Plan Review Details - Permit 12080060
Plan Review Stops For Permit 12080060
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-10-30 Cont ID  
Sent By shill Date 2012-10-30 Time 12:49 Rev Time 0.00
Received By shill Date 2012-10-30 Time 12:48 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-08-29 Cont ID  
Sent By jwitmer Date 2012-08-29 Time 14:36 Rev Time 0.00
Received By jwitmer Date 2012-08-29 Time 14:36 Sent To  
Notes
2012-08-29 14:39:19BUILDING PLAN REVIEW
 PERMIT: 12080060
 ADD: 4705 BROADWAY
 CONT: CILAS CONCRETE
 TEL: (561)255-3725
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW 8/29/2012
 ACTION: DENIED
  
 1) 2010 FBC-B 439.2 WALLS SEPARATING DWELLING UNITS IN
 THE SAME BUILDING, WALLS SEPARATING SLEEPING UNITS IN
 THE SAME BUILDING AND WALLS SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS FIRE
 PARTITIONS IN ACCORDANCE WITH SECTION 709.
  
 2) 2010 FBC-B TABLE 508.4 REQUIRED SEPERATION OF
 OCCUPANCIES BETWEEN RESIDENTIAL OCCUPANCIES AND STORAGE
 OCCUPANCIES REQUIRES 2 HOUR FOR NON-SPRINKLERED
 BUILDINGS.
  
 3)THE WALL IS NOT INDICATED TO CONTINUE TO THE DECK
 ABOVE, PROVIDE A ASSEMBLY WITH A 2HOUR RATING.
 709.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE
 TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW
 TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB
 OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED
 FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL
 BE SECURELY ATTACHED THERETO. IF THE PARTITIONS ARE NOT
 CONTINUOUS TO THE SHEATHING, DECK OR SLAB, AND WHERE
 CONSTRUCTED OF COMBUSTIBLE CONSTRUCTION, THE SPACE
 BETWEEN THE CEILING AND THE SHEATHING, DECK OR SLAB
 ABOVE SHALL BE FIREBLOCKED OR DRAFTSTOPPED IN
 ACCORDANCE WITH SECTIONS 717.2 AND 717.3 AT THE
 PARTITION LINE. THE SUPPORTING CONSTRUCTION SHALL BE
 PROTECTED TO AFFORD THE REQUIRED FIRE-RESISTANCE RATING
 OF THE WALL SUPPORTED, EXCEPT FOR WALLS SEPARATING
 TENANT SPACES IN COVERED MALL BUILDINGS, WALLS
 SEPARATING DWELLING UNITS, WALLS SEPARATING SLEEPING
 UNITS AND CORRIDOR WALLS, IN BUILDINGS OF TYPE IIB,
 IIIB AND VB CONSTRUCTION.
  
 4) 709.4.1 ROOF CONSTRUCTION. WHEN THE FIRE PARTITION
 IS CONTINUOUS TO THE UNDERSIDE OF THE ROOF SHEATHING IN
 OCCUPANCIES OF GROUPS R-1, R-2 AND R-3 AS APPLICABLE IN
 SECTION 101.2, IN TYPE III, IV AND V CONSTRUCTION THE
 FOLLOWING SHALL BE PROVIDED:
 709.4.1.1 ROOF SHEATHING.
  
 THE ROOF SHEATHING OR DECK SHALL BE OF APPROVED
 NONCOMBUSTIBLE MATERIALS OR OF FIRE-RETARDANT-TREATED
 WOOD, FOR A DISTANCE OF 4 FEET (1220 MM); OR
 709.4.1.2 ROOF PROTECTION.
  
 COMPLIED: THE ROOF SHALL BE PROTECTED WITH 0.625-INCH
 (15.88 MM) TYPE X GYPSUM BOARD DIRECTLY BENEATH THE
 UNDERSIDE OF THE ROOF SHEATHING OR DECK, SUPPORTED BY A
 MINIMUM OF NOMINAL 2-INCH (51 MM) LEDGERS ATTACHED TO
 THE SIDES OF THE ROOF FRAMING MEMBERS, FOR A MINIMUM
 DISTANCE OF 4 FEET (1220 MM).
  
 5) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-13 Cont ID  
Sent By jwitmer Date 2012-08-13 Time 13:40 Rev Time 0.00
Received By jwitmer Date 2012-08-13 Time 13:40 Sent To  
Notes
2012-08-13 13:43:05BUILDING PLAN REVIEW
 PERMIT: 12080060
 ADD: 4705 BROADWAY
 CONT: CILAS CONCRETE
 TEL: (561)255-3725
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 2010 FBC-B 439.2 WALLS SEPARATING DWELLING UNITS IN
 THE SAME BUILDING, WALLS SEPARATING SLEEPING UNITS IN
 THE SAME BUILDING AND WALLS SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS FIRE
 PARTITIONS IN ACCORDANCE WITH SECTION 709.
  
 2) 2010 FBC-B TABLE 508.4 REQUIRED SEPERATION OF
 OCCUPANCIES BETWEEN RESIDENTIAL OCCUPANCIES AND STORAGE
 OCCUPANCIES REQUIRES 2 HOUR FOR NON-SPRINKLERED
 BUILDINGS.
  
 3) 709.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM
 THE TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY
 BELOW TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING,
 SLAB OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED
 FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL
 BE SECURELY ATTACHED THERETO. IF THE PARTITIONS ARE NOT
 CONTINUOUS TO THE SHEATHING, DECK OR SLAB, AND WHERE
 CONSTRUCTED OF COMBUSTIBLE CONSTRUCTION, THE SPACE
 BETWEEN THE CEILING AND THE SHEATHING, DECK OR SLAB
 ABOVE SHALL BE FIREBLOCKED OR DRAFTSTOPPED IN
 ACCORDANCE WITH SECTIONS 717.2 AND 717.3 AT THE
 PARTITION LINE. THE SUPPORTING CONSTRUCTION SHALL BE
 PROTECTED TO AFFORD THE REQUIRED FIRE-RESISTANCE RATING
 OF THE WALL SUPPORTED, EXCEPT FOR WALLS SEPARATING
 TENANT SPACES IN COVERED MALL BUILDINGS, WALLS
 SEPARATING DWELLING UNITS, WALLS SEPARATING SLEEPING
 UNITS AND CORRIDOR WALLS, IN BUILDINGS OF TYPE IIB,
 IIIB AND VB CONSTRUCTION.
  
 4) 709.4.1 ROOF CONSTRUCTION. WHEN THE FIRE PARTITION
 IS CONTINUOUS TO THE UNDERSIDE OF THE ROOF SHEATHING IN
 OCCUPANCIES OF GROUPS R-1, R-2 AND R-3 AS APPLICABLE IN
 SECTION 101.2, IN TYPE III, IV AND V CONSTRUCTION THE
 FOLLOWING SHALL BE PROVIDED:
 709.4.1.1 ROOF SHEATHING.
  
 THE ROOF SHEATHING OR DECK SHALL BE OF APPROVED
 NONCOMBUSTIBLE MATERIALS OR OF FIRE-RETARDANT-TREATED
 WOOD, FOR A DISTANCE OF 4 FEET (1220 MM); OR
 709.4.1.2 ROOF PROTECTION.
  
 THE ROOF SHALL BE PROTECTED WITH 0.625-INCH (15.88 MM)
 TYPE X GYPSUM BOARD DIRECTLY BENEATH THE UNDERSIDE OF
 THE ROOF SHEATHING OR DECK, SUPPORTED BY A MINIMUM OF
 NOMINAL 2-INCH (51 MM) LEDGERS ATTACHED TO THE SIDES OF
 THE ROOF FRAMING MEMBERS, FOR A MINIMUM DISTANCE OF 4
 FEET (1220 MM).
  
 5) PLANS ARE NOT INDICATED THEY ARE DESIGNED BY A
 DESIGN PROFESSIONAL. 2010 WEST PALM BEACH
 ADMINISTRATIVE CODE 107.1 GENERAL. SUBMITTAL DOCUMENTS
 CONSISTING OF CONSTRUCTION DOCUMENTS, STATEMENT OF
 SPECIAL INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA
 SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 REQUIRED BY THE BUILDING OFFICIAL, AND MAY REQUIRE ONLY
 ONE SET OF SUBMITTALS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-11-01 Cont ID  
Sent By wjolin Date 2012-11-01 Time 12:03 Rev Time 0.00
Received By wjolin Date 2012-11-01 Time 12:02 Sent To  
Notes
2012-11-01 12:03:33MAY NEED AN ELECTRICAL INSPECTION TO CONFIRM EXISTING
 ELECTRICAL (WHICH APPEARS TO HAVE BEEN ALTERED)
 COMPLIES WITH CODE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-08-29 Cont ID  
Sent By ddaniels Date 2012-08-29 Time 14:36 Rev Time 0.00
Received By ddaniels Date 2012-08-29 Time 14:36 Sent To  
Notes
2012-08-29 14:38:16SEE BUILDING NOTES

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-08-04 Cont ID  
Sent By wjolin Date 2012-08-04 Time 21:39 Rev Time 0.00
Received By wjolin Date 2012-08-04 Time 20:54 Sent To B
Notes
2012-08-04 21:38:574705 BROADWAY
 PERMIT #12080060
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SECTION A-1 INDICATES ONLY ONE 5/8" LAYER OF FIRE RATED
 GYPSUM BOARD. INDICATE HOW THIS EQUATES TO A 2-HOUR
 FIRE SEPARATION.
  
 SUBMIT PRODUCT DATA FOR FIRE CAULK.
  
 NOTE: THERE IS EXISTING ELECTRICAL CONDUIT RUNNING
 NORTH/SOUTH ALONG THE 2X8 WOOD JOISTS IN THE STORAGE
 ROOM. THIS WORK APPEARS TO BE UNPERMITTED AND WILL NEED
 TO BE INSPECTED BY THE ELECTRICAL INSPECTOR (PHIL
 PETTY) BEFORE ANY CEILINGS ARE TO BE INSTALLED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-11-01 Cont ID  
Sent By wjolin Date 2012-11-01 Time 12:03 Rev Time 0.00
Received By wjolin Date 2012-10-18 Time 12:11 Sent To  
Notes
2012-10-18 12:11:36TO SH DESK (PER JW)
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-27 Cont ID  
Sent By wjolin Date 2012-09-27 Time 13:58 Rev Time 0.00
Received By wjolin Date 2012-08-28 Time 17:54 Sent To  
Notes
2012-08-28 17:54:20IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-10-01 Cont ID  
Sent By jwitmer Date 2012-08-13 Time 15:14 Rev Time 0.00
Received By jwitmer Date 2012-08-02 Time 17:06 Sent To  
Notes
2012-08-02 17:06:32SENT TO FIRE SHELF FOR REVIEW. JG.