Plan Review Details - Permit 12070779
Plan Review Stops For Permit 12070779
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-08-09 Cont ID  
Sent By jwitmer Date 2012-08-09 Time 07:55 Rev Time 0.00
Received By jwitmer Date 2012-08-09 Time 07:00 Sent To  
Notes
2012-08-09 07:51:15PROVISO:
 NOTES WHERE PLANS ARE INCORRECT:
 SHEET A-3.0
 TABLE 601 FIRE RESISTANT RATINGS, PROVIDED:
 STRUCTURAL FRAME INCLUDING TRUSSES INDICATED 1 HR
 PROTECTED, SHEET A-3.0 USE OF DROPPED ACOUSTICAL CEIL
 PER 2010 FBC COMPLYING WITH 808.1.1.1 NOT FIRE RATIED,
 FIRE RATING COMPLIES WITH 808.1.1.2 .
  
 BEARING WALLS, EXTERIOR INDICATES A 4 HR RATING,
 MISSING FOOTNOTE B OF TABLE 720.1(2) 3-1.3 USE
 EQUIVALENT THICKNESS, 2 HRS UNLESS CELLS FILLED.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-07-31 Cont ID  
Sent By rlecky Date 2012-07-31 Time 16:28 Rev Time 0.00
Received By rlecky Date 2012-07-31 Time 16:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-07-31 Cont ID  
Sent By wjolin Date 2012-07-31 Time 12:04 Rev Time 0.00
Received By wjolin Date 2012-07-31 Time 11:47 Sent To  
Notes
2012-07-31 12:03:58SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-09 Cont ID  
Sent By jwitmer Date 2012-08-09 Time 07:55 Rev Time 0.00
Received By jwitmer Date 2012-07-23 Time 15:18 Sent To  
Notes
2012-07-24 15:19:36B19

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2012-08-07 Cont ID  
Sent By hmoser Date 2012-08-07 Time 13:06 Rev Time 0.00
Received By hmoser Date 2012-08-07 Time 12:41 Sent To  
Notes
2012-08-07 13:06:03CALLED GENO RAY THERE IS NO AIR CONDITIONING WORK ON
 THIS JOB.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-08-02 Cont ID  
Sent By lwagner Date 2012-08-02 Time 11:52 Rev Time 0.00
Received By lwagner Date 2012-08-02 Time 09:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-08-03 Cont ID  
Sent By lfranco Date 2012-08-03 Time 15:10 Rev Time 0.00
Received By mdekle Date 2012-08-03 Time 15:10 Sent To  
Notes
***NONE***