Plan Review Details - Permit 12080323
Plan Review Stops For Permit 12080323
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-09-26 Cont ID  
Sent By T MOORE Date 2012-09-26 Time 09:55 Rev Time 0.00
Received By tmoore Date 2012-09-26 Time 09:47 Sent To  
Notes
2012-09-26 09:54:55WE HAVE ELECTRICAL PERMIT #12080965 TO SAFE OFF PHASES.
 CONTR. WILL BE RESPONSIBLE TO HAVE ELECTRICAL
 INSPECTIONS ON SAFING PHASES BEFORE DEMOLITION TAKES
 PLACE. PLUMBING PERMIT #12090494 FOR CAPPING SEWER
 LATERALS HAS BEEN PULLED. CONTR. WILL BE RESPONSIBLE TO
 HAVE LATERALS CAPPED AS WORK PROGRESSES. PHASE 1
 PARKING GARAGE MAY STILL HAVE LATERAL. HAVE OTHER
 NECESSARY RELEASES, SUCH AS ASBESTOS, GAS, RODENT.
 BACK TO BOX C-20 TO CONTINUE REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-13 Cont ID  
Sent By tmoore Date 2012-08-13 Time 09:53 Rev Time 0.00
Received By tmoore Date 2012-08-13 Time 09:18 Sent To  
Notes
2012-08-13 09:53:06SPOKE WITH KRYSTAL. ALTHOUGH THE APPLICATION IS FOR
 TOTAL DEMOLITION, THE PARKING GARAGE IN PHASE ONE WILL
 BE FIRST TO GO. REALIZING THAT PENNY'S WILL CONTINUE TO
 NEED POWER, AN ELECTRICAL PERMIT THAT WILL SAFE EACH
 PHASE OF DEMOLITION WILL NEED TO BE PULLED. ELECTRICAL
 INSPECTIONS CAN THEN SUFFICE FOR RELEASES OF PHASES.
 PARKING GARAGE STILL LIVE ACCORDING TO KRYSTAL.
 A GAS RELEASE FOR THE ENTIRE PROJECT OR HOW PENNY'S
 WILL REMAIN LIVE FOR DEMOLITION SHOULD BE RECEIVED
 PRIOR TO ANY PHASE RELEASE.
 WATER METER RELEASES, THERE WILL BE MANY WATER METERS
 ON THIS JOB THAT NEED TO BE PULLED OR KEPT. THIS CAN BE
 ACCOMPLISHED BY THE PLUMBING CONTRACTOR YET SIGNED ON.
 FIRE SPRINKLERS, NEED TO BE ADDRESSED. HOW WILL PENNY'S
 REMAIN PROTECTED? THIS MAY NEED FIRE TO SIGN OFF.
 NO POLLUTION PREVENTION PLAN IN APPLICATION. ENG. WILL
 NEED THAT.
 PLAN OUT FRONT UNDER "B".

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-08-29 Cont ID  
Sent By rlecky Date 2012-08-24 Time 09:05 Rev Time 0.00
Received By rlecky Date 2012-08-24 Time 09:02 Sent To ENG
Notes
2012-08-29 15:48:29SEE ELECTRIC DEMO PERMIT # 12080965

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2012-10-05 Cont ID  
Sent By lmartine Date 2012-10-05 Time 11:10 Rev Time 0.00
Received By lmartine Date 2012-10-05 Time 11:10 Sent To  
Notes
2012-10-05 11:10:48RECIEVED SURITY, OK TO RELEASE PERMIT, BRIAN

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2012-09-20 Cont ID  
Sent By MGONZALE Date 2012-09-20 Time   Rev Time 0.25
Received By mgonzale Date 2012-09-20 Time   Sent To  
Notes
2012-09-20 15:34:30SURETY REQUIRED. SEE PRIOR COMMENT.
  
 CONTACT:
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2012-08-28 Cont ID  
Sent By rlecky Date 2012-08-29 Time 15:47 Rev Time 1.00
Received By mgonzale Date 2012-08-28 Time   Sent To  
Notes
2012-08-28 12:31:54REQUIRES ENGINEERING SERVICES EROSION CONTROL & LAND
 STABILIZATION BOND (ORD. 4060-07) *
 GO TO
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 DOWNLOAD
 PERFORMANCE BOND - PUBLIC IMPROVEMENTS
  
 CONTACT:
 BRIAN R MOREE
 ENGINEERING SERVICES CONSTRUCTION SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1098
 FAX: 494-1118
 E-MAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-09-28 Cont ID  
Sent By W JOLIN Date 2012-09-28 Time 10:22 Rev Time 0.00
Received By wjolin Date 2012-09-28 Time 09:29 Sent To  
Notes
2012-09-28 10:17:091801 PALM BEACH LAKES BOULEVARD
 DEMOLITION PERMIT
 PERMIT #12080323
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 THE TEMPORARY CONSTRUCTION TRAILERS DO NOT APPEAR TO BE
 SEPARATED FROM EACH OTHER ADEQUATELY (PER NFPA 241);
 THEREFORE, THE TRAILERS NEED TO BE PROTECTED BY AN
 AUTOMATIC SPRINKLER SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-08-30 Cont ID  
Sent By wjolin Date 2012-08-30 Time 13:39 Rev Time 0.00
Received By wjolin Date 2012-08-30 Time 13:04 Sent To Z
Notes
2012-08-30 13:38:431801 PALM BEACH LAKES BOULEVARD
 PERMIT #12080323
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INDICATE THE QUANTITY, CONSTRUCTION TYPE AND LOCATION
 OF ANY TEMPORARY OFFICES, TRAILERS OR SHEDS. SEPARATION
 DISTANCES BETWEEN BUILDINGS UNDER CONSTRUCTION AND
 CONSTRUCTION-RELATED STRUCTURES, SUCH AS TEMPORARY
 OFFICES, TRAILERS, SHEDS, AND OTHER FACILITIES FOR THE
 STORAGE OF TOOLS AND MATERIALS HAVING COMBUSTIBLE
 CONSTRUCTION OR CONTENTS, SHALL BE IN ACCORDANCE WITH
 TABLE 4.2.1. (NFPA 241).
  
 PROVIDE A PHASED FIRE PROTECTION UTILITY PLAN
 INDICATING THE UNDERGROUND FIRE MAINS, FIRE HYDRANTS
 AND FIRE SPRINKLER SYSTEMS TO BE AFFECTED DURING EACH
 STAGE OF PHASING.
  
 A SUITABLE LOCATION AT THE SITE SHALL BE DESIGNATED AS
 A COMMAND POST AND PROVIDED WITH PLANS, EMERGENCY
 INFORMATION, KEYS, COMMUNICATIONS, AND EQUIPMENT, AS
 NEEDED.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241 - STANDARD FOR
 SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 TRASH CHUTES, WHERE PROVIDED, SHALL COMPLY WITH THE
 FOLLOWING: A TRASH CHUTE SAFETY PLAN SHALL BE SUBMITTED
 TO AND APPROVED BY THE AUTHORITY HAVING
 JURISDICTION.TRASH CHUTES USED ON THE EXTERIOR OF A
 BUILDING SHALL BE OF NONCOMBUSTIBLE CONSTRUCTION, OR
 PROTECTED WITH AUTOMATIC SPRINKLERS AND A LISTED FIRE
 HOSE.
  
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 ***FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.***
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 50 FEET.
  
 FIRE DEPARTMENT ACCESS ROADS/LANES SHALL MAINTAIN AN
 UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN
 UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES. FIRE HYDRANTS SHALL BE MAINTAINED WITH
 CLEARANCES OF 7?-6? TO THE FRONT AND SIDES AND 4? TO
 THE BACKSIDE.
  
 RESPONSIBILITY FOR HOT WORK OPERATIONS AND FIRE
 PREVENTION PRECAUTIONS, INCLUDING PERMITS AND FIRE
 WATCHES, SHALL BE IN ACCORDANCE WITH NFPA 51B, STANDARD
 FOR FIRE PREVENTION DURING WELDING, CUTTING, AND OTHER
 HOT WORK.
  
 PER SECTION 7.1 (NFPA 241) AN OVERALL CONSTRUCTION OR
 DEMOLITION FIRE SAFETY PROGRAM SHALL BE DEVELOPED.
 ESSENTIAL ITEMS TO BE EMPHASIZED INCLUDE THE FOLLOWING:
 (1) GOOD HOUSEKEEPING (2) ON-SITE SECURITY (3)
 INSTALLATION OF NEW FIRE PROTECTION SYSTEMS AS
 CONSTRUCTION PROGRESSES (4) PRESERVATION OF EXISTING
 SYSTEMS DURING DEMOLITION (5) DEVELOPMENT OF A PREFIRE
 PLAN WITH THE LOCAL FIRE DEPARTMENT (6) RAPID
 COMMUNICATION (7) CONSIDERATION OF SPECIAL HAZARDS
 RESULTING FROM PREVIOUS OCCUPANCIES (8) PROTECTION OF
 EXISTING STRUCTURES AND EQUIPMENT FROM EXPOSURE FIRES
 RESULTING FROM CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS
  
 THE OWNER SHALL DESIGNATE A PERSON WHO SHALL BE
 RESPONSIBLE FOR THE FIRE PREVENTION PROGRAM AND WHO
 SHALL ENSURE THAT IT IS CARRIED OUT TO COMPLETION. THE
 FIRE PREVENTION PROGRAM MANAGER SHALL HAVE THE
 AUTHORITY TO ENFORCE THE PROVISIONS OF THIS AND OTHER
 APPLICABLE FIRE PROTECTION STANDARDS. THE FIRE
 PREVENTION PROGRAM MANAGER SHALL HAVE KNOWLEDGE OF THE
 APPLICABLE FIRE PROTECTION STANDARDS, AVAILABLE FIRE
 PROTECTION SYSTEMS, AND FIRE INSPECTION PROCEDURES.
 INSPECTION RECORDS SHALL BE AVAILABLE FOR REVIEW BY THE
 AUTHORITY HAVING JURISDICTION. WHERE GUARD SERVICE IS
 PROVIDED, THE FIRE PREVENTION PROGRAM MANAGER SHALL BE
 RESPONSIBLE FOR THE GUARD SERVICE.
  
 FREE ACCESS FROM THE STREET TO FIRE HYDRANTS AND TO
 OUTSIDE CONNECTIONS FOR STANDPIPES, SPRINKLERS, OR
 OTHER FIRE EXTINGUISHING EQUIPMENT, WHETHER PERMANENT
 OR TEMPORARY, SHALL BE PROVIDED AND MAINTAINED AT ALL
 TIMES. PROTECTIVE PEDESTRIAN WALKWAYS SHALL NOT BE
 CONSTRUCTED SO THAT THEY IMPEDE ACCESS TO HYDRANTS. NO
 MATERIAL OR CONSTRUCTION SHALL INTERFERE WITH ACCESS TO
 HYDRANTS, SIAMESE CONNECTIONS, OR FIRE EXTINGUISHING
 EQUIPMENT.
  
 VERTICAL AND HORIZONTAL CUTOFFS SHALL BE RETAINED UNTIL
 RAZING OPERATIONS NECESSITATE THEIR REMOVAL AS
 PERMITTED BY THE AUTHORITY HAVING JURISDICTION. FIRE
 DOORS SHALL BE CLOSED AT THE END OF EACH WORKING DAY.
  
 THE OPERATION OF SPRINKLER CONTROL VALVES SHALL BE
 PERMITTED ONLY BY PROPERLY AUTHORIZED PERSONNEL AND
 SHALL BE ACCOMPANIED BY THE NOTIFICATION OF DESIGNATED
 PARTIES. WHERE THE SPRINKLER PROTECTION IS REGULARLY
 TURNED OFF AND ON TO FACILITATE REMOVAL AND CAPPING OF
 SEGMENTS, THE SPRINKLER CONTROL VALVES SHALL BE CHECKED
 AT THE END OF EACH WORK SHIFT TO ASCERTAIN THAT
 PROTECTION IS IN SERVICE. STANDPIPES SHALL BE
 MAINTAINED IN CONFORMITY WITH THE PROGRESS OF
 DEMOLITION ACTIVITY IN SUCH A MANNER THAT THEY ARE
 ALWAYS READY FOR FIRE DEPARTMENT USE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-28 Cont ID  
Sent By wjolin Date 2012-09-28 Time 10:22 Rev Time 0.00
Received By wjolin Date 2012-09-19 Time 08:19 Sent To  
Notes
2012-09-20 08:27:26C20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-09-05 Cont ID  
Sent By eschneid Date 2012-09-05 Time 12:03 Rev Time 0.00
Received By eschneid Date 2012-08-10 Time   Sent To  
Notes
2012-08-24 09:02:16C20

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-08-29 Cont ID  
Sent By lwagner Date 2012-08-29 Time 10:33 Rev Time 0.00
Received By lwagner Date 2012-08-29 Time 10:03 Sent To  
Notes
2012-08-29 10:33:06****PROVISO****
 FOR SEWER AND DOMESTIC WATER CAP OFF A SEPARATE
 PLUMBING PERMIT, APPLICATION, KEY PLAN, AND REVIEW
 REQUIRED.

Review Stop Z ZONING
Rev No 2 Status P Date 2012-09-21 Cont ID  
Sent By ESCHNEID Date 2012-09-21 Time 14:10 Rev Time 0.25
Received By eschneid Date 2012-09-21 Time 14:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2012-09-05 Cont ID  
Sent By eschneid Date 2012-09-05 Time 11:23 Rev Time 0.75
Received By eschneid Date 2012-09-05 Time 11:23 Sent To  
Notes
2012-09-05 11:56:12FAILED
  
 PROVIDE WRITTEN RESPONSES.
  
 1) THE SCOPE OF WORK INCLUDES FOUR SEPARATE PARCELS.
 PLEASE PROVIDE VERIFICATION FROM ROBERT BROWN,
 ASSISTANT BUILDING OFFICIAL, THAT A SEPARATE PERMIT
 APPLICATION IS NOT REQUIRED FOR EACH PARCEL.
  
 2) THE PLANS FOR THE PHASE I SHOW ONLY A PORTION OF THE
 PARKING GARAGE BEING DEMOLISHED. PLEASE EXLAIN WHY THE
 ENTIRE GARAGE IS NOT BEING REMOVED.
  
 3) WHY IS THE SMALL BANK BUILDING NOT BEING REMOVED?
  
 4) A LAND STABALIZATION BOND SHALL BE PROVIDED IN
 ACCORDANCE WITH SECTION 94-450(F).
  
 5) SERVICE TO THE CHASE BANK PARCEL MAY NOT BE CUT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.