Plan Review Details - Permit 12070700
Plan Review Stops For Permit 12070700
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-08-29 Cont ID  
Sent By jwitmer Date 2012-08-29 Time 12:12 Rev Time 0.00
Received By jwitmer Date 2012-08-29 Time 12:11 Sent To  
Notes
2012-08-29 12:18:03BUILDING PLAN REVIEW
 PERMIT: 12070700
 ADD: 600 NORTHPOINT PARKWAY
 CONT: CORPORATE PROPERTY SERVICES INC.
 TEL: (954)426-5144
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(B) WINDOWS
 (31)(E) STORM SHUTTERS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-06 Cont ID  
Sent By jwitmer Date 2012-08-06 Time 15:54 Rev Time 0.00
Received By jwitmer Date 2012-08-06 Time 15:11 Sent To  
Notes
2012-08-06 15:21:16BUILDING PLAN REVIEW
 PERMIT: 12070700
 ADD: 600 NORTHPOINT PARKWAY
 CONT: CORPORATE PROPERTY SERVICES INC.
 TEL: (954)426-5144
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE COVERSHEET CS-GR CODE DATA INDICATES THIS
 BUILDING WAS BUILT AS A TYPE V UNPROTECTED PER
 DOCUMENTS STATING 1987. THE 2004 FBC BUILDING TYPES
 CHANGED, THE PREVIOUS CODES A TYPE V-UNPROTECTED BECAME
 A TYPE IIIB IN THE 2004 FBC TO THE CURRENT VERSION.
  
 2) SHEET A403 INDICATES THE REMOVAL OF DOUBLE DOORS AND
 NOTE # 8 INFILL OF WALL AND NEW STOREFRONT GLAZING.
 2A) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
 (E) STORM SHUTTERS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-09-07 Cont ID  
Sent By rlecky Date 2012-09-07 Time 09:23 Rev Time 0.00
Received By rlecky Date 2012-09-07 Time 09:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-08-08 Cont ID  
Sent By rlecky Date 2012-08-08 Time 13:10 Rev Time 0.00
Received By rlecky Date 2012-08-07 Time 17:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-09-06 Cont ID  
Sent By wjolin Date 2012-09-06 Time 10:35 Rev Time 0.00
Received By wjolin Date 2012-09-06 Time 10:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-07-31 Cont ID  
Sent By wjolin Date 2012-07-31 Time 12:48 Rev Time 0.00
Received By wjolin Date 2012-07-31 Time 12:09 Sent To  
Notes
2012-07-31 12:46:42600 NORTHPOINT PARKWAY
 PERMIT #12070700
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.
  
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 NO FIRE ALARM APPLIANCES, EXIT SIGNS OR EMERGENCY
 LIGHTING LAYOUTS PROVIDED.
  
 SEPARATE SUB-PERMITS REQUIRED FOR MODIFICATION OF
 EXISTING FIRE ALARM AND FIRE SPRINKLER SYSTEMS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-07 Cont ID  
Sent By rlecky Date 2012-09-07 Time 09:24 Rev Time 0.00
Received By rlecky Date 2012-08-23 Time 12:47 Sent To  
Notes
2012-08-27 12:57:33EXPEDITED
 C-29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-14 Cont ID  
Sent By eschneid Date 2012-08-14 Time 10:34 Rev Time 0.00
Received By eschneid Date 2012-07-19 Time 08:36 Sent To  
Notes
2012-07-23 08:36:56SENT TO C29 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2012-09-06 Cont ID  
Sent By hmoser Date 2012-09-06 Time 09:32 Rev Time 0.00
Received By hmoser Date 2012-09-04 Time 10:11 Sent To  
Notes
2012-09-06 09:32:04CALLED CONTRACTOR THERE IS NO MECHANICAL ON THIS JOB .
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-08-07 Cont ID  
Sent By hmoser Date 2012-08-07 Time 11:33 Rev Time 0.00
Received By hmoser Date 2012-08-07 Time 10:55 Sent To  
Notes
2012-08-07 11:33:06PLANS DENIED
 PAGE A131 OF THE PLANS NOT 60 SEE MECHANICAL DRAWINGS.
 THERE ARE NO MECHANICAL PLANS SUBMITTED.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-08-29 Cont ID  
Sent By lwagner Date 2012-08-29 Time 14:40 Rev Time 0.00
Received By lwagner Date 2012-08-29 Time 14:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-08-06 Cont ID  
Sent By lwagner Date 2012-08-06 Time 13:11 Rev Time 0.00
Received By lwagner Date 2012-08-02 Time 14:51 Sent To  
Notes
2012-08-03 14:36:16FBC PLUMBING 2010 REVIEW #1
 DENIED:
  
 1. THERE APPEAR TO BE TWO EXISTING PUBLIC USE WATER
 CLOSETS FOR WOMEN ON SHEET A010.
 FROM SHEET CS THE OCCUPANT LOAD FOR WOMEN IN THE PUBLIC
 AREA IS:
 A-2____ 39 WOMEN @ 1 PER 75 = .52 WATER CLOSET
 A-3___ 144 WOMEN @ 1 PER 65 = 2.21
 TOTAL REQUIRED FOR WOMEN 2.73 (3) WATER CLOSETS WOULD
 BE REQUIRED PER TABLE FBC PLUMBING 403.1
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2012-08-14 Cont ID  
Sent By eschneid Date 2012-08-14 Time 10:24 Rev Time 0.25
Received By eschneid Date 2012-08-14 Time 10:24 Sent To  
Notes
2012-08-14 10:25:49***SIGNAGE REQUIRES A SEPARATE PERMIT***
  
 THE RENOVATIONS TO THE BUILDING WITHIN THE PAST YEAR DO
 NOT REACH 50% OF THE STRUCTURE VALUE.