Plan Review Details - Permit 12070697
Plan Review Stops For Permit 12070697
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-08-30 Cont ID  
Sent By jwitmer Date 2012-08-30 Time 08:00 Rev Time 0.00
Received By jwitmer Date 2012-08-30 Time 07:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-08 Cont ID  
Sent By jwitmer Date 2012-08-08 Time 16:29 Rev Time 0.00
Received By jwitmer Date 2012-08-08 Time 16:29 Sent To  
Notes
2012-08-08 16:45:23PERMIT: 12070697
 ADD: 2400 S DIXIE HWY
 CONT: SYMMETRY CONSTRUCTION GROUP
 TEL: (305)968-5811
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A2. 2010 FBC ACCESSIBILITY CODE PLEASE REVIEW
 FIGURE 604.8.1.6 WHEELCHAIR ACCESSIBLE TOLIET
 COMPARTMENTS IN NEW CONSTRUCTION AND SECTION 604.3.1
 AND FIGURE 604.3.1.
  
 2) SHEET A2. PROJECT SUMMARY INDICATES THIS TO BE AN
 A-3 OCCUPANCY BUT THE DESIGN LOAD IS FIGURED FOR A
 BUSINESS OCCUPANCY. THE 4160 SQ FT / 15 GROSS= TO AN
 OCCUPANT LOAD OF 278 OCCUPANTS. PLEASE REVIEW 2010
 FBC-B TABLE 1004.1.1. CHANGE IN OCCUPANCY, THE
 CONTRACTOR WILL NEED TO NOTE A CHANGE OF OCCUPANCY ON
 THE PERMIT APPLICATION.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-08-20 Cont ID  
Sent By rlecky Date 2012-08-20 Time 07:08 Rev Time 0.00
Received By rlecky Date 2012-08-17 Time 16:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-07-24 Cont ID  
Sent By rlecky Date 2012-07-24 Time 11:31 Rev Time 0.00
Received By rlecky Date 2012-07-24 Time 11:09 Sent To  
Notes
2012-07-24 11:38:2012070697
 2400 S. DIXIE
 ADA RESTROOM CONSTRUCTION
  
 DEPTH OF WORKING SPACE IN FRONT OF EXISTING PANEL
 BOARDS MUST BE AT LEAST 36 INCHES. NEC 110.26
  
 OVERCURRENT DEVICES AND ENCLOSURES SHOULD NOT BE
 LOCATED ADJACENT TO A MOP SINK. NEC 240.32, 312.2
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-08-29 Cont ID  
Sent By ddaniels Date 2012-08-29 Time 14:09 Rev Time 0.00
Received By ddaniels Date 2012-08-29 Time 14:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-07-31 Cont ID  
Sent By wjolin Date 2012-07-31 Time 10:11 Rev Time 0.00
Received By wjolin Date 2012-07-31 Time 09:43 Sent To  
Notes
2012-07-31 10:11:372400 SOUTH DIXIE HIGHWAY
 PERMIT #12070697
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE APPROPRIATE WORKING CLEARANCES TO ELECTRICAL
 PANELS PER NFPA 70.
  
 COMBUSTIBLE MATERIALS SHALL NOT BE STORED IN ELECTRICAL
 EQUIPMENT ROOMS PER SECTION 10.19.5 (FFPC - NFPA 1)
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-08-30 Cont ID  
Sent By jwitmer Date 2012-08-30 Time 08:00 Rev Time 0.00
Received By jwitmer Date 2012-08-13 Time 07:44 Sent To  
Notes
2012-08-29 12:45:26EXPEDITED REQUEST 8/29/12
2012-08-14 07:44:26B23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-08 Cont ID  
Sent By jwitmer Date 2012-08-08 Time 16:46 Rev Time 0.00
Received By jwitmer Date 2012-07-19 Time 08:52 Sent To  
Notes
2012-07-23 08:52:33SENT TO B23 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2012-08-30 Cont ID  
Sent By jwitmer Date 2012-08-30 Time 07:12 Rev Time 0.00
Received By jwitmer Date 2012-08-30 Time 07:12 Sent To  
Notes
2012-08-30 07:14:04CONTRACTOR TOOK PLANS TO PALM BEACH COUNTY IMPACT FEE
 ASSESSMENT OFFICE- PLANS STAMPED NO FEES DUE. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-08-08 Cont ID  
Sent By jwitmer Date 2012-08-08 Time 16:45 Rev Time 0.00
Received By jwitmer Date 2012-08-08 Time 16:45 Sent To  
Notes
2012-08-08 16:46:06BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-08-16 Cont ID  
Sent By lwagner Date 2012-08-16 Time 10:56 Rev Time 0.00
Received By lwagner Date 2012-08-16 Time 10:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-07-27 Cont ID  
Sent By lwagner Date 2012-07-27 Time 13:53 Rev Time 0.00
Received By lwagner Date 2012-07-26 Time 08:34 Sent To  
Notes
2012-07-26 15:32:11FBC PLUMBING 2010 REVIEW #1:
 DENIED:
  
 1. A RISER DIAGRAM IS REQUIRED PER FBC 107.3.5 PLUMBING
 (13) PLUMBING RISER.
  
 2. THE LAVATORIES SHOWN ON A-2, A3, P-1, AND P-2 ARE
 SHOWN IN THE REQUIRED 5' CLEARANCE FOR THE WATER
 CLOSET.
 FBC ACCESSIBILITY 604.3.2 ...NO OTHER FIXTURES OR
 OBSTRUCTIONS SHALL BE LOCATED WITHIN THE REQUIRED WATER
 CLOSET CLEARANCE. PLEASE SEE FIGURE 604.8.1.6
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 3 Status P Date 2012-09-07 Cont ID  
Sent By jroach Date 2012-09-07 Time 16:58 Rev Time 0.00
Received By jroach Date 2012-09-07 Time 16:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2012-08-27 Cont ID  
Sent By jroach Date 2012-08-27 Time 13:48 Rev Time 0.00
Received By jroach Date 2012-08-20 Time 15:42 Sent To  
Notes
2012-08-27 13:49:40ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.27.12
 PERMIT NO.: 12070697
 ADDRESS: 2400 SOUTH DIXIE HIGHWAY
 CONTRACTOR/CONTACT: LAZARO MARTINEZ
 TELEPHONE NO.: 305.418.8772
 SCOPE OF REVIEW: CONVERSION OF TWO EXISTING BATHROOMS
 TO ADA BATHROOMS, SAME LOCATION. NEW MOP SINK, NEW
 WATER FOUNTAIN.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. A UNITY OF TITLE SHALL BE RECORDED IN THE PUBLIC
 RECORDS OF PALM BEACH COUNTY TO COMBINE THE TWO (2)
 LOTS. AN APPLICATION FOR A UNITY OF TITLE SHALL BE
 OBTAINED FROM, AND SUBMITTED TO, VINCE NOEL, CITY
 SURVEYOR, IN THE CITY'S ENGINEERING SERVICE'S
 DEPARTMENT (PHONE: 561-494-1096).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-07-25 Cont ID  
Sent By jroach Date 2012-07-25 Time 15:28 Rev Time 0.00
Received By jroach Date 2012-07-25 Time 14:12 Sent To  
Notes
2012-07-25 15:28:50ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.25.12
 PERMIT NO.: 12070697
 ADDRESS: 2400 SOUTH DIXIE HIGHWAY
 CONTRACTOR/CONTACT: LAZARO MARTINEZ
 TELEPHONE NO.: 305.418.8772
 SCOPE OF REVIEW: CONVERSION OF TWO EXISTING BATHROOMS
 TO ADA BATHROOMS, SAME LOCATION. NEW MOP SINK, NEW
 WATER FOUNTAIN.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. A UNITY OF TITLE SHALL BE RECORDED IN THE PUBLIC
 RECORDS OF PALM BEACH COUNTY TO COMBINE THE TWO (2)
 LOTS. AN APPLICATION FOR A UNITY OF TITLE SHALL BE
 OBTAINED FROM, AND SUBMITTED TO, VINCE NOEL, CITY
 SURVEYOR, IN THE CITY'S ENGINEERING SERVICE'S
 DEPARTMENT (PHONE: 561-494-1096).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved