Plan Review Details - Permit 12070599
Plan Review Stops For Permit 12070599
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-09-10 Cont ID  
Sent By lmartine Date 2012-09-10 Time 09:48 Rev Time 0.00
Received By lmartine Date 2012-09-10 Time 09:48 Sent To  
Notes
2012-09-10 09:49:29PLANS STAMPED BY COUNTY FOR IMPACT FEES. ZERO DUE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-08-29 Cont ID  
Sent By jwitmer Date 2012-08-29 Time 16:42 Rev Time 0.00
Received By jwitmer Date 2012-08-29 Time 16:42 Sent To  
Notes
2012-08-29 16:43:15BUILDING PLAN REVIEW
 PERMIT: 11050812
 ADD: 815 33RD ST
 CONT: TO BE DETERMINED
 TEL: (561)839-0700
  
 2010 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
  
 2010/09 FBC-B 313.2.2 GROUP DAY CARE HOME. A GROUP DAY
 CARE HOME IS A DAY-CARE HOME IN WHICH AT LEAST SEVEN
 BUT NOT MORE THAN 12 CLIENTS RECEIVE CARE, MAINTENANCE,
 AND SUPERVISION BY OTHER THAN THEIR RELATIVE(S) OR
 LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS PER DAY WITH
 NO MORE THAN THREE CLIENTS INCAPABLE OF
 SELF-PRESERVATION.
  
 BUILDING PROVISO:
  
 1) 436.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH SHALL BE
 SUCH THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE
 CLOSET.
  
 2) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK SHALL
 BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR FROM
 THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE SHALL
 BE READILY ACCESSIBLE TO THE STAFF.
  
 3) 436.4 DOOR CLOSURE. ANY EXIT DOOR DESIGNED TO BE
 NORMALLY CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY
 WITH SECTION 715.3.
  
 4) PLANS DO NOT MAKE IT CLEAR IF THE THREE BEDROOMS ARE
 TO BE PART OF THE DAY CARE HOME, IF SO PLEASE COMPLY
 WITH :
  
 436.10.5 SMOKE DETECTION SYSTEMS.
  
 436.10.5.1 SINGLE-STATION SMOKE ALARMS INSTALLED IN
 ACCORDANCE WITH THE HOUSEHOLD FIRE WARNING EQUIPMENT
 REQUIREMENTS OF CHAPTER 2 OF NFPA 72 SHALL BE INSTALLED
 WITHIN DAY CARE HOMES.
  
 EXCEPTION: SYSTEM SMOKE DETECTORS INSTALLED IN
 ACCORDANCE WITH NFPA 72 AND ARRANGED TO FUNCTION IN THE
 SAME MANNER SHALL BE PERMITTED.
  
 436.10.5.2 WHERE THE DAY CARE HOME IS LOCATED WITHIN A
 BUILDING OF ANOTHER OCCUPANCY, ANY CORRIDORS SERVING
 THE DAY CARE HOME SHALL BE PROVIDED WITH A COMPLETE
 SMOKE DETECTION SYSTEM INSTALLED IN ACCORDANCE WITH
 NFPA 72.
  
 436.10.5.3 SINGLE-STATION SMOKE ALARMS SHALL BE POWERED
 BY THE BUILDING ELECTRICAL SYSTEM.
  
 436.10.5.4 SINGLE-STATION SMOKE ALARMS SHALL BE
 PROVIDED IN ALL ROOMS USED FOR SLEEPING.
  
 436.10.5.5 WHERE TWO OR MORE SMOKE ALARMS ARE REQUIRED
 WITHIN A LIVING UNIT, SUITE OF ROOMS, OR SIMILAR AREA,
 THEY SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE
 ALARM SHALL CAUSE ALL SMOKE ALARMS WITHIN THE LIVING
 UNIT, SUITE OF ROOMS OR SIMILAR AREA TO SOUND.
  
 436.10.5.5.1 THE ALARMS SHALL SOUND ONLY WITHIN AN
 INDIVIDUAL LIVING UNIT, SUITE OF ROOMS OR SIMILAR AREA
 AND SHALL NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM.
 REMOTE ANNUNCIATION SHALL BE PERMITTED.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-30 Cont ID  
Sent By jwitmer Date 2012-07-30 Time 10:09 Rev Time 0.00
Received By jwitmer Date 2012-07-30 Time 10:00 Sent To  
Notes
2012-07-30 10:08:49BUILDING PLAN REVIEW
 PERMIT: 11050812
 ADD: 815 33RD ST
 CONT: TO BE DETERMINED
 TEL: (561)839-0700
  
 2010 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
  
 2010/09 FBC-B 313.2.2 GROUP DAY CARE HOME. A GROUP DAY
 CARE HOME IS A DAY-CARE HOME IN WHICH AT LEAST SEVEN
 BUT NOT MORE THAN 12 CLIENTS RECEIVE CARE, MAINTENANCE,
 AND SUPERVISION BY OTHER THAN THEIR RELATIVE(S) OR
 LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS PER DAY WITH
 NO MORE THAN THREE CLIENTS INCAPABLE OF
 SELF-PRESERVATION.
  
 1ST REVIEW
  
 1) 436.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH SHALL BE
 SUCH THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE
 CLOSET.
  
 2) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK SHALL
 BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR FROM
 THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE SHALL
 BE READILY ACCESSIBLE TO THE STAFF.
  
 3) 436.4 DOOR CLOSURE. ANY EXIT DOOR DESIGNED TO BE
 NORMALLY CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY
 WITH SECTION 715.3.
  
 4) PLANS DO NOT MAKE IT CLEAR IF THE THREE BEDROOMS ARE
 TO BE PART OF THE DAY CARE HOME, IF SO PLEASE COMPLY
 WITH :
  
 436.10.5 SMOKE DETECTION SYSTEMS.
  
 436.10.5.1 SINGLE-STATION SMOKE ALARMS INSTALLED IN
 ACCORDANCE WITH THE HOUSEHOLD FIRE WARNING EQUIPMENT
 REQUIREMENTS OF CHAPTER 2 OF NFPA 72 SHALL BE INSTALLED
 WITHIN DAY CARE HOMES.
  
 EXCEPTION: SYSTEM SMOKE DETECTORS INSTALLED IN
 ACCORDANCE WITH NFPA 72 AND ARRANGED TO FUNCTION IN THE
 SAME MANNER SHALL BE PERMITTED.
  
 436.10.5.2 WHERE THE DAY CARE HOME IS LOCATED WITHIN A
 BUILDING OF ANOTHER OCCUPANCY, ANY CORRIDORS SERVING
 THE DAY CARE HOME SHALL BE PROVIDED WITH A COMPLETE
 SMOKE DETECTION SYSTEM INSTALLED IN ACCORDANCE WITH
 NFPA 72.
  
 436.10.5.3 SINGLE-STATION SMOKE ALARMS SHALL BE POWERED
 BY THE BUILDING ELECTRICAL SYSTEM.
  
 436.10.5.4 SINGLE-STATION SMOKE ALARMS SHALL BE
 PROVIDED IN ALL ROOMS USED FOR SLEEPING.
  
 436.10.5.5 WHERE TWO OR MORE SMOKE ALARMS ARE REQUIRED
 WITHIN A LIVING UNIT, SUITE OF ROOMS, OR SIMILAR AREA,
 THEY SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE
 ALARM SHALL CAUSE ALL SMOKE ALARMS WITHIN THE LIVING
 UNIT, SUITE OF ROOMS OR SIMILAR AREA TO SOUND.
  
 436.10.5.5.1 THE ALARMS SHALL SOUND ONLY WITHIN AN
 INDIVIDUAL LIVING UNIT, SUITE OF ROOMS OR SIMILAR AREA
 AND SHALL NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM.
 REMOTE ANNUNCIATION SHALL BE PERMITTED.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-08-27 Cont ID  
Sent By rlecky Date 2012-08-27 Time 12:58 Rev Time 0.00
Received By rlecky Date 2012-08-27 Time 12:40 Sent To  
Notes
2012-08-27 12:57:57PROVISO:
 RECEPTACLES IN THE BATHROOMS AND KITCHEN AREAS SHALL BE
 GFCI PROTECTED. NEC 210.8
 ALL RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.14
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-07-23 Cont ID  
Sent By rlecky Date 2012-07-23 Time 17:14 Rev Time 0.00
Received By rlecky Date 2012-07-23 Time 16:54 Sent To  
Notes
2012-07-23 17:20:2512070599
 815 33RD ST.
 DAYCARE
  
 PLEASE PROVIDE AN ELECTRICAL RECEPTICAL PLAN FOR THE
 FACILITY. NEC 215.5
 A SMOKE ALARM IS REQUIRED. FBC 436.7.2
 RECEPTACLES IN THE BATHROOMS AND KITCHEN AREAS SHALL BE
 GFCI PROTECTED. NEC 210.8
 ALL RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.14
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-08-26 Cont ID  
Sent By wjolin Date 2012-08-26 Time 17:46 Rev Time 0.00
Received By wjolin Date 2012-08-26 Time 17:25 Sent To  
Notes
2012-08-26 17:36:56815 33RD STREET
 PERMIT #12070599
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ***THIS IS A CHANGE OF OCCUPANCY CLASSIFICATION FROM
 FAMILY DAY-CARE HOME (3-6 CHILDREN) TO GROUP DAY-CARE
 HOME (7-12 CHILDREN)***
  
 THERE SHALL BE NO MORE THAN 3 CHILDREN THAT ARE
 24-MONTHS OF AGE OR YOUNGER, THAT WILL BE CARED FOR AT
 ANY ONE TIME.
  
 PROVIDE ESCAPE WINDOWS FOR ROOM #1, #2 AND #3.
 (1) SUCH WINDOWS SHALL BE OPERABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20-INCHES IN WIDTH, 24-INCHES
 IN HEIGHT, AND 5.7 SQ.FT. IN AREA.
 (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN
 44-INCHES ABOVE THE FLOOR.
 (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID,
 WITH A WIDTH AND HEIGHT THAT PROVIDES NOT LESS THAN THE
 REQUIRED 5.7 SQ.FT. OPENING AND A DEPTH OF NOT LESS
 THAN 20-INCEHS TO PASS FULLY THROUGH THE OPENING.
  
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN
 BUILDING PRIOR TO FINAL FIRE INSPECTION.
  
 EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL
 DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM.
  
 FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY
 BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A
 COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN
 A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL
 BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO
 ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED
 CLEAR OF OBSTRUCTIONS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-07-23 Cont ID  
Sent By wjolin Date 2012-07-23 Time 10:46 Rev Time 0.00
Received By wjolin Date 2012-07-23 Time 10:05 Sent To  
Notes
2012-07-23 10:46:56815 33RD STREET
 PERMIT #12070599
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ***THIS IS A CHANGE OF OCCUPANCY CLASSIFICATION FROM
 FAMILY DAY-CARE HOME (3-6 CHILDREN) TO GROUP DAY-CARE
 HOME (7-12 CHILDREN)***
  
 NO ADDRESS INDICATE ON THE PLANS.
  
 INDICATE THE MAXIMUM NUMBER OF CHILDREN THAT ARE
 24-MONTHS OF AGE OR YOUNGER, THAT WILL BE CARED FOR AT
 ANY ONE TIME.
  
 INDICATE THE STAFF TO CHILDREN RATIO.
  
 INDICATE THE LOCATION OF ALL PORTABLE FIRE
 EXTINGUISHERS AND SMOKE ALARMS. EXTINGUISHERS SHALL
 HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE TAGGED BY
 A LICENSED FIRE EXTINGUISHER COMPANY. SMOKE ALARMS ARE
 REQUIRED IN ALL ROOMS USED FOR SLEEPING PURPOSES.
  
 PROVIDE THE FOLLOWING INFORMATION ON THE PLANS:
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN
 BUILDING PRIOR TO FINAL FIRE INSPECTION.
  
 EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL
 DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM.
  
 FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY
 BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A
 COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN
 A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL
 BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO
 ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED
 CLEAR OF OBSTRUCTIONS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2012-07-26 Cont ID  
Sent By fmittner Date 2012-07-26 Time 10:43 Rev Time 0.00
Received By fmittner Date 2012-07-26 Time 10:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-09-10 Cont ID  
Sent By lmartine Date 2012-09-10 Time 09:49 Rev Time 0.00
Received By lmartine Date 2012-09-07 Time 08:53 Sent To  
Notes
2012-09-10 08:53:47LM

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-06 Cont ID  
Sent By hmoser Date 2012-09-06 Time 12:43 Rev Time 0.00
Received By hmoser Date 2012-08-23 Time 17:15 Sent To  
Notes
2012-08-23 17:22:23B19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-21 Cont ID  
Sent By hmoser Date 2012-08-21 Time 12:07 Rev Time 0.00
Received By hmoser Date 2012-07-18 Time 14:51 Sent To  
Notes
2012-07-19 14:54:38B17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-09-10 Cont ID  
Sent By lmartine Date 2012-09-10 Time 09:49 Rev Time 0.00
Received By lmartine Date 2012-09-10 Time 09:49 Sent To  
Notes
2012-09-10 09:50:47PLANS STAMPED BY COUNTY, ZERO DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-07-30 Cont ID  
Sent By jwitmer Date 2012-07-30 Time 10:11 Rev Time 0.00
Received By jwitmer Date 2012-07-30 Time 10:10 Sent To  
Notes
2012-07-30 10:11:22BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2012-09-06 Cont ID  
Sent By hmoser Date 2012-09-06 Time 12:42 Rev Time 0.00
Received By hmoser Date 2012-09-06 Time 12:42 Sent To B
Notes
2012-09-06 12:42:21CALLED CAROLIN SHE TOLD ME THERE IS NO AIR CONDITIONING
 WORK BEING DONE.
 SHE HAS WINDOW UNITS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-08-21 Cont ID  
Sent By hmoser Date 2012-08-21 Time 12:07 Rev Time 0.00
Received By hmoser Date 2012-08-21 Time 12:05 Sent To  
Notes
2012-08-21 12:06:47NO MECHANICAL PLANS SUBMITTED.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-09-04 Cont ID  
Sent By lwagner Date 2012-09-04 Time 08:38 Rev Time 0.00
Received By lwagner Date 2012-08-30 Time 16:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-07-24 Cont ID  
Sent By lwagner Date 2012-07-24 Time 14:09 Rev Time 0.00
Received By lwagner Date 2012-07-24 Time 12:55 Sent To  
Notes
2012-07-24 13:32:34FBC PLUMBING REVIEW #1
 DENIED:
  
 1. PLUMBING 403.1 MINIMUM FACILITIES - DAYCARE
 FACILITIES REQUIRE A SERVICE SINK (OR LAUNDRY TUB). IF
 ONE IS EXISTING, PLEASE INDICATE THE LOCATION ON THE
 PLAN.
  
 2. THE BATHROOM DOES NOT APPEAR TO MEET THE FLORIDA
 ACCESSIBILITY CODE. HOWEVER, THE COST MAY BE
 DISPROPORTINATE TO THE OVERALL PROJECT.
  
 FBC EXISTING BUILDING CODE 2010 912.8 ACCESSIBILITY.
 EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR
 OCCUPANCY SHALL COMPLY WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 FBC ACCESSIBILITY 2010 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA.
  
 FBC ACCESSIBILITY 2010 202.4.2 ACCESSIBLE FEATURES IN
 THE EVENT OF DISPROPORTIONALITY. WHEN THE COST OF
 ALTERATIONS NECESSARY TO MAKE THE PATH OF TRAVEL TO THE
 ALTERED AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO
 THE COST OF THE OVERALL ALTERATION, THE PATH OF TRAVEL
 SHALL BE MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE
 MADE ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE
 COSTS. IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE
 ROUTE TO THE ALTERED AREA; (III) AT LEAST ONE
 ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2012-09-06 Cont ID  
Sent By mdekle Date 2012-09-06 Time   Rev Time 0.00
Received By mdekle Date 2012-09-06 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2012-07-31 Cont ID  
Sent By fmittner Date 2012-07-31 Time   Rev Time  
Received By mdekle Date 2012-07-31 Time   Sent To  
Notes
2012-07-31 13:29:16PLANNING: **** FAILED **** (PER A.V.)
 PLEASE RESPOND TO COMMENTS IN WRITING.
  
 IN ORDER FOR THE BUSINESS OWNER TO EXPAND (INCREASE THE
 NUMBER OF CHILDREN) THE OPERATION, THE BUSINESS OWNER
 MUST DEMONSTRATE COMPLIANCE WITH THE LARGE FAMILY
 DAY-CARE FACILITY REQUIREMENTS FOUND WITHIN ARTICLE IX
 SECTION 94-273 #19.2 (LARGE FAMILY CHILD CARE HOMES.
  
 THE CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS ARE AVAILABLE ONLINE AT WWW.MUNICODE.COM.
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME DIRECTLY.
  
 MURRIAH DEKLE, MPA
 PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved