Plan Review Details - Permit 12080313
Plan Review Stops For Permit 12080313
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-10-17 Cont ID  
Sent By jwitmer Date 2012-10-17 Time 07:54 Rev Time 0.00
Received By jwitmer Date 2012-10-17 Time 07:04 Sent To  
Notes
2012-10-17 07:59:56BUILDING PLAN REVIEW
 PERMIT: 12080313
 ADD: 427 25TH ST
 CONT: CLEAR SPAN STRUCTURES, LLC
 TEL: (561)803-8100
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 DESIGNER OF RECORD: RAFAEL A RODRIGUEZ AR0016608
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
  
 DOOR #2 & 8 WILL REQUIRE 45 MINUTE FIRE RATING WILL NOT
 HAVE LARGE MISSILE TESTING, THEY WILL ALSO REQUIRE
 STORM SHUTTERS IF THEY HAVE A GLAZED OPENING, PLEASE
 PROVIDE PRODUCT APPROVALS FOR STORM SHUTTERS AND KEY
 PLAN IF DOORS HAVE A GLAZED OPENING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-09-26 Cont ID  
Sent By jwitmer Date 2012-09-26 Time 09:08 Rev Time 0.00
Received By jwitmer Date 2012-09-26 Time 07:02 Sent To  
Notes
2012-09-26 09:15:21BUILDING PLAN REVIEW
 PERMIT: 12080313
 ADD: 427 25TH ST
 CONT: TO BE DETERMINED
 TEL: (202) 375-4753
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 DESIGNER OF RECORD: RAFAEL A RODRIGUEZ AR0016608
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 SEPT. 26/ 2012
 ACTION: DENIED
  
 1) 2ND REQUEST. PLEASE REVIEW SECTION 2010 FBC-B 1026.6
 EXTERIOR STAIRWAY PROTECTION AS REQUIRED IN SECTION
 1022.1.1022.3 OPENING PROTECTIVES AS REQUIRED IN
 SECTION 715 & TABLE 7.15.4. WILL REQUIRE 45 MINUTE
 OPENING PROTECTIVES FOR WINDOWS J & DOOR #09.
  
 2) 2ND REQUEST: PRODUCT APPROVAL REPORT SUBMITTED.
 WINDOWS THAT WILL REQUIRE 45 MINUTE FIRE RATING WILL
 NOT HAVE LARGE MISSILLE TESTING, THEY WILL ALSO REQUIRE
 STORM SHUTTERS, PLEASE PROVIDE PRODUCT APPROVALS FOR
 STORM SHUTTERS AND KEY PLAN. PROVIDE STORM PANEL
 INFORMATION(CIRCLE AND OR HIGHLIGHT) WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR
 REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT ISSUANCE.
  
 3-5A) COMPLIED.
 5A) COMPLIED. PLEASE REVIEW SECTION 2010 FBC-B 916.1
 CARBON DIOXIDE DETECTORS.
 5B) NEW COMMENT. NEITHER A-2 NOR ANY OF THE E SHEETS
 INDICATE COMPLIANCE WITH SECTION 2010 FBC-B 907.2.9
 FIRE ALARM SYSTTEMS AND SMOKE ALARMS.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-27 Cont ID  
Sent By jwitmer Date 2012-08-27 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2012-08-27 Time 06:58 Sent To  
Notes
2012-08-27 07:43:56BUILDING PLAN REVIEW
 PERMIT: 12080313
 ADD: 427 25TH ST
 CONT: TO BE DETERMINED
 TEL: (202) 375-4753
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 DESIGNER OF RECORD: RAFAEL A RODRIGUEZ AR0016608
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE REVIEW SECTION 2010 FBC-B 1026.6 EXTERIOR
 STAIRWAY PROTECTION AS REQUIRED IN SECTION
 1022.1.1022.3 OPENING PROTECTIVES AS REQUIRED IN
 SECTION 715 & TABLE 7.15.4. WILL REQUIRE 45 MINUTE
 OPENING PROTECTIVES FOR WINDOWS J & K.
  
 2) WINDOWS THAT WILL REQUIRE 45 MINUTE FIRE RATING WILL
 NOT HAVE LARGE MISSILLE TESTING, THEY WILL ALSO REQUIRE
 STORM SHUTTERS, PLEASE PROVIDE PRODUCT APPROVALS FOR
 STORM SHUTTERS AND KEY PLAN. PROVIDE STORM PANEL
 INFORMATION WITH INSTALLATION SCHEDULE AND KEY PLAN
 WITH SPECIFIC ANCHORS AND MOUNTING TO BE USED FOR ALL
 NON-IMPACT GLAZING. FBC 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR
 REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT ISSUANCE.
  
 3) THE WINDOW SCHEDULE LOCATED ON SHEET A7 HAS A WINDOW
 DEPICTED BETWEEN WINDOW TYPE VI AND VII THAT IS NOT
 IDENTIFIED, PLEASE PROVIDE ADDITIONAL INFORMATION
 107.2.1.3.
  
 4) PLEASE PROVIDE MANUFATURERS SPECIFICATION ON SPIRAL
 STAIRS IN COMPLIANCE WITH 2010 FBC-B 1009.9.3.
  
 5) PLEASE REVIEW SECTION 2010 FBC-B 916.1 CARBON
 DIOXIDE DETECTORS.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-08-14 Cont ID  
Sent By rlecky Date 2012-08-14 Time 12:24 Rev Time 0.00
Received By rlecky Date 2012-08-14 Time 12:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-09-28 Cont ID  
Sent By wjolin Date 2012-09-28 Time 10:51 Rev Time 0.00
Received By wjolin Date 2012-09-28 Time 10:36 Sent To  
Notes
2012-09-28 10:51:08927 25TH STREET
 PERMIT #12080314 (FIRST FLOOR)
 PERMIT #12080313 (SECOND FLOOR)
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL FIRE REVIEW COMMENTS HAVE BEEN ADDRESSED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-08-30 Cont ID  
Sent By wjolin Date 2012-08-30 Time 10:57 Rev Time 0.00
Received By wjolin Date 2012-08-30 Time 10:04 Sent To  
Notes
2012-08-30 10:55:59927 25TH STREET
 PERMIT #12080314 (FIRST FLOOR)
 PERMIT #12080313 (SECOND FLOOR)
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-1: STORAGE OCCUPANCIES SHALL BE SEPARATED FROM
 OTHER OCCUPANCIES SUCH AS MERCANTILE, WITH A 2-HOUR
 FIRE BARRIER PER TABLE 6.1.14.4.1B (NFPA 101).
  
 SHEET A-4: ONLY ONE MEANS OF EGRESS IS PROVIDED FROM
 THE THIRD FLOOR ROOFTOP AREA. THIS DESIGN RESULTS IN A
 COMMON PATH OF TRAVEL GREATER THAN 35 FEET (REFERENCE
 SECTION 30.2.3.5.1 NFPA 101).
  
 SHEET A-4: HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE
 STAIR.
  
 ALL DOORS/WINDOWS/OPENINGS LOCATED WITHIN 10 FEET
 HORIZONTALLY (AND BELOW) THE EXTERIOR STAIR SHALL HAVE
 A 45-MINUTE FIRE RESISTANCE RATING PER SECTIONS
 7.2.2.6.3 AND 7.2.2.6.4 OF NFPA 101.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-10-18 Cont ID  
Sent By jwitmer Date 2012-10-18 Time 11:37 Rev Time 0.00
Received By jwitmer Date 2012-10-11 Time 10:29 Sent To  
Notes
2012-10-12 10:29:53C04

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-10-05 Cont ID  
Sent By lmartine Date 2012-10-05 Time 16:08 Rev Time 0.00
Received By lmartine Date 2012-09-19 Time 12:59 Sent To  
Notes
2012-09-20 12:59:43EXPEDITED
 C--4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-09-20 Cont ID  
Sent By lmartine Date 2012-09-06 Time 12:56 Rev Time 0.00
Received By lmartine Date 2012-08-10 Time 16:30 Sent To  
Notes
2012-08-10 16:30:25EXPEDITED
 B--13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2012-10-18 Cont ID  
Sent By jwitmer Date 2012-10-18 Time 11:35 Rev Time 0.00
Received By jwitmer Date 2012-10-18 Time 11:35 Sent To  
Notes
2012-10-18 11:36:59IMPACT FEE
 MU-2012-19218
 340 SQ FT
 FEES: $1,093.12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-08-27 Cont ID  
Sent By jwitmer Date 2012-08-27 Time 07:47 Rev Time 0.00
Received By jwitmer Date 2012-08-27 Time 07:47 Sent To  
Notes
2012-08-27 07:47:42BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-08-21 Cont ID  
Sent By hmoser Date 2012-08-21 Time 11:29 Rev Time 0.00
Received By hmoser Date 2012-08-21 Time 11:24 Sent To  
Notes
2012-08-21 11:29:07THE PARKING GARAGE IS EXISTING BUT WE RECOMMEND
 THAT YOU REFER TO SECTION 404 ENCLOSED PARKING GARAGE
 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2012-10-17 Cont ID  
Sent By lwagner Date 2012-10-17 Time 09:37 Rev Time 0.00
Received By lwagner Date 2012-10-17 Time 09:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2012-10-05 Cont ID  
Sent By lwagner Date 2012-10-05 Time 13:34 Rev Time 0.00
Received By lwagner Date 2012-10-05 Time 10:38 Sent To  
Notes
2012-10-05 10:48:33FBC ACCESSIBILITY 2010
 FBC PLUMBING 2010 REVIEW #2
 DENIED:
  
 1. SHEETS A-1 AND A-8 (1) PARTIALLY COMPLIED:
 FBC ACCESSIBILITY CODE 2010 604.2 LOCATION. THE WATER
 CLOSET SHALL BE POSITIONED WITH A WALL OR PARTITION TO
 THE REAR AND TO ONE SIDE. THE CENTERLINE OF THE WATER
 CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM TO 18 INCHES
 (455 MM) MAXIMUM FROM THE SIDE WALL OR PARTITION.
  
 2. ***PROVISO***
 IF A SINGLE DRINKING FOUNTAIN IS TO BE USED IT MUST
 COMPLY WITH 602.1 THROUGH 602.6 AND 602.7. A CUP HOLDER
 DOES NOT COMPLY WITH 211.2
  
 FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 3.
  
 4.
  
 ***NOTE***
 IRRIGATION IS NOT PART OF THIS REVIEW. SEPARATE
 APPLICATION, DRAWING, REVIEW, AND FEE REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-08-15 Cont ID  
Sent By lwagner Date 2012-08-15 Time 10:58 Rev Time 0.00
Received By lwagner Date 2012-08-15 Time 10:58 Sent To  
Notes
2012-08-15 11:02:36FBC ACCESSIBILITY 2010
 FBC PLUMBING 2010 REVIEW #1
 DENIED:
  
 1. SHEETS A-1 AND A-8 (1) SHOW AN NEW RESTROOM THAT
 DOES NOT COMPLY WITH FBC ACCESSIBILITY 2010.
 THE RESTROOM WILL BE REQUIRED TO BE A MINIMUM OF 7'-1"
 WIDE TO ACHIVE THE REQUIRED 5' CLEAR SPACE FOR THE
 WATER CLOSET. FBC ACCESSIBILITY CODE 2010 604.3.1
 THE LAVATORY WILL NOT BE PERMITTED IN THE 5' SPACE. FBC
 ACCESSIBILITY CODE 2010 604.3.2
  
 2. SHEETS A-1 AND A-8 (1) SHOW A DRINKING FOUNTAIN THAT
 DOES NOT COMPLY WITH FBC ACCESSIBILITY 2010.
 FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 3. SHEET A-3 THE PLUMBING RISER DIAGRAM DOES NOT SHOW
 THE DRINKING FOUNTAINS.
  
 4. PLEASE INCLUDE THE WATER PIPE IN THE DRAWING.
 FBC 2010 LOCAL AMENDMENTS 107.3.5.1.3 PLUMBING (3)
  
 ***NOTE***
 IRRIGATION IS NOT PART OF THIS REVIEW. SEPARATE
 APPLICATION, DRAWING, REVIEW, AND FEE REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676

Review Stop Z ZONING
Rev No 2 Status P Date 2012-10-04 Cont ID  
Sent By lfranco Date 2012-10-04 Time 19:18 Rev Time 1.50
Received By lfranco Date 2012-10-03 Time 13:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2012-09-19 Cont ID  
Sent By Lfranco Date 2012-09-19 Time 10:02 Rev Time 0.00
Received By ajones Date 2012-09-06 Time 09:58 Sent To  
Notes
2012-09-19 10:02:55PLANNING AND ZONING: **** FAILED ****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PURSUANT TO THE ZONING CODE, SECTION 94-211(D)(6),
 STORIES ABOVE THE FIRST FLOOR SHALL HAVE CLEAR GLAZED
 AREA AND OPENINGS BETWEEN 25 PERCENT AND 45 PERCENT OF
 THE FACADE AREA. PROVIDE DIMENSIONS SHOWING COMPLIANCE
 ACCORDINGLY.
  
 3. PURSUANT TO THE ZONING CODE, SECTION 94-211(D)(8)
 WINDOWS SHALL BE RECESSED A MINIMUM OF TWO INCHES FROM
 THE EXTERIOR FACE OF THE FACADE. SHOW DETAIL OR
 DIMENSIONS.
  
 4. SHEET A-5 : PURSUANT TO THE ZONING CODE, SECTION
 94-211(D)(10) OPENINGS IN UPPER STORIES SHALL BE
 CENTERED DIRECTLY ABOVE OPENINGS IN THE FIRST STORY.
 THE PROPOSED OPENINGS DO NOT COMPLY. THIS REGULATION IS
 APPLICABLE TO ALL FACADES OF THE BUILDING.
  
 5. PURSUANT TO THE ZONING CODE, SECTION 94-211(D)(13),
 ALL WINDOWS, EXCEPT STOREFRONT WINDOWS, SHALL BE
 OPERABLE. WINDOW C ON SHEET C-5 IS NOT OPERABLE. REVISE
 ALL WINDOWS ACCORDINGLY.
  
 6. SIGNAGE WILL BE REVIEWED UNDER SEPARATE PERMIT AND
 SHALL COMPLY WITH THE ZONING CODE, SECTION 94-211(E).
 THE PROPOSED SIGN HAS TO BE PART OF THE FACADE OR BE
 INCORPORATED AS PART OF THE BUILDING. ADDITIONALLY,
 COMPLY WITH SUBSECTION (7) AND (8) SO ALL FASTENERS ARE
 CONCEALED.
  
 ALSO, PLEASE REVISE PLANS TO A UNIVERSAL SCALE SUCH AS
 THE ARCHITECTURAL SCALE OR AN ENGINEERING SCALE.
  
 7. SEPARATE LANDSCAPE AND IRRIGATION PERMITS ARE
 REQUIRED. TWO (2) COPIES OF THE LANDSCAPE PLAN AND A
 CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST OF
 ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST SHALL BE SUBMITTED WITH THE LANDSCAPE PERMIT
 APPLICATION.
  
 PLEASE HAVE LANDSCAPE ARCHITECT CONTACT ME TO DISCUSS
 PROPOSED LANDSCAPE PLAN.
  
 NOTE: THE PROPOSED MAHOGANY TREE ALONG THE TERMINAL
 ISLANDS MAY NOT BE APPROPRIATE FOR THE LOCATION BY THE
 ALLEY AND WITHIN CLOSE PROXIMITY OF THE SILK TREE.
 CONSIDER USING A SMALLER TREE SUCH AS THE CRAPE MYRTLE
 TREE 16'HEIGHT, O.A., 6' SPREAD OR PINK/YELLOW TAB OR
 SIMILAR TREE SPECIES. ALSO CONSIDER REVERSING THE
 LOCATION OF THE MONTGOMERY PALMS WITH THE FLOSS SILK
 TREE TO GIVE THE FLOSS SILK TREE MORE AREA TO GROW. IT
 IS CURRENTLY PROPOSED TOO CLOSE TO THE FENCE AT
 +/2'-6".
  
 ALSO, PLEASE REVISE PLANS TO A UNIVERSAL SCALE SUCH AS
 THE ARCHITECTURAL SCALE OR AN ENGINEERING SCALE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: 9561) 822-1443
 EMAIL: [email protected]
  
  
  