Plan Review Details - Permit 12070630
Plan Review Stops For Permit 12070630
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-08-09 Cont ID  
Sent By shill Date 2012-08-09 Time 16:14 Rev Time 0.00
Received By shill Date 2012-08-09 Time 16:14 Sent To  
Notes
2012-08-09 16:17:59***PROVISO***
 ***ISSUED AT CONTRACTOR'S / OWNER'S RISK***
  
  
 PROVIDE LETTER WITH WIND DESIGN CRITERIA FROM ENGINEER
 (MIN 170 EXPOSURE C) AT INSPECTION
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-08 Cont ID  
Sent By shill Date 2012-08-08 Time 10:22 Rev Time 0.00
Received By shill Date 2012-08-06 Time 13:26 Sent To  
Notes
2012-08-08 10:22:24****CORRECTIONS****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PLEASE REVISE SITE PLAN TO INCLUDE LOCATION OF
 PROPOSED IMPROVEMENT, FBC 106.
  
 2. REGARDING THE ENGINEERING - INCLUDE WIND DESIGN
 CRITERIA, FBC RESIDENTIAL 301. THIS CAN BE SUBMITTED IN
 LETTER FROM VIA EMAIL FROM THE ENGINEER, ON THE
 ENGINEER'S LETTERHEAD WITH SEAL. AN ORIGINAL WILL BE
 REQUIRED AT FIRST INSPECTION. ALTERNATIVELY, CONTRACTOR
 CAN SUBMIT AN ORIGINAL LETTER WHEN RESUBMITTING TO
 ADDRESS ITEM #1.
  
 3. REGARDING ROOF PERMIT DOCUMENTS - SEE ITEM # 7 OF
 THE ROOF NOA, RAS CALCULATIONS PREPARED BY AN
 ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT
 REQUIRED FOR ENHANCED FASTENING.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2012-07-30 Cont ID  
Sent By rlecky Date 2012-07-30 Time 07:18 Rev Time 0.00
Received By rlecky Date 2012-07-30 Time 07:15 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2012-07-27 Cont ID  
Sent By fmittner Date 2012-07-27 Time 11:51 Rev Time 0.00
Received By fmittner Date 2012-07-27 Time 11:51 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2012-07-26 Cont ID  
Sent By fmittner Date 2012-07-26 Time 10:15 Rev Time 0.00
Received By fmittner Date 2012-07-26 Time 10:15 Sent To  
Notes
2012-07-26 10:16:28REQUIRES COA, SURVEY. FHM SPOKE TO CONTRACTOR TRENT
 HASTON 7/26/12. WILL PROVIDE MISSING INFORMATION WITHIN
 24 HRS. PERMIT UPSTAIRS WITH FHM, WAITING ON
 RESOLUTION.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-08 Cont ID  
Sent By shill Date 2012-08-08 Time 10:22 Rev Time 0.00
Received By shill Date 2012-07-18 Time 11:25 Sent To  
Notes
2012-07-20 11:25:58EXPEDITED
 IN ZONING BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2012-07-27 Cont ID  
Sent By fmittner Date 2012-07-27 Time 11:51 Rev Time 0.00
Received By fmittner Date 2012-07-20 Time 13:19 Sent To  
Notes
2012-07-20 13:19:347/20/12 - GAVE TO FM - MD.