Plan Review Details - Permit 12080192
Plan Review Stops For Permit 12080192
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2012-08-29 Cont ID  
Sent By jwitmer Date 2012-08-29 Time 10:36 Rev Time 0.00
Received By jwitmer Date 2012-08-29 Time 10:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-10-04 Cont ID  
Sent By rlecky Date 2012-10-04 Time 16:36 Rev Time 0.00
Received By rlecky Date 2012-10-04 Time 16:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-08-14 Cont ID  
Sent By rlecky Date 2012-08-14 Time 15:12 Rev Time 0.00
Received By rlecky Date 2012-08-14 Time 12:40 Sent To  
Notes
2012-08-14 15:12:4212080192
 275 @ N QUADRILLE BLVD.
 QUADRILLE STREETSCAPE
  
 SHEET E-4
 PROVIDE AN ELECTRICAL SYSTEM BONDING AND GROUNDING
 SCHEMATIC FOR THE ELECTRICAL SERVICE. NEC 250.4, 250.20
  
 SHEET E-5
 PROVIDE SIGNED AND SEALED WIND LOADING CERTIFICATION
 FOR THE SITE LIGHT POLE ASSEMBLY WITH FIXTURES. 2010
 FBC 1609.1., ASCE 7-10
  
 REVISE PLAN DISCREPANCY FOR WIND LOADING TO INDICATE
 THE CURRENT FLORIDA BUILDING CODE (FBC) 2010. PROVIDE
 AN EXPOSURE CATEGORY AND IMPORTANCE FACTOR TO THE
 DESIGN. FBC 1609, ASCE 7-10
  
 NOTE: PLANS FOR NEW CONSTRUCTION SHALL BE SIGNED BY THE
 DESIGNER OF RECORD.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2012-10-16 Cont ID  
Sent By bmoree Date 2012-10-16 Time 17:58 Rev Time 0.00
Received By bmoree Date 2012-10-16 Time 17:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-10-23 Cont ID  
Sent By lmartine Date 2012-10-16 Time 12:40 Rev Time 0.00
Received By lmartine Date 2012-09-26 Time 11:01 Sent To  
Notes
2012-09-28 11:02:15RESUB SENT TO C01 PER L MARTINEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2012-09-10 Time   Rev Time 0.00
Received By jwitmer Date 2012-08-08 Time 09:38 Sent To  
Notes
2012-08-08 09:38:33INCOMING SENT TO C-01. JW

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-09-10 Cont ID  
Sent By lwagner Date 2012-09-10 Time 15:41 Rev Time 0.00
Received By lwagner Date 2012-09-07 Time 10:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-08-15 Cont ID  
Sent By ajones Date 2012-08-15 Time 09:08 Rev Time 0.00
Received By ajones Date 2012-08-15 Time 09:08 Sent To  
Notes
***NONE***