Plan Review Details - Permit 12070800
Plan Review Stops For Permit 12070800
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2012-10-02 Cont ID  
Sent By lmartine Date 2012-10-03 Time 10:13 Rev Time 0.00
Received By jnguyen Date 2012-10-02 Time 13:48 Sent To  
Notes
2012-10-03 10:12:42UPON EXAMINATION OF THE SITE PLAN & RECOMMENDATIONS
 FROM VARIOUS STAKEHOLDERS IN THE ADDRESSING REVIEW
 PANEL, THE DECISION WAS MADE THAT THE PRIMARY ADDRESS
 OF 7000 S DIXIE HWY WOULD REMAIN AS THE "MAIN ROOFTOP
 ADDRESS" OF THE WEST BUILDING WITH NEW SECONDARY UNIT
 ADDRESSES OF 7000 S DIXIE HWY # 100, # 110, # 120, #
 130, # 140, # 150, # 160, # 170 & # 180 PER BAY ON PCN#
 74434410000007020.
  
 IN ADDITION, NEW SECONDARY ADDRESSES FOR THE EAST
 BUILDING STARTING WITH A "MAIN ROOFTOP ADDRESS" OF 7050
 S DIXIE HWY & THE FOLLOWING ASSIGNED SUITE ADDRESSES
 FROM NORTH TO SOUTH: # 100, # 110, # 120, # 130 & #
 140.
  
 THIS OPTION WILL ALLOW THE PROPERTY OWNER TO DETERMINE
 THE ADDRESSING ADJUSTMENTS FOR NEW SUITE NUMBERS AT
 HIS/HER DISCRETION, WHENEVER THESE TWO BUILDINGS GO
 THROUGH INTERIOR MODIFICATIONS & RENOVATIONS IN THE
 FUTURE (SUCH AS THE MERGER OR SPLITTING OF BAYS). FOR
 EXAMPLE, IF NEW A BAY FORMS IN BETWEEN 7000 S DIXIE HWY
 # 100 & # 110, THEN THE PROPERTY MANAGER CAN ASSIGN IT
 7000 S DIXIE HWY # 105, AS THE SUITE NUMBERS OF # 101
 TO # 109 WERE AVAILABLE TO-BE-ISSUED. ESSENTIALLY, THE
 GROUNDWORK OF SUITE ADDRESSES HAS ALREADY BEEN LAID OUT
 FOR THE DEVELOPER.
  
  
 ACCORDING TO SECTION 1.3B OF THE CITY OF WPB ADDRESSING
 POLICY:
  
 ONE PRIMARY NUMBER SHALL BE ASSIGNED TO EACH STRUCTURE
 WITH MULTIPLE UNITS. EACH UNIT WITHIN THE STRUCTURE
 SHALL BE ASSIGNED A UNIT DESIGNATOR SUCH AS ?SUITE?.
 ALLOWED UNIT DESIGNATORS INCLUDE APARTMENT (APT)
 NUMBERS FOR APARTMENTS, AND SUITE, BAY, UNIT (STE, OR
 BAY, OR UNIT) NUMBERS FOR COMMERCIAL BUILDINGS. THE
 UNIT DESIGNATOR SHALL BE NUMERIC AND REFRAIN FROM THE
 USE OF ALPHA CHARACTERS "IF POSSIBLE".
  
 IT WILL BE THE DEVELOPER?S RESPONSIBILITY TO ASSIGN
 UNIT (DESIGNATORS) ADDRESSES TO ALL UNITS INSIDE THE
 STRUCTURE. THE LIST OF ADDRESSES MUST BE APPROVED BY
 THE SUPPORT SERVICES DEPARTMENT IN CHARGE OF ADDRESSING
 PRIOR TO RELEASE THE CERTIFICATE OF OCCUPANCY.
  
 EXAMPLES TO ASSIGN UNIT NUMBERS ARE:
  
 GROUND/FIRST FLOOR: UNIT NUMBERS FROM 100 TO 199, (100
 MAIN ST. # 100, INDICATES THE FIRST UNIT ON THE FIRST
 FLOOR)
 SECOND FLOOR: UNIT NUMBERS FROM 200 TO 299, (100 MAIN
 ST. # 200, INDICATES THE FIRST UNIT ON THE SECOND
 FLOOR)
  
  
  
 ACCORDING TO THE CODE OF ORDINANCE SEC. 78-6. NUMBERING
 STANDARDS--RESIDENTIAL, COMMERCIAL, INDUSTRIAL AND
 INSTITUTIONAL STRUCTURES- FOR THE INSTALLATION OF THE
 ADDRESS SIGN:
  
 THE ADDRESS SIGN SHALL BE POSTED ON THAT PORTION OF THE
 STRUCTURE FRONTING OR FACING UPON THE STREET OR
 PRINCIPAL VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE
 READILY VISIBLE TO APPROACHING VEHICLES.
  
 ALL RESIDENTIAL, COMMERCIAL, INDUSTRIAL, OR
 INSTITUTIONAL STRUCTURES UTILIZING ADDRESSES WITHIN THE
 CITY SHALL POST ADDRESS CHARACTERS IN COMPLIANCE WITH
 THIS SECTION AS FOLLOWS:
  
 (1) SIZE AND TYPE. ALL ADDRESS CHARACTERS SHALL BE
 ARABIC NUMERALS, EXCEPT THAT ENGLISH LETTERS MAY BE
 USED TO IDENTIFY INDIVIDUAL UNITS ALL POSSESSING THE
 SAME NUMERIC ADDRESS, WHERE APPLICABLE. ALL CHARACTERS
 ON SINGLE-FAMILY HOMES, DUPLEXES AND "MOTHER-IN-LAW
 SUITES" SHALL BE NO LESS THAN THREE INCHES IN HEIGHT
 AND ONE INCH IN WIDTH. ALL CHARACTERS ON BUILDINGS
 OTHER THAN SINGLE-FAMILY HOMES AND DUPLEXES SHALL BE NO
 LESS THAN SIX INCHES IN HEIGHT AND ONE INCH IN WIDTH.
  
 (2) LOCATION, BUILDINGS CONTAINING MORE THAN ONE
 ADDRESS. ALL ADDRESSES SHALL BE POSTED ON THAT PORTION
 OF THE STRUCTURE FRONTING OR FACING UPON THE STREET OR
 PRINCIPAL VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE
 READILY VISIBLE TO APPROACHING VEHICLES. OWNERS OR
 TENANTS OF ALL HOUSES AND BUILDINGS USING A SERVICE
 ALLEY SHALL ALSO POST A NUMBER ON THE SIDE OF THE
 BUILDINGS ADJACENT TO AND FACING SUCH ALLEY. IF THE
 HOUSE OR BUILDING IS OBSTRUCTED BY A FENCE, THEN THE
 NUMBER SHALL BE POSTED ON THE FENCE. THE PLACEMENT OF
 NUMBERS ON BUILDINGS OR FENCES, AS THE CASE MAY BE,
 SHALL BE SUBJECT TO THE DIRECTION OR APPROVAL OF THE
 CITY'S CONSTRUCTION SERVICES DEPARTMENT. BUILDINGS
 WHICH CONTAIN MORE THAN ONE RESIDENTIAL, COMMERCIAL,
 INDUSTRIAL, OR INSTITUTIONAL ADDRESS SHALL POST A
 SEPARATE ADDRESS MEETING THE REQUIREMENTS OF THIS
 SECTION AT THE EXTERIOR ENTRANCE TO EACH INDIVIDUAL
 ADDRESS OR COMMON EXTERIOR ENTRANCE TO SEVERAL
 ADDRESSES THEREIN, AND THE UNIT NUMBER SHALL ALSO BE
 POSTED ON THE EXTERIOR DOOR OF EACH UNIT SERVED BY SUCH
 A COMMON EXTERIOR ENTRANCE.
  
 (3) MONUMENT SIGNS. ALL MONUMENT SIGNS FOR MULTIPLE
 RESIDENTIAL, COMMERCIAL, INDUSTRIAL, OR INSTITUTIONAL
 DEVELOPMENTS SHALL POST THE ADDRESS RANGE FOR THE
 DEVELOPMENT. THE POSTED ADDRESS RANGE SHALL MEET THE
 REQUIREMENTS OF THIS SECTION.
  
 (4) COLOR OF CHARACTERS. ALL ADDRESS CHARACTERS SHALL
 BE OF A COLOR IN DIRECT CONTRAST TO AND CLEARLY
 DISTINGUISHABLE FROM THE BACKGROUND TO WHICH THE
 CHARACTERS ARE AFFIXED.
  
 (5) ADDRESSES TO BE CLEARLY VISIBLE FROM THE STREET.
 EACH ADDRESS UPON THE EXTERIOR OF ANY BUILDING SHALL BE
 CLEARLY VISIBLE FROM THE STREET OR OTHER PRINCIPAL
 MEANS OF VEHICULAR ACCESS. LANDSCAPING SHALL NOT BE
 PERMITTED TO COVER OR CONCEAL ADDRESSES. NIGHTTIME
 LIGHTING SHALL BE LOCATED SO AS TO MAXIMIZE VISIBILITY
 OF ADDRESSES.
  
 (6) CORRECTNESS. IT IS THE RESPONSIBILITY OF THE
 PROPERTY OWNER OF ANY STRUCTURE OR BUILDING SUBJECT TO
 THE REQUIREMENTS OF THIS SECTION TO POST THE CORRECT
 ADDRESS ON THE PROPERTY.
  
 (7) RESPONSIBILITY FOR MAINTENANCE. THE OWNER OF ANY
 STRUCTURE OR BUILDING SUBJECT TO THE REQUIREMENTS OF
 THIS SECTION SHALL MAINTAIN, REPAIR OR REPLACE ALL
 ADDRESSES WHEN NECESSARY TO COMPLY WITH THE
 REQUIREMENTS OF THIS SECTION.
  
  
 JOHN NGUYEN
 GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 PUBLIC UTILITIES DEPARTMENT
 OFFICE: (561) 822-1239
 FAX: (561) 822-1249
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-09-25 Cont ID  
Sent By jwitmer Date 2012-09-25 Time 13:19 Rev Time 0.00
Received By jwitmer Date 2012-09-25 Time 07:05 Sent To  
Notes
2012-09-25 13:38:49BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 A REVISION WILL BE REQUIRED, LIFE SAFETY SHEET
 PROVIDING 2 HR OCCUPANCY WALL BETWEEN THE RESIDENTIAL
 OCCUPANCY AND BUSINESS OCCUPANCY IN BUILDING B, PER
 TABLE 508.4 FOR NON-SPRINKLERED BUILDINGS.
  
 PLEASE PROVIDE WALL TYPE ASSEMBLY FOR 2 HR RATED WALL.
 PLEASE ALSO NOTE FOR FIRE PARTITIONS 709.4 CONTINUITY.
 709.4 FIRE PARTITIONS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW TO THE
 UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR DECK
 ABOVE OR TO THE FIRE-RESISTANCE-RATED FLOOR/CEILING OR
 ROOF/CEILING ASSEMBLY ABOVE, AND SHALL BE SECURELY
 ATTACHED THERETO. IF THE PARTITIONS ARE NOT CONTINUOUS
 TO THE SHEATHING, DECK OR SLAB, AND WHERE CONSTRUCTED
 OF COMBUSTIBLE CONSTRUCTION, THE SPACE BETWEEN THE
 CEILING AND THE SHEATHING, DECK OR SLAB ABOVE SHALL BE
 FIREBLOCKED OR DRAFTSTOPPED IN ACCORDANCE WITH SECTIONS
 717.2 AND 717.3 AT THE PARTITION LINE. THE SUPPORTING
 CONSTRUCTION SHALL BE PROTECTED TO AFFORD THE REQUIRED
 FIRE-RESISTANCE RATING OF THE WALL SUPPORTED, EXCEPT
 FOR WALLS SEPARATING TENANT SPACES IN COVERED MALL
 BUILDINGS, WALLS SEPARATING DWELLING UNITS, WALLS
 SEPARATING SLEEPING UNITS AND CORRIDOR WALLS, IN
 BUILDINGS OF TYPE IIB, IIIB AND VB CONSTRUCTION .
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-02 Cont ID  
Sent By jwitmer Date 2012-08-02 Time 16:03 Rev Time 0.00
Received By jwitmer Date 2012-08-02 Time 07:04 Sent To  
Notes
2012-08-02 09:23:32BUILDING PLAN REVIEW
 PERMIT: 12070800
 ADD: 7000 S DIXIE HWY
 CONT: CUTTING EDGE BUILDING SYSTEMS
 TEL: (561)282-8265
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-0.0 COVER SHEET, MISSING CRITERIA FOR
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS 2010 FBC-B.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION PLAN;
 FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 2 107.3.5.1.1(2). OCCUPANCY GROUP AND SPECIAL OCCUPANCY
 REQUIREMENTS SHALL BE DETERMINED. CHANGE OF OCCUPANCY
 FOR THE OFFICE PORTION ONLY WILL NEED TO COMPLY WITH
 2010 EXISTING BUILDING CODE CHAPTER 9 .
 TO BE DETERMINED: IF SECTIONS EXST BLDG 901.3 APPLY OR
 IF 901.3.1 APPLY NEXT COMMENT WILL DETERMINE.
  
 3) 107.3.5.1.1(3). MINIMUM TYPE OF CONSTRUCTION SHALL
 BE DETERMINED (SEE TABLE 503). THE DESIGNER OF RECORD
 WILL NEED TO INDICATE THE MINIMUM CONSTRUCTION TYPE, IF
 THE TOTAL SQUARE FOOT AREA IS FIGURED AS IN 2010 FBC-B
 503.1.2 BUILDING ON SAME LOT, WHERE THERE IS NO FIRE
 SEPERATION REQUIREMENTS BETWEEN BUILDINGS OR AS TWO
 SEPERATE BUILDINGS WITH
 FIRE SEPERATION REQUIREMENTS AND ASSUMED PROPERTY LINES
 BETWEEN THE TWO BUILDINGS.
  
 NOTE IF FIGURED AS TWO SEPERATE BUILDINGS THEN (2)
 SEPERATE PERMITS WILL NEED TO BE APPLIED FOR FOR RECORD
 KEEPING PURPOSES. NOTE THE LIVE WORK UNITS ARE STILL
 CLASSIFIED AS A R2 OCCUPANCY AND WILL NEED TO MEET THE
 REQUIREMENTS OF THE 2010 FBC-B 438.
  
 4) 107.3.5.1.1(4). FIRE-RESISTANT CONSTRUCTION
 REQUIREMENTS SHALL INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
  
 5) 107.3.5.1.1(5) FIRE SUPPRESSION SYSTEMS SHALL
 INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 PRE-ENGINEERED SYSTEMS
  
 6) 107.3.5.1.1(6). LIFE SAFETY SYSTEMS SHALL BE
 DETERMINED AND SHALL INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 EARLY WARNING
  
 7) 107.3.5.1.1(7) . OCCUPANCY LOAD/EGRESS REQUIREMENTS
 SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 8) 107.3.5.1.1 (10) 10. ACCESSIBILITY REQUIREMENTS
 SHALL INCLUDE THE FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
  
 9) A-1.1 & A-3.0 BOTH SHEETS INDICATE NEW EXSPANSION
 (30), THIS IS NOT CLEAR IF THIS IS AN ADDITION OR SPACE
 THAT HAS BEEN RECONFIGURED. 107 2.1.3. ADDITIONAL
 INFORMATION REQUIRED.
  
 10) THE COMPUTER FILES INDICATE A CODE CASE FROM
 9/02/2009 CASE ID 09080014 FOR STRUCTURAL DAMAGE TO THE
 OFFICE AND ENTRANCE, ROOF FRAMING, PLANS SUBMITTED DO
 NOT INDICATE ANY STRUCTURAL WORK THAT WILL SATISFY THIS
 CODE CASE? ADDITIONAL INFORMATION REQUIRED, 107.2.1.3.
 & 116.1* UNSAFE BUILDING OR SYSTEMS.
  
 11) BUILDING # 1 OFFICES 1-8 (CHANGE IN OCCUPANCY) :
 PLEASE CLARIFY SUITE # 18 E3 INDICATES THIS AREA TO BE
 MAIN RETAIL AREA, IS THIS A NEW MERCANTILE OCCUPANCY?
 FBC-B 107.2.1.3 / 309.1.
  
 12A) BUILDING # 1, PLANS DO NOT PROVIDE TENANT
 SEPERATION AS REQUIRED BY 2010 FBC-B 709.1(6).
  
 12B) 2010 FBC-B 439.2 SEPARATION WALLS. WALLS
 SEPARATING DWELLING UNITS IN THE SAME BUILDING, WALLS
 SEPARATING SLEEPING UNITS IN THE SAME BUILDING AND
 WALLS SEPARATING DWELLING OR SLEEPING UNITS FROM OTHER
 OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME BUILDING
 SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE
 WITH SECTION 709.
  
 13A) EXIST BUILDING CODE 906.1/ 912.8 FLORIDA BUILDING
 CODE- BUILDING. THE BUSINESS OCCUPANCIES BUILDING # 1,
 OFFICES 1-8 WILL NEED TO PROVIDE ACCESSIBILITY PLEASE
 SEE HOW MONIES ARE TO BE ALLOCATED TO ACCESSIBILITY
 UPGRADES TO THESE UNITS AS WELL AS BUILDING # 2 UNITS
 1-4.
  
 2010 ACCESSIBILITY CODE 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
 PLEASE PROVIDE AN ITEMIZED LIST WHERE AN ADDITIONAL
 $34,915.80 WILL BE ALLOCATED TO ACCESSIBILITY IN THE
 ORDER LISTED ABOVE.
  
 PLEASE NOTE FOR PUBLIC ACCESS TO ALL AREAS OF OFFICES
 AND OFFICES IN THE LIVE WORK LOFT THE MINIMUM CLEAR
 OPENING IS 2'-10" FOR ALL DOORS THAT YOU CAN PASS
 THROUGH, EVEN WALK IN CLOSETS.IT APPEARS THAT
 APPROXIMATELY 50 % OF THE DOORS ON SHEET A-3.1 & A-3.2
 DO NOT APPEAR ON THE DOOR SCHEDULE. 2010 FBC-B 1008.1.1
 & ACCESSIBILITY CODE 404.2.3.
  
 13B) PLEASE SEE ACCESSIBILITY REQUIREMENTS FOR UNITS
 1-4 IN BUILDING # 2:
 2010 ACCESSIBILITY CODE' 201.2.1 COMMERCIAL FACILITIES
 AND PLACES OF PUBLIC ACCOMMODATION LOCATED IN PRIVATE
 RESIDENCES.
 201.2.1.1
 WHEN A COMMERCIAL FACILITY OR PLACE OF PUBLIC
 ACCOMMODATION IS LOCATED IN A PRIVATE RESIDENCE, THE
 PORTION OF THE RESIDENCE USED EXCLUSIVELY AS A
 RESIDENCE IS NOT COVERED BY THIS SUBPART, BUT THAT
 PORTION USED EXCLUSIVELY IN THE OPERATION OF THE
 COMMERCIAL FACILITY OR THAT PORTION USED BOTH FOR THE
 COMMERCIAL FACILITY AND FOR RESIDENTIAL PURPOSES IS
 COVERED BY THE NEW CONSTRUCTION AND ALTERATIONS
 REQUIREMENTS OF THIS SUBPART.
 201.2.2.2
 THE PORTION OF THE RESIDENCE COVERED UNDER PARAGRAPH
 (B)(1) OF THIS SECTION EXTENDS TO THOSE ELEMENTS USED
 TO ENTER THE COMMERCIAL FACILITY, INCLUDING THE
 HOMEOWNER?S FRONT SIDEWALK, IF ANY, THE DOOR OR
 ENTRYWAY, AND HALLWAYS; AND THOSE PORTIONS OF THE
 RESIDENCE, INTERIOR OR EXTERIOR, AVAILABLE TO OR USED
 BY EMPLOYEES OR VISITORS OR CUSTOMERS AND CLIENTS OF
 THE COMMERCIAL FACILITY, INCLUDING RESTROOMS
  
 14) PLANS ARE MISSING THE WIND DESIGN CRITERIA:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 PRODUCT APPROVALS CAN NOT BE REVIEWED UNTIL PRESSURES
 ARE PROVIDED.
  
 15) SHEET A-3.01 & A-3.02 BOTH INDICATE THE EXTERIOR
 WALLS, THE CELLS TO BE FILLED WITH CORE-FIL 500 R-14
 FOAM, PLEASE UPDATE ENERGY CALCULATIONS, 107.2.1.3.
  
 16) PLANS A-3.01 & A3.02 BOTH INDICATE ACCESSIBLE
 PARKING SPACES BUT THE PLANS DO NOT INDICATE ACCESS TO
 THE WALKWAYS, ACCESSIBILITY 406.1 CURB RAMPS.
  
 17) PLEASE PROVIDE EGRESS WINDOW SIZE FOR BEDROOMS OF
 THE LIVE WORK LOFTS 2010 FBC-B 1029.2/ 1029.1-4.
  
 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-09-25 Cont ID  
Sent By rlecky Date 2012-09-25 Time 17:22 Rev Time 0.00
Received By rlecky Date 2012-09-25 Time 16:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-08-07 Cont ID  
Sent By rlecky Date 2012-08-06 Time 10:56 Rev Time 0.00
Received By rlecky Date 2012-07-31 Time 16:54 Sent To  
Notes
2012-08-06 11:00:0312070800
 7000 S.DIXIE
 COMMERCIAL RENOVATION/ CHANGE OF USE
  
 PLEASE SPECIFY AN ELECTRICAL WIRING METHOD. NEC 110.8
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 EQUIPMENT. NEC 110.22, 110.16
 PLEASE INDICATE THE TYPE OF CEILING AND HEIGHT. THE
 HEIGHT OF CEILING FANS SHALL BE IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS. NEC 110.3
 SMOKE ALARMS ARE REQUIRED FOR THE SLEEPING UNITS. FBC
 704.4.3
 RESIDENTIAL UNITS REQUIRE SOME ADDITIONAL RECEPTACLES.
 NEC 210.8, FBC 708.1
 UNDERGROUND SERVICE CONDUCTORS REQUIRE A WARNING
 RIBBON. NEC 300.5(D) (3)
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-10-02 Cont ID  
Sent By wjolin Date 2012-10-02 Time 11:23 Rev Time 0.00
Received By wjolin Date 2012-10-02 Time 11:16 Sent To AD
Notes
2012-10-02 11:12:377000 SOUTH DIXIE HIGHWAY
 PERMIT #12070800 - BUILDING "A" (WEST BLD.)
 PERMIT #12090630 - BUILDING "B" (EAST BLD.)
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REMOVE COOKING APPLIANCES FROM BUSINESS OCCUPANCY OR
 PROVIDE PROPER AUTOMATIC FIRE SUPPRESSION.
  
 ALL DEMOLITION/CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 PROVIDE BUILDING ADDRESSES VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 STRUCTURES WITH LIGHT FRAME ROOF TRUSS CONSTRUCTION
 SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO THE
 BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER "R" DESIGNATION
 PER FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE
 CODE 69A-60.0081.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-07-30 Cont ID  
Sent By wjolin Date 2012-07-30 Time 11:59 Rev Time 0.00
Received By wjolin Date 2012-07-28 Time 17:55 Sent To  
Notes
2012-07-30 11:59:497000 SOUTH DIXIE HIGHWAY
 PERMIT #12070800
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THIS PROJECT APPEARS TO HAVE THREE REHABILITATION
 CLASSES:
 (1) ADDITION
 (2) CHANGE OF OCCUPANCY (FRONT BUILDING ONLY - MOTEL
 OCCUPANCY TO BUSINESS OCCUPANCY)
 (3) LEVEL III ALTERATION WHEREBY MORE THAN 50% OF THE
 COMBINED BUILDING AREAS ARE BEING REHABILITED.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 SHEET A-3.0 INDICATES THE USE OF THE SPACE AS BUSINESS
 OFFICES; HOWEVER, SHEET E-2 INDICATES THE SAME SPACES
 TO BE USED AS STORAGE AND RETAIL WHICH WOULD BE TREATED
 AS TWO SEPARATE OCCUPANCIES TYPES ALTOGETHER.
  
 THE MOTEL SUITES INDICATE INDIVIDUAL COOKING FACILITIES
 WHICH WOULD CLASSIFY THE BUILDING AS A MIXED-USE HOTEL
 AND APARTMENT OCCUPANCY. THE STRICTEST FIRE PROTECTION
 AND LIFE SAFETY PROVISIONS OF EACH OCCUPANCY WILL
 APPLY.
  
 PER THE LIFE SAFETY CODE (NFPA 101) SECTION 43.6.4.1,
 "IN A BUILDING WITH REHABILITATION WORK AREAS INVOLVING
 OVER 50 PERCENT OF THE AGGREGATE BUILDING AREA,
 AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED..IN
 ACCORDANCE WITH THE REQUIREMENTS OF OTHER SECTIONS OF
 THIS CODE APPLICABLE TO NEW CONSTRUCTION FOR THE
 OCCUPANCY."
  
 PER NFPA 101 SECTION 30.3.5, "ALL APARTMENT BUILDINGS
 SHALL BE PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED, AUTOMATIC SPRINKLER SYSTEM."
  
 PER NFPA 101 SECTION 30.3.4.5, HARD-WIRED MULTI-STATION
 SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA,
 OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS, AND ON ALL LEVELS OF THE DWELLING
 UNIT, INCLUDING BASEMENTS.
  
 INDICATE IF LAUNDRY #37 IS DEDICATED TO ONE MOTEL SUITE
 OR IF THE LAUNDRY WILL BE USED BY ALL MOTEL GUESTS.
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PROVIDE BUILDING ADDRESSES VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND (REFERENCE: SECTION 10.12.1.2
 OF THE FLORIDA FIRE PREVENTION CODE ? NFPA 1).
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-10-02 Cont ID  
Sent By lmartine Date 2012-10-02 Time 15:01 Rev Time 0.00
Received By lmartine Date 2012-09-24 Time 15:51 Sent To  
Notes
2012-09-24 15:55:38INCOMING SENT TO C-3. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2012-08-21 Time   Rev Time 0.00
Received By rmcdouga Date 2012-07-23 Time 15:31 Sent To  
Notes
2012-07-24 15:32:34C04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2012-10-09 Cont ID  
Sent By jgomez Date 2012-10-09 Time 11:45 Rev Time 0.00
Received By jgomez Date 2012-10-09 Time 11:45 Sent To  
Notes
2012-10-09 11:47:02MU-2012-18481

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-10-01 Cont ID  
Sent By hmoser Date 2012-10-01 Time 09:40 Rev Time 0.00
Received By hmoser Date 2012-10-01 Time 09:28 Sent To  
Notes
2012-10-01 09:39:54PASS PROVISO
 1) REFER TO SECTION 601.4 BALANCED RETURN AIR.
 2010 FBC (M) .
 2) REFER TO SECTION 607.5.1 FIRE WALLS 2010 FBC (M)
 3) PROVIDE A DETAIL FROM THE ENGINEER ON CURB OR
 CONDENSER STAND TIE DOWN TO ROOF, AND UNIT TIE DOWN
 TO STAND OR CURB . SECTION 301.12 WIND RESISTANCE
 2010 FBC (M) .
 4) REFER TO SECTION 403.1 VENTILATION 2010 FBC (M)
 5) HAVE REVISED PLAN BE FOR FINAL INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-08-21 Cont ID  
Sent By rregueir Date 2012-08-21 Time 08:52 Rev Time 0.00
Received By rregueir Date 2012-08-20 Time 16:59 Sent To  
Notes
2012-08-21 08:52:28REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2010 CODE FAMILY
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAYNE AHU LOOKS TO BE OVER AN AREA OF HARD CEILING.
 FULL ACCESS FOR SERVICE AND/OR REPLACEMENT IS REQUIRED
 PER FBC-M 306.1.
  
 2. PROVIDE BALANCED RETURN FOR SYSTEMS WHERE A
 CENTRALIZED RETURN IS UTILIZED AND CLOSED DOORS WILL
 IMPEDE THE FREE FLOW OF RETURN AIR TO THE UNIT PER
 FBC-M 601.4.
  
 3. PROVIDE VENTILATION CALCULATIONS AND SHOW HOW
 VENTILATION IS TO BE PROVIDED FOR ALL AREAS WHICH
 CONSTITUTE A CHANGE OF OCCUPANCY PER FBC-M 403.1.
  
 4. PROVIDE WIND RESISTANT ATTACHMENT DETAILS FOR THE
 RTU AND ACCU PER FBC-M 301.12.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2012-08-07 Cont ID  
Sent By avann Date 2012-08-07 Time 09:57 Rev Time 0.00
Received By ajones Date 2012-08-07 Time 09:56 Sent To  
Notes
2012-08-07 10:02:538/7/12- APPROVED WITH THE PROVISO THAT A SEPERATE
 PAVING, STRIPING AND LANDSCAPE PERMIT IS REQUIRED.
  
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]