Plan Review Details - Permit 12070466
Plan Review Stops For Permit 12070466
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-07-17 Cont ID  
Sent By wjolin Date 2012-07-17 Time 11:09 Rev Time 0.00
Received By wjolin Date 2012-07-17 Time 10:43 Sent To M
Notes
2012-07-17 11:03:241601 FORUM PLACE: SUITE #805
 PERMIT #12070466
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  