIDE, PLEASE SUBMIT
 COMPLETE LEGIBLE PLANS, FBC 107.2.1.
  
 4. WALL FRAMING SPACING NOT INCLUDED IN PLAN (2X6
 BEARING WALL).
  
 5. RAFTER TIE IS NOTED ON THE PLAN, BUT NOT SHOWN
 GRAPHICALLY (SEC B-B), PROPOSED CONSTRUCTION NOT CLEAR
 FBC R 301.1, FBC 107.2.1.
  
 6. INCLUDE WIND DESIGN CRITERIA, FBC R 301.1. THIS
 SHOULD INCLUDE WIND SPEED AND EXPOSURE CLASSIFICATION.
  
 IF PLANS ARE NOT SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL LICENSED UNDER FS471 OR FS481 (ENGINEER OR
 ARCHITECT), PLEASE ADDRESS THE FOLLOWING:
  
 7. SEE FBC RESIDENTIAL 301.2.1.1, DESIGN IS TO BE IN
 ACCORDANCE WITH ONE OF THE METHODS LISTED. PLEASE
 SPECIFY AND REVISE PLAN TO INCLUDE DESIGN CRITERIA.
  
 IF USING A PRESCRIPTIVE METHOD, IT WOULD BE HELPFUL TO
 PLAN REVIEW TO INDICATE ON WHICH PAGES THESE DETAILS
 CAN BE LOCATED (ICC 600, AF & PA).
  
 IF USING ASCE 7-10, CALCULATINS MAY BE REQUIRED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-30 Cont ID  
Sent By shill Date 2012-08-30 Time 14:34 Rev Time 0.00
Received By shill Date 2012-08-30 Time 14:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-08-16 Cont ID  
Sent By mdekle Date 2012-08-16 Time   Rev Time 0.00
Received By mdekle Date 2012-08-14 Time 09:14 Sent To B
Notes
2012-08-14 06:50:31SENT TO ZONING


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved