Plan Review Details - Permit 12070803
Plan Review Stops For Permit 12070803
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-09-07 Cont ID  
Sent By shill Date 2012-09-07 Time 09:53 Rev Time 0.00
Received By shill Date 2012-09-07 Time 09:53 Sent To  
Notes
2012-09-07 09:55:46****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 PROVIDE A LETTER AT INSPECTION FROM THE ARCHITECT WHICH
 STATES THAT DESIGN COMPLIES WITH REQUIREMENT OF 170MPH,
 EXPOSURE C
  
 IF ARCHITECT HAS DESIGNED TO A DIFFERENT DESIGN
 CRITERIA, SUBMIT A REVISION
  
 SEPARATE PERMIT REQUIRED FOR ROOF. WITH ROOF PERMIT
 APPLICATION PLEASE SUBMIT THE FOLLOWING:
  
 PRODUCT APPROVAL
  
 INDICATE APPROVED ASSEMBLY PROPOSED
  
 RAS117 CALCULATIONS OR ENHANCED FASTENING PATTERN FOR
 ZONES 2 & 3 PREPARED BY ARCHITECT, ENGINEER, OR
 REGISTERED ROOF CONSULTANT AS APPLICABLE
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-28 Cont ID  
Sent By shill Date 2012-08-28 Time 14:58 Rev Time 0.00
Received By shill Date 2012-08-28 Time 14:58 Sent To  
Notes
2012-08-28 15:37:22****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 1. PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY AS
 WELL AS A SITE PLAN SHOWING LOCATION OF PROPOSED
 IMPROVEMENT AND DISTANCE TO PROPERTY LINES, FBC 106,
 FBC 2010 RESIDENTIAL 302.1.
  
 2. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 3. FBC 107.2.1.4, PROVIDE A STRUCTURAL ARCHITECTURAL
 QUALITY PLAN, DRAWN TO SCALE. SEE ALSO FBC R 301.1. IT
 IS NOT CLEAR HOW PROPOSED CONSTRUCTION WILL RESIST
 LOADS SUCH AS WIND AND GRAVITY, APPEARS THAT ONLY A
 TRUSS END AND A STRAP ARE TO SUPPORT THE NEW ROOF
 FRAMING. AS PROPOSED CONSTRUCTION DOES NOT IMPLEMENT
 CONSTRUCTION METHODS TYPICAL OF THIS AREA, PROVIDE
 CALCULATIONS TO SHOW THAT THE EXISTING TRUSSES AND
 PROPOSED NAILINT/STRAP TO TRUSS AND TIE BEAM ARE
 ADEQUATE TO RESIST WIND AND GRAVITY LOADS. FBC R
 801.2.1.6.4, ALSO PROVIDE CALCULATIONS TO SHOW THAT
 EXISTING TRUSSES CAN PROVIDE THE RESISTANCE TO LOADS
 FOR PROPOSED IMPROVEMENT WITHOUT AFFECTING EXISTING
 STRUCTURE.
  
 4. PLAN TO INCLUDE WIND DESIGN CRITERIA AS WELL AS
 DESIGN METHOD, SEE FBC R 301.2.1.1.
  
 5. SPECIFY STRAPS AND PROVIDE PRODUCT APPROVAL,
 FAC9N-3, FBC RESIDENTIAL 301.1 (WIND).
  
 6. SPECIFY ROOF PITCH AND ROOF HEIGHT AT LOWEST POINT,
 FBC R

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-07 Cont ID  
Sent By shill Date 2012-09-07 Time 09:56 Rev Time 0.00
Received By shill Date 2012-08-30 Time 10:06 Sent To  
Notes
2012-09-04 10:07:07IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-28 Cont ID  
Sent By shill Date 2012-08-28 Time 15:38 Rev Time 0.00
Received By shill Date 2012-07-23 Time 14:36 Sent To  
Notes
2012-07-24 14:36:58SENT TO ZONING BOX

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2012-09-06 Time   Rev Time 0.00
Received By mdekle Date 2012-09-04 Time 13:21 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2012-07-30 Time   Rev Time 0.00
Received By mdekle Date 2012-07-24 Time 16:35 Sent To  
Notes
2012-07-30 13:56:37PLANNING: **** FAILED ****
 PLEASE RESPOND TO COMMENTS IN WRITING.
  
 THE APPLICANT MUST SUBMIT A SURVEY OR SITE PLAN
 DEPICTING THE EXACT LOCATION OF THE ADDITION, IN
 RELATION TO THE PROPERTY LINE(S).
  
 PLEASE BE ADVISED; SEC. 94-72. - SINGLE-FAMILY LOW
 DENSITY-3 (SF3) RESIDENTIAL DISTRICT; SINGLE-FAMILY
 MEDIUM DENSITY-5 (SF5) RESIDENTIAL DISTRICT;
 SINGLE-FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT.
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING.
 FRONT: 25 FEET;
 CORNER: 12.5 FEET;
 REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER IS
 LESS;
 SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 MURRIAH DEKLE, MPA
 PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
  
  