Plan Review Details - Permit 12080390
Plan Review Stops For Permit 12080390
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-10-11 Cont ID  
Sent By jwitmer Date 2012-10-11 Time 14:36 Rev Time 0.00
Received By jwitmer Date 2012-10-11 Time 14:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-09-19 Cont ID  
Sent By jwitmer Date 2012-09-19 Time 10:02 Rev Time 0.00
Received By jwitmer Date 2012-09-18 Time 16:01 Sent To  
Notes
2012-09-18 16:56:46BUILDING PLAN REVIEW
 PERMIT: 12080390
 ADD: 210 S OLIVE AVE
 CONT: CHARLTON BROTHERS
 TEL: (561)748-8753
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 SEPT. 18/ 2012
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) SECOND REQUEST, RESPONCE NOTED. SHEET A3 THE NEW
 RESTROOM NEEDS TO HAVE 5'-0" CLEAR BETWEEN THE WATER
 CLOSET AND LAVATORY PLEASE REVIEW 2010 ACCESSIBILITY
 CODE
 FIGURE 604.8.1.6. FLORIDA SPECIFIC, GRAY BOX. PLEASE
 REVIEW THESE SECTIONS OF THE 2010 ACCESSIBILITY CODE:
 213.2 TOILET ROOMS; (NOT COMPARTMENTS)
  
 213.3 PLUMBING FIXTURES AND ACCESSORIES. PLUMBING
 FIXTURES AND ACCESSORIES PROVIDED IN A TOLIET ROOM OR
 BATHING ROOM REQUIRED TO COMPLY WITH 213.2 (TOILET
 ROOMS) SHALL COMPLY WITH 213.3 (PLUMBING FIXTURES &
 ACCESSORIES).
  
 213.3.2 WATER CLOSETS. WHERE WATER CLOSETS ARE
 PROVIDED, AT LEAST ONE SHALL COMPLY WITH 604.
  
 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE
 WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER
 CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY
 NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE
 ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT
 OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER
 FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE
 REQUIRED WATER CLOSET CLEARANCE
  
 FIGURE 604.8.1.6. IS AN ILLUSTRATION SHOWING THE
 REQUIRED CLEAR FLOOR SPACE, TRUE IT DOES SAY TOILET
 COMPARTMENT BUT 213.3 .2 THIS IS SPECIFIC TO WHAT CAN
 BE IN THE REQUIRED CLEAR FLOOR SPACE FOR A TOLIET ROOM.
  
 PLEASE NOTE UNDER THE 2007 ACCESSIBILITY CODE WE WOULD
 HAVE AGREED THAT THE CLEAR SPACE BETWEEN THE LAV AND
 WATER CLOSET WAS NOT REQUIRED FOR TOLIET ROOMS, UNDER
 THE 2010 ACCESSIBILITY CODE IT IS REQUIRED !!!
  
 WE HAVE TAKEN CLASSES ON THE 2010 ACCESSIBILITY CODE
 AND HAVE ADDITIONAL PICTURES OF ACCESSIBLE TOLIET ROOMS
 THAT ARE ACCEPTABLE THAT ARE NOT DEPICTED IN THE
 FLORIDA ACCESSIBLILTY CODE BUT THE LANGUAGE IS THERE,
 PLEASE SEE WEBSITE:
 HTTP://WWW.ADA.GOV/2010ADASTANDARDS_INDEX.HTM SEE
 GUIDEANCE ON THE ADA STANDARDS FOR ACCESSIBLE DESIN .
  
 3) 2ND REQUEST, RESPONCE NOTED. 2010 EXST BLDG CODE
 703.1 SCOPE. THE REQUIREMENTS OF THIS SECTION ARE
 LIMITED TO WORK AREAS IN WHICH LEVEL 2 ALTERATIONS ARE
 BEING PERFORMED, AND SHALL APPLY BEYOND THE WORK AREA
 WHERE SPECIFIED.
 2010 EXISTING BUILDING CODE 705.91 MINIUMUM
 REQUIREMENTS, HANDRAILS ARE REQUIRED ON BOTH SIDES.
  
 4A) 2ND REQUEST , RESPONCE NOTED. CONTRACTOR TO PROVIDE
 PRODUCT APPROVALFOR DOOR # 4. SHEET A4 INDICATES IN THE
 DOOR SCHEDULE DOOR # 4 TO BE REPLACED, IF DOOR AND
 FRAME ARE TO BE REPLACED THEN A PRODUCT APPROVAL WILL
 BE REQUIRED FOR THE OPENING. OPENING PROTECTIVES
 1609.6/ 1715.5.3. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 4B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-29 Cont ID  
Sent By jwitmer Date 2012-08-29 Time 15:21 Rev Time 0.00
Received By jwitmer Date 2012-08-29 Time 13:41 Sent To  
Notes
2012-08-29 15:40:51BUILDING PLAN REVIEW
 PERMIT: 12080390
 ADD: 210 S OLIVE AVE
 CONT: CHARLTON BROTHERS
 TEL: (561)748-8753
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE UPDATE THE COVER SHEET TO THE 2010 FBC, IT
 WAS ADOPTED MARCH 15, 2012 STATEWIDE. SHEET A.3 ALSO
 MAKES REFERENCE TO THE 2007 CODE AT THE REAR OF THE
 BUILDING AT THE CLEAR WIDTH (DOOR) STATEMENT.
  
 2) SHEET A3 THE NEW RESTROOM NEEDS TO HAVE 5'-0" CLEAR
 BETWEEN THE WATER CLOSET AND LAVATORY PLEASE REVIEW
 2010 ACCESSIBILITY CODE FIGURE 604.8.1.6. FLORIDA
 SPECIFIC, GRAY BOX.
  
 3) 2010 EXISTING BUILDING CODE 705.91 MINIUMUM
 REQUIREMENTS, HANDRAILS ARE REQUIRED ON BOTH SIDES.
  
 4) SHEET A4 INDICATES IN THE DOOR SCHEDULE DOOR # 4 TO
 BE REPLACED, IF DOOR AND FRAME ARE TO BE REPLACED THEN
 A PRODUCT APPROVAL WILL BE REQUIRED FOR THE OPENING.
 OPENING PROTECTIVES 1609.6/ 1715.5.3.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-09-25 Cont ID  
Sent By rlecky Date 2012-09-25 Time 16:14 Rev Time 0.00
Received By rlecky Date 2012-09-25 Time 14:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-08-17 Cont ID  
Sent By rlecky Date 2012-08-17 Time 16:41 Rev Time 0.00
Received By rlecky Date 2012-08-17 Time 16:23 Sent To  
Notes
2012-08-17 16:42:4012080390
 210 S. OLIVE AVENUE
 COMMERCIAL INTERIOR REMODEL
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION:
  
 VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING
 ARE SIX OR LESS AND GROUPED IN ONE LOCATION.
 NEC 230.2, 230.71, 230.72
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 NEW SERVICE AND SWITCH GEAR. NEC 110.9, 110.10
 ELECTRICAL PANELS MAY NOT BE LOCATED IN STORAGE ROOMS.
 PROVIDE A DESIGNATED LOCATION FOR THE PANEL BOARDS
 WHICH REMAINS CLEAR OF OBSTRUCTION AND STORAGE AT ALL
 TIMES. NEC 110.26, 240.24
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-10-15 Cont ID  
Sent By wjolin Date 2012-10-15 Time 10:29 Rev Time 0.00
Received By wjolin Date 2012-10-15 Time 10:14 Sent To  
Notes
2012-10-15 10:15:37210 SOUTH OLIVE AVENUE
 PERMIT #12080390
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: GUARDS, AT LEAST 42-INCHES TALL, SHALL
 BE PROVIDED ALONG A MEANS OF EGRESS (STAIRS, MEZZANINE,
 ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN
 GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER
 SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR
 OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT
 OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH
 DIAMETER SPHERE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-09-27 Cont ID  
Sent By wjolin Date 2012-09-27 Time 10:28 Rev Time 0.00
Received By wjolin Date 2012-09-27 Time 10:17 Sent To  
Notes
2012-09-27 10:28:33210 SOUTH OLIVE AVENUE
 PERMIT #12080390
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: GUARDS, AT LEAST 42-INCHES TALL, SHALL
 BE PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS
 (STAIRS, MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE
 THE FLOOR. OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A
 4-INCH DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE
 TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND
 BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE
 PASSAGE OF A 6-INCH DIAMETER SPHERE.
  
 REPEAT COMMENT: PROVIDE HANDRAILS ON BOTH SIDES OF THE
 STAIR.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-08-26 Cont ID  
Sent By wjolin Date 2012-08-26 Time 13:45 Rev Time 0.00
Received By wjolin Date 2012-08-26 Time 13:08 Sent To  
Notes
2012-08-26 13:45:31210 SOUTH OLIVE AVENUE
 PERMIT #12080390
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION INDICATES THE ADDRESS IS 210
 WHILE THE PLANS INDICATE AN ADDRESS OF 208 S OLIVE
 AVENUE. PLEASE CONFIRM THE CORRECT ADDRESS.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING
 OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE
 EXTINGUISHER COMPANY.
  
 STRUCTURES WITH LIGHT FRAME FLOOR CONSTRUCTION SHALL BE
 IDENTIFIED WITH A SIGN AFFIXED TO THE BUILDING. THE
 SIGN SHALL FEATURE A MALTESE CROSS 8-INCHES WIDE AND
 8-INCHES TALL AND BE OF A BRIGHT RED REFLECTIVE COLOR
 AND BEAR THE LETTER "F" DESIGNATION PER FLORIDA STATUTE
 633.027 AND FLORIDA ADMINISTRATIVE CODE 69A-60.0081.
  
 GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT
 THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE,
 ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN
 GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER
 SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR
 OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT
 OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH
 DIAMETER SPHERE.
  
 PROVIDE HANDRAILS ON BOTH SIDES OF THE STAIR.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-10-16 Cont ID  
Sent By lwagner Date 2012-10-16 Time 15:27 Rev Time 0.00
Received By lwagner Date 2012-10-04 Time 08:24 Sent To  
Notes
2012-10-05 08:24:37B--19
 SUBMITTED BUILDING REVIEW RESPONCES EARLY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-10-16 Cont ID  
Sent By lwagner Date 2012-10-16 Time 15:27 Rev Time 0.00
Received By lwagner Date 2012-09-14 Time 10:51 Sent To  
Notes
2012-09-14 10:51:14B19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-29 Cont ID  
Sent By jwitmer Date 2012-08-29 Time 15:41 Rev Time 0.00
Received By jwitmer Date 2012-08-13 Time 07:37 Sent To  
Notes
2012-08-14 07:37:40B07

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2012-10-11 Cont ID  
Sent By jwitmer Date 2012-10-11 Time 14:37 Rev Time 0.00
Received By jwitmer Date 2012-10-11 Time 14:37 Sent To  
Notes
2012-10-11 14:38:37MECHANICAL CONTRACTOR WILL PULL SEPERATE PERMIT, AND
 PLANS, NOT PART OF THIS REVIEW. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2012-08-21 Cont ID  
Sent By hmoser Date 2012-08-21 Time 14:47 Rev Time 0.00
Received By hmoser Date 2012-08-21 Time 14:22 Sent To  
Notes
2012-08-21 14:47:05NOTE ON PAGE A.6 OF PLANS AIR CONDITIONING
 CONTRACTOR IS GOING TO SUPPLY HIS OWN APPLICATION AND
 PLANS
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2012-10-16 Cont ID  
Sent By lwagner Date 2012-10-16 Time 15:26 Rev Time 0.00
Received By lwagner Date 2012-10-16 Time 13:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2012-09-17 Cont ID  
Sent By lwagner Date 2012-09-17 Time 14:05 Rev Time 0.00
Received By lwagner Date 2012-09-17 Time 14:05 Sent To  
Notes
2012-09-17 13:47:02FBC ACCESSIBILITY 2010
 FBC PLUMBING 2010 REVIEW #2
 DENIED:
  
 COMMENTS NOTED, HOWEVER, PLEASE SEE SCOPING 213.3:
 PLUMBING FIXTURES AND ACCESSORIES. PLUMBING FIXTURES
 AND ACCESSORIES PROVIDED IN A TOILET ROOM OR BATHING
 ROOM REQUIRED TO COMPLY WITH 213.2 SHALL COMPLY WITH
 213.3.
  
 213.3.2 WATER CLOSETS. WHERE WATER CLOSETS ARE
 PROVIDED, AT LEAST ONE SHALL COMPLY WITH 604.
  
 FROM REVIEW #1:
  
 1. SHEETS A.3 AND A.4 (1) SHOW AN NEW RESTROOM THAT
 DOES NOT COMPLY WITH FBC ACCESSIBILITY 2010.
 THE RESTROOM WILL BE REQUIRED TO BE A MINIMUM OF 7'-1"
 WIDE TO ACHIEVE THE REQUIRED 5' CLEAR SPACE FOR THE
 WATER CLOSET. FBC ACCESSIBILITY CODE 2010 604.3.1
 THE LAVATORY WILL NOT BE PERMITTED IN THE 5' SPACE. FBC
 ACCESSIBILITY CODE 2010 604.3.2
 NOTE - OTHER CONFIGURATIONS ARE POSSIBLE AS LONG AS THE
 WATER CLOSET HAS A 5' CLEAR SPACE WITH THE LAVATORY IN
 THE SAME ROOM AND NOT IN THE CLEAR SPACE.
  
 2.
  
 3. SHEET A.6 THE PLUMBING (SANITARY) RISER DIAGRAM DOES
 NOT SHOW
 THE DRINKING FOUNTAINS.
  
 4.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-08-15 Cont ID  
Sent By lwagner Date 2012-08-15 Time 13:40 Rev Time 0.00
Received By lwagner Date 2012-08-15 Time 12:32 Sent To  
Notes
2012-08-15 13:17:35FBC ACCESSIBILITY 2010
 FBC PLUMBING 2010 REVIEW #1
 DENIED:
  
 1. SHEETS A.3 AND A.4 (1) SHOW AN NEW RESTROOM THAT
 DOES NOT COMPLY WITH FBC ACCESSIBILITY 2010.
 THE RESTROOM WILL BE REQUIRED TO BE A MINIMUM OF 7'-1"
 WIDE TO ACHIEVE THE REQUIRED 5' CLEAR SPACE FOR THE
 WATER CLOSET. FBC ACCESSIBILITY CODE 2010 604.3.1
 THE LAVATORY WILL NOT BE PERMITTED IN THE 5' SPACE. FBC
 ACCESSIBILITY CODE 2010 604.3.2
 NOTE - OTHER CONFIGURATIONS ARE POSSIBLE AS LONG AS THE
 WATER CLOSET HAS A 5' CLEAR SPACE WITH THE LAVATORY IN
 THE SAME ROOM AND NOT IN THE CLEAR SPACE.
  
 2. BUSINESS OCCUPANCIES WITH OVER 15 OCCUPANTS REQUIRE
 DRINKING FOUNTAINS. FBC PLUMBING TABLE 403.1(E & F)
 SHEET A-1 SHOWS A FUTURE DRINKING FOUNTAIN. THE
 REQUIRED DRINKING FOUNTAIN SHALL COMPLY WITH FBC
 ACCESSIBILITY 2010.
 FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 3. SHEET A.6 THE PLUMBING RISER DIAGRAM DOES NOT SHOW
 THE DRINKING FOUNTAINS.
  
 4. PLEASE INCLUDE THE WATER PIPE IN THE DRAWING.
 FBC 2010 LOCAL AMENDMENTS 107.3.5.1.3 PLUMBING (3)
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2012-09-25 Cont ID  
Sent By AV/AA Date 2012-09-25 Time 10:30 Rev Time 0.00
Received By aaponte Date 2012-09-25 Time 10:30 Sent To  
Notes
***NONE***