Plan Review Details - Permit 12070653
| Plan Review Stops For Permit 12070653 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2012-08-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-08-07 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-07-30 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2012-08-07 12:54:23 | 1. SHEET A9.03 (01) MENS & WOMENS ROOMS WILL BE | | | REQUIRED TO BE A MINIMUM OF 7'-1" WIDE TO ACHIVE THE | | | REQUIRED 5' CLEAR SPACE FOR THE WATER CLOSET. | | | FBC ACCESSIBILITY CODE 2010 604.3.1 THE LAVATORY WILL | | | NOT BE PERMITTED TO BE IN THE 5' SPACE. | | | FBC ACCESSIBILITY CODE 2010 604.3.2 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-08-13 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-08-13 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-08-13 |
Time |
11:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2012-08-10 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-08-10 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-08-10 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2012-08-10 13:14:01 | 1100 NORTHPOINT PARKWAY | | | PERMIT #12070653 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET E3-1: PROVIDE FIRE ALARM NOTIFICATION APPLIANCES | | | IN ALL PUBLIC AND COMMON USE AREAS SUCH AS BREAK #120, | | | RESTROOM #130, RESTROOM #162, ETC. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-08-30 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2012-08-30 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2012-07-24 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2012-07-27 16:15:46 | DIGITAL |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2012-08-30 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2012-08-30 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2012-08-30 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2012-08-30 14:42:05 | PASS PROVISO | | | REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2012-08-07 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2012-08-07 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2012-08-07 |
Time |
12:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2012-08-30 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2012-08-30 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2012-08-30 |
Time |
14:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2012-08-16 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2012-08-16 |
Time |
14:21 |
Rev Time |
0.75 |
| Received By |
eschneid |
Date |
2012-08-16 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2012-08-16 14:22:12 | PERMIT VALUE OVER PAST YEAR IS LESS THAN 50% OF THE | | | STRUCTURE VALUE. | | | | | | THE NEW ROOFTOP MECHANICAL EQUIPMENT IS SCREENED BEHIND | | | A PARAPET. | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |