Plan Review Details - Permit 12080026
Plan Review Stops For Permit 12080026
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-08-29 Cont ID  
Sent By shill Date 2012-08-29 Time 10:13 Rev Time 0.00
Received By shill Date 2012-08-29 Time 10:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-15 Cont ID  
Sent By shill Date 2012-08-15 Time 18:05 Rev Time 0.00
Received By shill Date 2012-08-15 Time 18:05 Sent To  
Notes
2012-08-15 18:07:53****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%.
  
 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM
 /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF)
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4,
 PROVIDE CALCULATIONS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-15 Cont ID  
Sent By shill Date 2012-08-15 Time 18:08 Rev Time 0.00
Received By shill Date 2012-08-02 Time 09:55 Sent To  
Notes
2012-08-02 09:55:46MISC 1