Plan Review Details - Permit 12080296
Plan Review Stops For Permit 12080296
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-02-07 Cont ID  
Sent By shill Date 2014-02-07 Time 18:16 Rev Time 0.00
Received By shill Date 2014-02-07 Time 18:16 Sent To  
Notes
2014-02-07 18:52:17ELEVATION CERTIFICATE OK
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-10-03 Cont ID  
Sent By rmcdouga Date 2012-10-03 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2012-10-02 Time 17:38 Sent To  
Notes
2012-10-03 08:32:54SUBMIT ELEVATION CERTIFICATE

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-09-24 Cont ID  
Sent By rmcdouga Date 2012-09-24 Time 16:36 Rev Time 0.00
Received By rmcdouga Date 2012-09-21 Time 15:26 Sent To  
Notes
2012-09-24 16:36:482010 FBC
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 ALUMINUM METAL ROOF FL#5286.1 IS FOR THE 2007 FBC AND
 HAS A MAXIMUM DESIGN UPLIFT PRESSURE OF -69.25 PSF
 WHICH IS TOO LOW FOR A STRUCTURE WITH A 4/12 SLOPE ROOF
 AND A 20 ' PLUS MEAN ROOF HEIGHT LOCATED IN EXPOSURE
 CATEGORY D WITH A 170 MPH WINDSPEED ( VULT 170 MPH/
 VASD 132 MPH) . ALSO THE PLANS SPECIFY THIS AS A COPPER
 ROOF. PLEASE PROVIDE THE APPROPRIATE PRODUCT APPROVALS.
 DCA RULE 9N-3 AND FBC R301.2.1
  
 2) SUBMIT TWO COPIES OF EVALUATION REPORTS FOR THE
 SPRAY FOAM INSULATION THAT WILL BE INSTALLED.
  
 3) SPECIFY THE METHOD OF ATTACHMENT LISTED IN THE
 CEMENT ROOF TILE PRODUCT APPROVAL THAT WILL BE USED TO
 INSTALL THE ROOF TILE AND RESIST THE OVERTURN MOMENT.
 FBC R 301.2.1 AND FBC R905.3
  
 4) SUBMIT TWO COPIES OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING OF THE CORNER AND
 PERIMETER AREAS AS REQUIRED BY LIMITATION #7 OF THE
 PRODUCT APPROVAL FOR THE GAF MODIFIED ROOF SYSTEM WITH
 THE -52.5 PSF DESIGN PRESSURE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-16 Cont ID  
Sent By rmcdouga Date 2012-08-16 Time 08:54 Rev Time 0.00
Received By rmcdouga Date 2012-08-15 Time 07:45 Sent To  
Notes
2012-08-16 08:07:502010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WHICH
 REQUIRES THE LOWEST FINISHED FLOOR TO HAVE A MINIMUM
 ELEVATION OF 7'6" BASE FLOOD ELEVATION. THIS INCLUDES
 THE 6" FREEBOARD ESTABLISHED BY THE CITY OF WEST PALM
 BEACH'S FLOOD ORDINANCE. SPECIFY THE FINISH FLOOR
 ELEVATIONS FOR THE EXISTING STRUCTURE AND THE PROPOSED
 ADDITION ON THE PLANS AND SUBMIT A ELEVATION
 CERTIFICATE FOR THE PROPOSED ADDITION. WPB CODE OF
 ORDINANCES CHAPTER 94, ARTICLE XVII SECTIONS 94-541
 THRU 94-547.
  
 2) ON SHEET A-1 THE COVERED ENTRY IS MISLABELED AS
 BEDROOM #2. PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 3) THE PROJECT IS LOCATED IN AN AREA OF QUESTIONABLE
 SOIL. SUBMIT TWO SIGNED AND SEALED COPIES OF A
 SUBSURFACE SOILS REPORT FOR THE PROJECT. FBC R401.4
  
 4) SUBMIT TWO SETS OF ENERGY CALCULATIONS SIGNED BY THE
 PREPARER AND THE OWNER/AGENT FOR THE ADDED AREAS OF
 CONDITIONED SPACE AS REQUIRED BY 2010 FBC ENERGY
 CONSERVATION SECTION 402.
  
 5) THE PLANS SPECIFY "POLYISOCENE" INSULATION. DO YOU
 MEAN "POLYICYNENE" SPRAY FOAM INSULATION? SUBMIT TWO
 SETS OF THE EVALUATION REPORTS FOR THE SPRAY FOAM
 INSULATION AND SPECIFY THAT THE ATTIC IS UNVENTED ON
 THE PLANS. FBC R316
  
 6) THE BALCONY GUARDS ARE SPECIFIED AS 32" IN HEIGHT.
 FBC R 312.2 REQUIRES THE GUARDS TO BE A MINIMUM OF 36"
 ABOVE THE WALKING SURFACE. PLEASE CORRECT.
  
 7) SHOW COMPLIANCE WITH FBC R312.3 WHICH REQUIRES THAT
 OPENINGS IN THE GUARDS CAN NOT ALLOW A 4" DIAMETER
 SPHERE TO PASS.
  
 8) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 9) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 SINGLE HUNG WINDOWS (NOA NO. 08-1210.03) AND THE
 OUTSWING DOORS (NOA NO. 11-0912.12) HAVE BEEN
 SUPERSEDED. PLEASE SUBMIT 2 SETS OF CURRENT PRODUCT
 APPROVALS FOR THE SINGLE HUNG WINDOWS AND THE OUTSWING
 DOORS. DCA RULE 9N-3
  
 10) PLEASE SUBMIT 2 SETS OF CURRENT PRODUCT APPROVALS
 FOR THE FIXED GLASS WINDOWS, THE STRUCTURAL MULLIONS,
 THE CONCRETE ROOF TILES (SPECIFY ATTACHMENT METHOD) THE
 STANDING SEAM METAL ROOF, THE MODIFIED BITUMEN ROOFING
 ON THE BALCONIES (WITH RAS 117 ENHANCED FASTENING
 CALCULATIONS) AND THE SIMPSON CONNECTORS, STRAPS &
 HANGERS AS REQUIRED BY DCA RULE 9N-3.
  
 11) IN ORDER TO SPEED REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS HAVE
 BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-08-13 Cont ID  
Sent By rlecky Date 2012-08-13 Time 08:00 Rev Time 0.00
Received By rlecky Date 2012-08-13 Time 06:58 Sent To  
Notes
2012-08-13 09:16:31ROUTED TO BIN R10
2012-08-13 08:07:14ADDITIONAL REQUIREMENTS NOTED ON PLAN.
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2012-08-15 Cont ID  
Sent By rmcdouga Date 2012-08-15 Time 08:28 Rev Time 0.00
Received By rmcdouga Date 2012-08-15 Time 08:28 Sent To  
Notes
2012-08-15 08:32:27SEPARATE PERMITS, APPLICATION, PLANS AND REVIEW IS
 REQUIRED FOR THE GAS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-02-07 Cont ID  
Sent By shill Date 2014-02-07 Time 18:16 Rev Time 0.00
Received By shill Date 2014-02-07 Time 18:16 Sent To  
Notes
2014-02-07 18:16:18ELEVATION CERT ROUTED TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-10-03 Cont ID  
Sent By rmcdouga Date 2012-10-03 Time 08:19 Rev Time 0.00
Received By rmcdouga Date 2012-10-02 Time 16:50 Sent To  
Notes
2012-10-02 16:51:07GAVE TO ROBBIE
 EXPEDITED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-24 Cont ID  
Sent By rmcdouga Date 2012-09-24 Time 16:37 Rev Time 0.00
Received By rmcdouga Date 2012-09-17 Time 13:30 Sent To  
Notes
2012-09-17 13:30:42SENT TO MCDOUGAL'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-30 Cont ID  
Sent By rlecky Date 2012-08-30 Time 16:01 Rev Time 0.00
Received By rlecky Date 2012-08-09 Time 16:17 Sent To  
Notes
2012-08-13 09:16:11R10
2012-08-09 16:18:19EXPEDITED
 GAVE TO LECKY

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2012-10-05 Cont ID  
Sent By rmcdouga Date 2012-10-05 Time 08:46 Rev Time 0.00
Received By rmcdouga Date 2012-10-05 Time 08:46 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-09-24 Cont ID  
Sent By rmcdouga Date 2012-09-24 Time 16:37 Rev Time 0.00
Received By rmcdouga Date 2012-09-24 Time 08:18 Sent To  
Notes
2012-09-24 16:37:45AN IMPACT FEE REVIEW BY PALM BEACH COUNTY WILL BE
 REQUIRED BEFORE THE PERMIT IS ISSUED. THIS IS TYPICALLY
 DONE AFTER THE PLANS HAVE BEEN APPROVED BY THE CITY.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-08-15 Cont ID  
Sent By rmcdouga Date 2012-08-15 Time 08:24 Rev Time 0.00
Received By rmcdouga Date 2012-08-15 Time 08:24 Sent To  
Notes
2012-08-15 08:27:05AN IMPACT FEE REVIEW BY PALM BEACH COUNTY WILL BE
 REQUIRED BEFORE THE PERMIT IS ISSUED. THIS IS TYPICALLY
 DONE AFTER THE PLANS HAVE BEEN APPROVED BY THE CITY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-09-24 Cont ID  
Sent By rmcdouga Date 2012-09-24 Time 08:56 Rev Time 0.00
Received By rmcdouga Date 2012-09-24 Time 08:56 Sent To  
Notes
2012-09-24 09:10:132010 FBC
  
 MECHANICAL REVISION REQUIRED
  
 1) THE EQUIPMENT FOR BOTH OF THE 19 SEER UNITS AS
 SPECIFIED ON THE ENERGY CALCULATIONS IS TO BE LISTED IN
 THE EQUIPMENT SIZING CALCULATION SUMMARIES AND AN
 EQUIPMENT MATCHING SCHEDULE IS REQUIRED ON THE PLANS.
 FBCR M1401.3 AND CITY AMENDMENTS 107.2.1

Review Stop P PLUMBING
Rev No 3 Status P Date 2012-10-02 Cont ID  
Sent By rmcdouga Date 2012-10-02 Time 17:37 Rev Time 0.00
Received By rmcdouga Date 2012-10-02 Time 17:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2012-09-24 Cont ID  
Sent By rmcdouga Date 2012-09-24 Time 10:10 Rev Time 0.00
Received By rmcdouga Date 2012-09-24 Time 10:10 Sent To  
Notes
2012-09-24 10:16:532010 FBC
  
 DENIED BY PLUMBING
  
 1) SECOND FLOOR BATHROOM #3 IS NOT SHOWN ON THE
 SANITARY PLUMBING ISOMETRIC DRAWINGS. PLEASE CORRECT.
 FBCR M1401.3 AND CITY AMENDMENTS 107.2.1
  
 2) THE SANITARY ISOMETRIC DRAWINGS THAT WERE SUBMITTED
 SHOW EACH FIXTURE GROUP SEPARATELY. SUBMIT 2 SETS OF
 SANITARY ISOMETRIC DRAWINGS FOR THE ENTIRE (DWV)
 SANITARY DRAINAGE SYSTEM SHOWN TOGETHER. FBCR P3001.1
 AND CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-08-15 Cont ID  
Sent By rmcdouga Date 2012-08-15 Time 07:36 Rev Time 0.00
Received By rmcdouga Date 2012-08-15 Time 07:36 Sent To  
Notes
2012-08-15 08:23:562010 FBC
  
 DENIED BY PLUMBING
  
 1) SUBMIT TWO SETS OF A SANITARY RISER ISOMETERIC
 DRAWINGS AS REQUIRED BY CITY AMENDMENTS 107.3.5.3.
 SPECIFY ALL DRAIN, WASTE AND VENT PIPE SIZES ON THE
 DRAWINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2012-08-29 Cont ID  
Sent By ajones Date 2012-08-29 Time 15:19 Rev Time 0.00
Received By ajones Date 2012-08-29 Time 15:19 Sent To  
Notes
***NONE***