| 2012-08-24 18:03:12 | BUILDING PLAN REVIEW |
| | PERMIT: 12080314 |
| | ADD: 429 25TH ST |
| | CONT: TO BE DETERMINED |
| | TEL: (202) 375-4753 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | DESIGNER OF RECORD: RAFAEL A RODRIGUEZ AR0016608 |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET SP-1 INDICATES THE EXISTING GARAGE TO BE |
| | STORAGE OCCUPANCY, PLEASE REVIEW 2010 FBC-B 406.1, |
| | CLASSIFICATION. PRIVATE GARAGES ARE CONSIDERED GROUP U |
| | OCCUPANCIES. PLEASE SEE THE ALLOWABLE AREA INCREASE ( |
| | FBC-B 406.1.2) TO 3,000 SQ FT AND REQUIREMENTS FOR |
| | OPENING PROTECTIVES FOR MIXED USE BUILDINGS, SEE |
| | FBC-B TABLE 715.4 FOR ALL OPENINGS GARAGE DOOR |
| | (OVERHEAD) AS WELL AS WINDOWS AND SWING DOORS (DOOR 03) |
| | INTO MERCANTILE OCCUPANCY. PLEASE ALSO REVIEW |
| | SECTION 406.1.4 FOR SEPERATION REQUIREMENTS TO THE |
| | RESIDENTIAL UNITS ABOVE. |
| | THE LIMITATIONS TO PRIVATE OR PLEASURE-TYPE MOTOR |
| | VEHICLES PREVENT COMMERCIAL MOTOR VEHICLES AND THEIR |
| | INCREASED HAZARDS FROM BEING LOCATED IN OVERSIZED |
| | PRIVATE GARAGES, WILL THE PAKING SPACES BE USED FOR |
| | COMMERCIAL OR PRIVATE USE? |
| | |
| | 2) 2010 FBC-B 713.3 FIRE-RESISTANCE-RATED WALLS. |
| | PENETRATIONS INTO OR THROUGH FIRE WALLS, FIRE BARRIERS, |
| | SMOKE BARRIER WALLS AND FIRE PARTITIONS SHALL COMPLY |
| | WITH SECTIONS 713.3.1 THROUGH 713.3.3. PLEASE PROVIDE |
| | SPECIFICATIONS FOR PENETRATIONS THROUGH BOTH THE |
| | HORIZONTAL OCCUPANCY FIRE RATED CEILING AND VERTICAL |
| | FIRE RATED |
| | OCCUPANCY FIRE RATED WALL. |
| | |
| | 3) SHEET A1, A2 & A5 THE RIGHT SIDE ELEVATION INDICATE |
| | THE USE OF ONLY ONE (EXTERIOR) STAIR WITH MULTIPLE DOOR |
| | AND WINDOW OPENINGS WITHIN TEN FEET OF THE STAIR & |
| | LANDING, PLEASE REVIEW SECTION 2010 FBC-B 1026.6 AND |
| | FIGURE 1023.1 2007 FBC-B COMMENTARY FOR AREAS |
| | RESTRICTION OF NO WINDOWS AND AREAS WHERE 3/4 HOUR |
| | OPENING PROTECTIVES CAN OCCUR. |
| | |
| | 4) SHEET A1 1ST FLOOR FRONT WINDOWS THAT FACE 25TH |
| | STREET, WINDOW TYPE "A" FIVE UNITS WITH A STRUCTURAL |
| | MULLION 6"X2"X3/8" STRUCTURAL TUBE STEEL, ALSO SHOWN ON |
| | SHEET S-1 COLOUMN HEADING SC-2 HSS 6X2X3/8 STEEL TUBE |
| | THE DETAIL INDICATES TTHE USE OF (2) 5/8"X9" J-BOLTS |
| | ASSUMED FOR THE BOTTOM STEEL PLATE, UNDER THE HEADING |
| | "REMARKS" IT INDICATES WEDGE ANCHORS ARE ACCEPTABLE |
| | WITH NO MINIMUM DIMENSIONS REQUIRED FOR THE WEDGE |
| | ANCHOR. THE STRUCTURAL STEEL TUBES ARE TO BE CONSIDERED |
| | AS PART OF THE (MWFRS) MAIN WIND FORCE RESISTING SYSTEM |
| | 1609.6.4.DESIGN PROCEDURES, NOT ONLY DO THESE COLUMNS |
| | PROVIDE STRENGHT FOR THE BEAM ABOVE WHERE BLOCK WAS |
| | REMOVED, AND A CONTINIOUS LOAD PATH (MWFRS), BUT THEY |
| | WILL PROVIDE A STRUCTURAL ELEMENT FOR THE WINDOWS AND |
| | DOORS TO ANCHOR TO SECTION 1715.5.4.1 ANCHORING |
| | REQUIREMENTS- WINDOWS AND DOORS. |
| | |
| | 5) SHEET A1 INDICATES A NEW PORTION OF ROOFING THAT |
| | EXTENDS OUT PAST THE PROPERTY LINE AS INDICATED ON THE |
| | SITE PLAN. SHEET A5 WHEN SCALED IS APPROXIMATELY |
| | 9'-0" FROM GRADE TO THE BOTTOM OF THE ROOF DECK OR |
| | EYEBROW, PLEASE INDICATE COMPLIANCE WITH SECTION |
| | 3202.3.2 IT APPEARS THAT A EXISTING NON-COMPLIANT |
| | ELEMENT IS BEING EXSPANDED? |
| | |
| | 6) SHEET A1 DOOR #2 INDICATES THE ACCESSIBLE PATH BEING |
| | 48 INCHES WIDE BUT IS REDUCED TO ONLY 42 INCHES AT RAMP |
| | AND THE UPPER LANDING. PLEASE REVIEW |
| | MANEUVERING CLEARENCES AT DOORS ACCESSIBILITY CODE |
| | FIGURE 404.2.4.1 (H) REQUIRES A 48 INCHES CLEAR. |
| | |
| | 7) SHEET A1 EXISTING TOLIET ROOM AND DOOR # 05 ON SHEET |
| | 7 THE DOOR SCHEDULE THIS ROOM IS LABELED A UNISEX |
| | RESTROOM, IS A TERM FOUND IN THE PLUMBING CODE FOR |
| | A SINGLE RESTROOM TO BE USED BY BOTH SEXES THAT IS AN |
| | ACCESSIBLE RESTROOM, THIS RESTROOM IS NOT ACCESSIBLE |
| | SEE ACCESSIBLITY CODE FIGURE 604.8.1.6. |
| | |
| | PLEASE PROVIDE A CONTRACT BREAKDOWN FOR FIRST FLOOR |
| | VALUE, CONTRACT VALUE ON PERMIT APPLICATION INDICATES A |
| | WORK VALUE OF $45, 000.00 THIS AMOUNT OF MONEY SEES LOW |
| | FOR THE AMOUNT OF WORK BEING COMPLETED UNDER THIS |
| | PERMIT 109.3BUILDING PERMIT VALUATIONS. PLEASE REVUE |
| | SECTION ACCESSIBILITY CODE 202.4.1 / 202.4.2 ACCESSIBLE |
| | FEATURES IN THE EVENT OF DISSPROPORTIONALITY. THE |
| | CONTRACTOR TO PROVIDE DOCUMENTATION WHERE 20% OF THE |
| | FUNDS WILL BE USED IN BRINGING THIS BUILDING UP TO THE |
| | CURRENT ACCESSIBILITY CODE THE DOOR WAY LEADING TO |
| | RESTROOM ROOM # 106 MAY OR MAY NOT NEED TO BE WIDENED |
| | TO COMPLY WITH THE CODE. |
| | |
| | 8) SHEET A1 INDICATES A SINGLE DRINKING FOUNTAIN PLEASE |
| | REVIEW ACCESSIBILITY CODE SECTION 602.1 DRINKING |
| | FOUNTAINS SHALL COMPLY WITH 307 & 602. |
| | |
| | 9) PLEASE NOTE: WINDOW AND DOOR PRODUCT APPROVALS |
| | SUBMITTED MEET WIND LOADING REQUIREMENTS BUT SOME OF |
| | THESE OPENINGS WILL NEED TO MEET ADDITIONAL |
| | REQUIREMENTS AS FIRE RATINGS THAT WILL EFFECT LARGE |
| | MISSILE TESTING AND REQUIRE STORM SHUTTER PROTECTION. |
| | WINDOWS WITH 45 MINUTE FIRE RATING REQUIREMENTS 2010 |
| | FBC-B 1026.6 AND FIGURE 1023.1 2007 FBC-B COMMENTARY. |
| | |
| | 10) NO PRODUCT APPROVALS WERE SUBMITTED FOR THE |
| | OVERHEAD GARAGE DOOR. |
| | |
| | 11) ROOFING PRODUCT APPROVAL NOA 11-0601.09 & |
| | 12-0227.18 NONE OF THE SUB-SYSTEMS AND OR OPTIONS WERE |
| | HIGHLIGHTED, LIMITATION # 7 IN EFFECT REQUIRING A |
| | DESIGN PROFESSIONAL TO PROVIDE CALCULATIONS FOR |
| | ENHANCED FASTENING IN ZONES 2 & 3. |
| | |
| | 12) NOA 11-1013.24 IS A PGT OUTSWING ALUMINUN OUTSWING |
| | FRENCH DOOR SYSTEM, WHEREAS THE PLANS SHEET A1 INDICATE |
| | THE USE OF A INSWING DOOR.1609.1.2/ RULE RULE 9N-3(31) |
| | DOORS, & ADDITIONAL INFORMATION REQUIRED 107.2.1.3. |
| | |
| | 13) PRODUCT TESTING SHEETS FOR TRULITE INDICATE THEY |
| | ARE TESTED TO THE FLORIDA APPROVAL SYSTEM, PLEASE |
| | PROVIDE DOCUMENATION THIS PRODUCT HAS BEEN TESTED WITH |
| | THIS TESTING AGENCY. RULE 9N3 (31). |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |