Plan Review Details - Permit 12070649
Plan Review Stops For Permit 12070649
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-07-09 Cont ID  
Sent By jwitmer Date 2013-07-09 Time 14:01 Rev Time 0.00
Received By jwitmer Date 2013-07-09 Time 12:08 Sent To  
Notes
2013-07-09 14:11:06BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) PRODUCT APPROVALS FOR DOORS 105A & 110.
  
 2) PROVIDE SHOP DRAWING FOR FLOATING CEILING AND
 SOFFITS FOUND ON SHEET A1 & A6.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-02-15 Cont ID  
Sent By jwitmer Date 2013-02-15 Time 10:26 Rev Time 0.00
Received By jwitmer Date 2013-02-15 Time 10:26 Sent To  
Notes
2013-02-15 10:54:48BUILDING PLAN REVIEW
 PERMIT: 12070649
 ADD: 501 FERN ST
 CONT: AUTO BUILDERS
 TEL: (561)722-3956
  
 2007 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 FEB. 15/ 2013
 ACTION: DENIED
  
 1) ADDITIONAL INFORMATION IS REQUIRED. THE SCOPE OF THE
 PERMIT APPEARS TO HAVE CHANGED, THE PERMIT APPLICATION
 UNDER THE DESCRIPTION OFPROJECT, DEMOLITION, STRUCTURAL
 STEEL WORK SHELL ONLY. THE PLANS NOW HAVE A PLUMBING,
 ELECTRICAL & MECHANICAL SHEETS, NEW DETAILS FOR A
 MEZZANINE LEVEL. THE CONTRACTOR TO UPDATE THE SCOPE OF
 WORK NO LONGER A SHELL, INCREASE THE VALUE OF THE
 PERMIT, AND IS THIS A CHANGE IN OCCUPANCY, PROVIDE THE
 TRYPE OF SERVICES WILL TAKE PLACE IN THIS BUILDING.
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 2) PROVIDE A KEY PLAN AS TO WHERE THIS SPACE IS LOCATED
 WITHIN THE LAYOUT OF THE BUILDING, PROVIDE THE TYPE OF
 OCCUPANCY WILL OCCUPY THIS TENANT SPACE. PROVIDE THE
 MINIMUM BUILDING TYPE PER 2010 FBC-B TABLE 503. IS THIS
 STRUCTURE FIRE SPRINKLERED OR NOT, IF SPRINKLERED A
 LAYOUT OF SPRINKLERS OCCUPANCY TYPE AND OCCUPANT LOAD,
 LIFE SAFETY PLANS WITH EGRESS, 107.3.5.1 MINIMUM PLAN
 REVIEW CRITERIA FOR COMMERCIAL BUILDINGS.
  
 3) DISCREPANCY, THERE ARE TWO SETS OF STRUCTURAL SHEETS
 WITH TWO COMPLETELY DIFFERNT SCOPE OF WORK EACH HAVING
 A S1 & S2 SHEET NAME? THE CONTRACTOR OF RECORD WILL
 NEED TO REVIEW DOCUMENTS TO SEE IF THE SCOPE HAS
 CHANGED OR IF THE SHEETS SHOULD BE NUMERED S3 & S4?
 COALATE PLANS. WHEN RESUBMITTING PLANS PLEASE INSERT
 THE NEW SHEETS & REMOVE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 4) SHEET S-1 DATED JULY 17. 2012 INDICATES WIND DESIGN
 PRESSURES WITH A "B" EXPOSURE, SHOULD BE A "C" WITH
 PRESSURES BUT TO DATE NO PRODUCT APPROVAL WERE
 SUBMITTED FOR:
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) SINCE THERE ARE NO ARCHITECTURAL SHEETS IT IS NOT
 CLEAR WHAT IS NEW AND WHAT IS EXISTING, PLEASE TO AWARE
 OF 2010 ACCESSIBILITY CODE AND DISPROPORTIONATE COST.
  
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 7)) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 8) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 A MEETING WITH THE CONTRACTOR BEFORE THE PLANS ARE
 RESUBMITTED SHOULD BE ARRANGED TO BE ABLE TO REVIEW THE
 PLANS, TO DATE IT IS NOT CLEAR THE INTENT OF THIS
 PERMIT SINCE THE SCOPE OF THE PERMIT SEEMS TO HAVE
 CHANGED!!!!!!!!!!!!!!!!!
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-01 Cont ID  
Sent By jwitmer Date 2012-08-01 Time 14:26 Rev Time 0.00
Received By jwitmer Date 2012-08-01 Time 14:26 Sent To  
Notes
2012-08-01 14:32:28BUILDING PLAN REVIEW
 PERMIT: 12070649
 ADD: 501 FERN ST
 CONT: AUTO BUILDERS
 TEL: (561)722-3956
  
 2007 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE WORK TO BE
 COMPLETED UNDERTHIS PERMIT IS LOCATED AT 501 FERN ST.
 THE LOCATION APPEARS TO BE LOCATED AT 515 FERN ST. SEE
 PLUMBING COMMENT, A DIFFERENT PCN NUMBER. EITHER THE
 PERMIT APPLICATION NEEDS TO HAVE THE ADDRESS AND PCN
 NUMBER CORRECTED OR A UNITY OF TITLE WILL BE REQUIRED
 TO UNIFY THE TWO LOTS INTO ONE LOT.
  
 NOTE : A SEPERATE ROOFING PERMIT WILL BE REQUIRED. JW
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-07-31 Cont ID  
Sent By dharvey Date 2013-07-31 Time 12:49 Rev Time 0.00
Received By dharvey Date 2013-07-31 Time 10:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-02-25 Cont ID  
Sent By rlecky Date 2013-02-25 Time 11:34 Rev Time 0.00
Received By rlecky Date 2013-02-25 Time 11:34 Sent To  
Notes
2013-02-25 11:36:54 
 12070649
 501 FERN ST # C1
 NEW FOOD MARKET
  
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH
 PROTECTION, HIGH-LEG MARKING, PANELBOARDS AND THE MAIN
 DISCONNECTING MEANS. REVISE PLANS TO SHOW THE SERVICE
 VOLTAGE BEING PROVIDED BY THE UTILITY. NEC 110.22,
 110.16, 110.22
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLANS SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 RECEPTACLES ON ROOF REQUIRE GFCI PROTECTION. NEC
 210.8(B)
  
 RISER PLAN APPEARS TO BE MISSING PANEL SLP? NEC 215.5
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA,
 CABLE TV, POS, AND FIRE ALARM SYSTEMS.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-07-24 Cont ID  
Sent By rlecky Date 2012-07-24 Time 11:04 Rev Time 0.00
Received By rlecky Date 2012-07-24 Time 10:13 Sent To  
Notes
2012-07-24 11:05:4012070649
 501 FERN ST # C1
 COMMERCIAL SHELL
  
 VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING
 ARE SIX OR LESS AND GROUPED IN ONE LOCATION.
 NEC 230.2, 230.71, 230.72
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 NEW SERVICE AND SWITCH GEAR. NEC 110.9, 110.10
  
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2012-08-02 Cont ID  
Sent By jwitmer Date 2012-08-02 Time 16:27 Rev Time 0.00
Received By jwitmer Date 2012-08-02 Time 16:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-07-09 Cont ID  
Sent By wjolin Date 2013-07-09 Time 17:15 Rev Time 0.00
Received By wjolin Date 2013-07-09 Time 16:49 Sent To  
Notes
2013-07-09 17:15:19501 FERN STREET
 PERMIT #12070649
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE PANIC HARDWARE ON ALL EXIT DOORS.
  
 COOKING APPLIANCES CAPABLE OF PRODUCING SMOKE OR
 GREASE-LADEN VAPORS SHALL BE PROTECTED WITH A CLASS I
 MECHANICAL EXHAUST HOOD EQUIPPED WITH AN AUTOMATIC
 WET-CHEMICAL FIRE SUPPRESSION SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-02-25 Cont ID  
Sent By wjolin Date 2013-02-25 Time 14:11 Rev Time 0.00
Received By wjolin Date 2013-02-25 Time 14:02 Sent To  
Notes
2013-02-25 14:11:45501 FERN STREET
 PERMIT #12070649
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
  
 DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 THE CURRENT PLANS WERE SUBMITTED WITHOUT A LIFE SAFETY
 PLAN AND OCCUPANCY DECLARATION; THEREFORE, A COMPLETE
 AND THOROUGH PLAN REVIEW CANNOT BE PERFORMED AT THIS
 TIME.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
2013-02-07 09:08:50NEW SHEETS SUBMITTED. JG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-07-31 Cont ID  
Sent By wjolin Date 2012-07-31 Time 09:31 Rev Time 0.00
Received By wjolin Date 2012-07-31 Time 09:23 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-02-13 Cont ID  
Sent By lwagner Date 2013-02-13 Time 13:07 Rev Time 0.00
Received By lwagner Date 2013-02-13 Time 12:40 Sent To  
Notes
2013-02-13 13:07:57SEPARATE GAS PERMIT REQUIRED
2013-02-07 09:06:58NEW SHEETS SUBMITTED. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-07-31 Cont ID  
Sent By dharvey Date 2013-07-31 Time 12:49 Rev Time 0.00
Received By dharvey Date 2013-07-08 Time 09:13 Sent To  
Notes
2013-07-09 09:13:39C06

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-08 Cont ID  
Sent By hmoser Date 2013-03-08 Time 15:35 Rev Time 0.00
Received By hmoser Date 2013-02-06 Time 09:14 Sent To  
Notes
2013-02-07 09:15:21SENT TO C9 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-02 Cont ID  
Sent By jwitmer Date 2012-08-02 Time 16:27 Rev Time 0.00
Received By jwitmer Date 2012-07-19 Time 10:56 Sent To  
Notes
2012-07-23 10:56:46SENT TO B22 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-07-23 Cont ID  
Sent By hmoser Date 2013-07-23 Time 14:40 Rev Time 0.00
Received By hmoser Date 2013-07-23 Time 10:48 Sent To  
Notes
2013-07-23 14:40:51PASS PROVISO
 PROVIDE ENERGY CALCULATIONS BY 1ST INSPECTION.
 HOODS ARE NOT PART OF THIS REVIEW. SEPARATE
 APPLICATION, PLANS ARE REQUIRED FOR HOOD PERMIT
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-03-08 Cont ID  
Sent By hmoser Date 2013-03-08 Time 15:35 Rev Time 0.00
Received By hmoser Date 2013-03-08 Time 14:57 Sent To  
Notes
2013-03-08 15:35:25PLANS DENIED
 1) PROVIDE EQUIPMENT SCHEDULE WITH MODEL NUMBER
 ON THE PLANS. PER SECTION 107 FBC 1210
 2) REFER TO TABLE 403.4 TOILET ROOMS PUBLIC. 2010 (M)
 3) PROVIDE ENERGY CALCULATIONS WITH THE PLANS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
2013-02-07 09:07:38NEW SHEETS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 3 Status P Date 2013-07-22 Cont ID  
Sent By lwagner Date 2013-07-22 Time 10:33 Rev Time 0.00
Received By lwagner Date 2013-07-17 Time 13:41 Sent To  
Notes
2013-07-22 10:06:52***PROVISO***
 DISHWASHERS WILL REQUIRE HOT WATER UNLESS DOCUMENTED
 OTHERWISE BY MANUFACTURER.
  
 WHILE THE PLANS MEET THE REQUIREMENTS OF THE FLORIDA
 PLUMBING CODE, THE FLORIDA DIVISION OF HOTELS AND
 RESTAURANTS MAY HAVE OTHER REQUIREMENTS. SUCH AS HAND
 SINKS AND THREE COMPARTMENT SINKS, ETC.
 HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/HR/

Review Stop P PLUMBING
Rev No 2 Status F Date 2013-02-13 Cont ID  
Sent By lwagner Date 2013-02-13 Time 12:40 Rev Time 0.00
Received By lwagner Date 2013-02-12 Time 15:13 Sent To  
Notes
2013-02-13 10:15:32FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
  
 1. THE PLANS DO NOT INDICATE THE BUILDING OCCUPANCY
 TYPE AND OCCUPANT LOAD TO DETERMINE THE REQUIRED
 FIXTURES AND AMOUNT OF FIXTURES.
 FBC 2010 PLUMBING 403.1
  
 2. IF THIS PROJECT IS FOOD SERVICE, A SERVICE SINK WILL
 BE REQUIRED.
 FBC 2010 PLUMBING 403.1
  
 3. DRINKING FOUNTAINS WILL BE REQUIRED - WITH THE
 EXCEPTION 410.1 WHERE WATER IS SERVED IN RESTAURANTS,
 DRINKING FOUNTAINS SHALL NOT BE REQUIRED.
  
 NOTE
 THE TOTAL VALUE OF THIS PROJECT APPEARS TO BE TOO LOW.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
2013-02-07 09:06:11NEW SHEETS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-07-25 Cont ID  
Sent By lwagner Date 2012-07-25 Time 14:40 Rev Time 0.00
Received By lwagner Date 2012-07-25 Time 09:27 Sent To  
Notes
2012-07-25 14:44:08ADDRESS FOR THIS PROJECT APPEARS TO BE INCORRECT?
 GIS SHOWS ADDRESS AS 515 FERN ST PCN-74434321010220080
 ?

Review Stop Z ZONING
Rev No 3 Status P Date 2013-07-24 Cont ID  
Sent By aaponte Date 2013-07-24 Time 08:59 Rev Time 0.00
Received By aaponte Date 2013-07-24 Time 08:59 Sent To  
Notes
2013-07-22 10:46:087/22/13

Review Stop Z ZONING
Rev No 2 Status F Date 2013-02-21 Cont ID  
Sent By aaponte Date 2013-02-21 Time 14:10 Rev Time 0.00
Received By aaponte Date 2013-02-21 Time 14:10 Sent To  
Notes
2013-02-21 14:12:141. SURVEY REQUIRED TO INDICATE THE LOCATION OF THE
 SUBJECT BUILDING.
 2. IF NEW WINDOWS ADDED ELEVATIONS SHALL BE SUBMITTED
 TO CONFIRM COMPLIANCE WITH MINIMUM TRANSPARENCY
 REQUIREMENTS.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-08-02 Cont ID  
Sent By aaponte Date 2012-08-02 Time 14:43 Rev Time 0.00
Received By aaponte Date 2012-08-02 Time 14:43 Sent To  
Notes
2012-08-02 15:00:551. PLEASE PROVIDE A SURVEY OF THE PROPERTY INDICTING
 THE BUILDING SUBJECT OF WORK.
 2. PLEASE INDICATE ON THE ELEVATIONS ANY ADDITION OR
 REMOVAL OF WINDOWS OR DOORS TO ENSURE COMPLIANCE WITH
 MINIMUM TRNASPARENCY REQUIREMENTS ALOGN FERN STREET.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.