Plan Review Details - Permit 12070653
Plan Review Stops For Permit 12070653
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-08-07 Cont ID  
Sent By jwitmer Date 2012-08-07 Time 16:13 Rev Time 0.00
Received By jwitmer Date 2012-07-30 Time 13:47 Sent To  
Notes
2012-08-07 12:54:231. SHEET A9.03 (01) MENS & WOMENS ROOMS WILL BE
 REQUIRED TO BE A MINIMUM OF 7'-1" WIDE TO ACHIVE THE
 REQUIRED 5' CLEAR SPACE FOR THE WATER CLOSET.
 FBC ACCESSIBILITY CODE 2010 604.3.1 THE LAVATORY WILL
 NOT BE PERMITTED TO BE IN THE 5' SPACE.
 FBC ACCESSIBILITY CODE 2010 604.3.2

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-08-13 Cont ID  
Sent By rlecky Date 2012-08-13 Time 11:19 Rev Time 0.00
Received By rlecky Date 2012-08-13 Time 11:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-08-10 Cont ID  
Sent By wjolin Date 2012-08-10 Time 13:14 Rev Time 0.00
Received By wjolin Date 2012-08-10 Time 13:00 Sent To  
Notes
2012-08-10 13:14:011100 NORTHPOINT PARKWAY
 PERMIT #12070653
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET E3-1: PROVIDE FIRE ALARM NOTIFICATION APPLIANCES
 IN ALL PUBLIC AND COMMON USE AREAS SUCH AS BREAK #120,
 RESTROOM #130, RESTROOM #162, ETC.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-30 Cont ID  
Sent By hmoser Date 2012-08-30 Time 14:42 Rev Time 0.00
Received By hmoser Date 2012-07-24 Time 16:15 Sent To  
Notes
2012-07-27 16:15:46DIGITAL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-08-30 Cont ID  
Sent By hmoser Date 2012-08-30 Time 14:39 Rev Time 0.00
Received By hmoser Date 2012-08-30 Time 14:39 Sent To  
Notes
2012-08-30 14:42:05PASS PROVISO
 REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-08-07 Cont ID  
Sent By lwagner Date 2012-08-07 Time 14:38 Rev Time 0.00
Received By lwagner Date 2012-08-07 Time 12:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2012-08-30 Cont ID  
Sent By hmoser Date 2012-08-30 Time 14:42 Rev Time 0.00
Received By hmoser Date 2012-08-30 Time 14:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-08-16 Cont ID  
Sent By eschneid Date 2012-08-16 Time 14:21 Rev Time 0.75
Received By eschneid Date 2012-08-16 Time 14:21 Sent To  
Notes
2012-08-16 14:22:12PERMIT VALUE OVER PAST YEAR IS LESS THAN 50% OF THE
 STRUCTURE VALUE.
  
 THE NEW ROOFTOP MECHANICAL EQUIPMENT IS SCREENED BEHIND
 A PARAPET.
  