Plan Review Details - Permit 12070422
Plan Review Stops For Permit 12070422
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-07-20 Cont ID  
Sent By rlecky Date 2012-07-20 Time 10:01 Rev Time 0.00
Received By rlecky Date 2012-07-20 Time 09:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-07-14 Cont ID  
Sent By wjolin Date 2012-07-14 Time 20:10 Rev Time 0.00
Received By wjolin Date 2012-07-14 Time 20:10 Sent To E
Notes
2012-07-14 20:10:531711 WORTHINGTON ROAD - BUILDING "A" & "B"
 PERMIT #12070414 & #12070422
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO- SUBMIT REVISION WITH THE FOLLOWING
 INFORMATION*****
  
 SUBMIT CUTSHEETS FOR EQUIPMENT TO BE INSTALLED.
  
 PROVIDE A SMOKE DETECTOR IN THE ELECTRICAL ROOM HOUSING
 THE NAC POWER EXTENDER.
  
 EACH BUILDING SHALL BE ANNUNCIATED SEPARATELY. PROVIDE
 A GRAPHIC ANNUNCIATOR (OR SIMILAR), THAT WILL ALLOW
 EMERGENCY RESPONDERS TO QUICKLY IDENTIFY IF THE ALARM
 CONDITION IS LOCATED IN BUILDING "A" OR BUILDING "B."
  
 PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 NOTE: WHERE THE FIRE ALARM CIRCUITS ENTER OR EXIT
 BUILDINGS, THE CIRCUITS AND EQUIPMENT SHALL BE
 INSTALLED IN ACCORDANCE WITH THE NEC (NFPA 70) SECTION
 760.32.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-20 Cont ID  
Sent By hmoser Date 2012-07-20 Time 14:16 Rev Time 0.00
Received By hmoser Date 2012-07-14 Time 09:14 Sent To  
Notes
2012-07-14 09:14:31TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-07-20 Cont ID  
Sent By hmoser Date 2012-07-20 Time 14:16 Rev Time 0.00
Received By hmoser Date 2012-07-20 Time 14:16 Sent To  
Notes
***NONE***